Electric Valve Actuator
FA-33xx-741x
(FA42/6000)
for V H & VBD
JCI Regelungstechnik GmbH
Westendhof
3
♦
D-45143 Essen
Tel.: +49(0)201-2400-0
♦
Fax: +49(0)201-2400-351
www.johnsoncontrols.com
General:
This service and data information (in brief SDI) contains instructions for the safe installation and operation of
the FA-33xx-741x (FA42/6000) actuator. In the event of difficulties, which cannot be overcome with the aid of
this SDI please consult the supplier.
This SDI conforms to the relevant EN-safety standards and the appropriate regulations and directives of the
European Community.
When operating the valve actuators outside the Federal Republic of Germany, it is the responsibility of the
operator or system administrator to ensure that valid national control standards are met.
The manufacturer maintains all rights for technical changes and improvements at any time. Qualified
personnel (see below) are essential to the application of this SDI.
Operating personnel must receive instructions contained in this SDI.
Qualified personnel:
These are persons conversant with installation, mounting, commissioning, operation and service of the
product and in possession of the respective qualifications through their activities and functions, e.g.:
•
Instructors with obligation to supervise adherence to all operative regional and internal ordinances and
requirements.
•
Trainers or instructors on safety standards, maintenance and utilisation of adequate safety- and
protective operation equipment.
•
Trainers in first aid, etc. (See TRB 700).
Application:
Electric actuators FA-33xx-741x (FA42/6000) are intended for the regulation and can be combined with the
following valves:
VG8000N
PN 16, DN 100 to 150
VG8000H
PN 25, DN 100 to 150
VBD
PN 25, DN 80 to 150
Danger:
Safe operation of the valve is only ensured if the valve is installed, commissioned and serviced by qualified
personnel in compliance with warning references in this SDI. In addition, the general installation- and safety
regulations for pipelines, installation construction and the professional use of tools and safety equipment
must be guaranteed. Observe unconditionally during all work on the control valve. Ignoring this information
may cause physical or material damages.
Storage:
•
Storage temperature -40°C to +60°C, dry and free of dirt.
•
Do not damage the lacquer. The lacquer is a foundation intended only as a protection against corrosion
while in storage and during transport.
•
In rooms where moisture or condensation are present use heating or a drying agent to maintain a
moisture free atmosphere.
Transport:
•
Transport temperature -40°C to +60°C.
•
Protect against external forces (shock, Vibration etc.).
•
Do not damage the protective lacquer.
Actuator Installation site information:
The installation site should be easily accessible and provide sufficient room for service and removal of
actuators. Manual shut-off valves should be located up and downstream of the control valve, to facilitate
service and repairs without draining the piping system. The control valve should preferably be installed
vertically with the actuator in the upright position. When carrying out inclined to horizontal installation of
actuators the stanchions must be aligned vertically one above the other