background image

5396714-BUM-C-0919

Johnson Controls Ducted Systems

3

SECTION IV: FURNACE OPERATION

CIRCUIT BREAKERS

Your electric furnace is equipped with a unique safety feature: circuit
breakers. These circuit breakers are located behind the door of the fur-
nace near the bottom of the furnace. See Figure 1. If a component fails
inside the furnace, the circuit breakers prevent damage that can be
caused by an electrical short. 

If the breakers trip, follow these steps to reset them:

1. Turn off the power to the furnace at the circuit breaker panel in the

home. 

2. Remove the furnace door and reset the circuit breaker in the fur-

nace. 

3. Reinstall the furnace door and turn the power back on at the circuit

breaker panel in the home. 

Note:

 If the circuit breakers trip again, there is a problem in the furnace.

Contact a service technician. A list of authorized service centers is pro-
vided with every furnace. Use this for assistance in obtaining service for
your furnace.

LUBRICATION

The blower motor bearings are factory sealed. Additional lubrication is
not required.

BLOWER ASSEMBLY

Every electric furnace comes equipped with a blower capable of operat-
ing a heat pump or air conditioner. With the addition of the proper heat
pump, you can avail of comfort and savings throughout the year. An air
conditioner also works with your furnace and can provide cooling in
summer at a very low operating cost.

AIR FILTER

The filter supplied with the furnace is a throw-away filter. Clean filters
frequently. Shake out all loose dirt, and use a vacuum cleaner for addi-
tional cleaning. This method of cleaning prolongs filter life. Change fil-
ters regularly because clean filters provide added comfort, provide a
better and cleaner environment, and increase the efficiency of the fur-
nace.

FILTER LOCATION:

 For the downflow furnace, you must remove the

front panel of the furnace to gain access to the filter. See Figure 1. For
the upflow furnace, the filter is located behind the return air grill, adja-
cent to the furnace closet or any other location in the return air.

RETURN AIR

Return air must be provided back to the circulating blower to provide air
distribution. DO NOT OBSTRUCT ANY RETURN AIR GRILLE. This
causes the furnace heating elements to cycle off and on repeatedly.

ABSENCE FROM HOME

The power supply to your furnace is equipped with either a fused or
breaker type disconnect. If an overload occurs, this interrupts the oper-
ation of your furnace until it is reset or the fuse is replaced. Do not
assume that the furnace can operate unattended for long periods of
time, especially if there is a possibility of damage to your property due
to freezing. If you are away from home for a period, arrange for some-
one to check your home regularly (daily or every second day).

PREPARATION FOR HEATING SEASON

At the beginning of each heating season:

1. Replace filters as outlined previously in this document. Clean dust

and lint from in and around the furnace. Clean dust and lint from the
blower and the blower compartment. 

2. If the furnace fails to operate properly:

a.

Ensure that electrical power is being supplied to the furnace.
Check the main household power supply.

b.

If the furnace still fails to operate, shut off the furnace and
contact your service technician.

YOUR AUTHORIZED SERVICE TECHNICIAN

It is important to service your furnace. If the unit gives any indication of
improper operation, call your authorized service technician. If a service
technician performs routine care of your furnace, they can identify
potential problems and correct them. Preventive maintenance allows
you to operate your furnace with minimum concern and helps to prolong 

furnace life.

 WARNING

You must first de-energize the furnace at the main household power
supply and lock it.

!

NOTICE

Be sure electrical supply to furnace is turned off at the household
service box and furnace circuit breakers before cleaning.

Содержание EBE10A

Страница 1: ...could result in death or serious injury CAUTION indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It is also used to alert against unsafe practic...

Страница 2: ...f in the reverse order and the blower turns off LIMIT CONTROLS Each element has an automatic limit switch that is wired into the circuit The limit switch shuts off power to that element if the heat ex...

Страница 3: ...f the furnace to gain access to the filter See Figure 1 For the upflow furnace the filter is located behind the return air grill adja cent to the furnace closet or any other location in the return air...

Страница 4: ...ts downflow or upflow orientation to achieve higher airflow Refer to the installation instructions packed with the accessory package for more information FIGURE 3 EBE EUE Furnace Location of Component...

Страница 5: ...5396714 BUM C 0919 Johnson Controls Ducted Systems 5 SECTION V REPAIR PARTS LIST FIGURE 4 EBE Downflow Application...

Страница 6: ...reaker 3500 128 3500 128 3500 128 21 Circuit Breaker 1 Required S1 3500 377P A Circuit Breaker 2 Required S1 3500 377P A S1 3500 377P A 22 Buss Bar See Note 2 S1 3500 378P S1 3500 378P S1 3500 378P 23...

Страница 7: ...S1 02541250000 20 Bracket Circuit Breaker 3500 128 3500 128 3500 128 21 Circuit Breaker 2 Required See Note 2 S1 3500 377P A S1 3500 377P A S1 3500 377P A 22 Buss Bar S1 3500 378P S1 3500 378P S1 350...

Страница 8: ...5396714 BUM C 0919 8 Johnson Controls Ducted Systems FIGURE 5 EUE Upflow Application...

Страница 9: ...500 128 3500 128 3500 128 21 Circuit Breaker 1 Required S1 3500 377P A Circuit Breaker 2 Required S1 3500 377P A S1 3500 377P A 22 Buss Bar See Note 2 S1 3500 378P S1 3500 378P S1 3500 378P 23 Ground...

Страница 10: ...S1 02541250000 20 Bracket Circuit Breaker 3500 128 3500 128 3500 128 21 Circuit Breaker 2 Required S1 3500 377P A S1 3500 377P A S1 3500 377P A 22 Buss Bar S1 3500 378P S1 3500 378P S1 3500 378P 23 Gr...

Страница 11: ...with Company promptly after installation This will initiate the warranty period and allow us to contact you should it become necessary You can register your product by returning the Warranty Registra...

Страница 12: ...furnace 14 Damages caused by improper parts components or accessories not suitable for use in or with the unit For a list of parts that are known to be compatible reference equipment repair parts lis...

Отзывы: