A pressure transducer senses the high-side refrigerant pressure through a service access port.
The port is located on the liquid refrigerant line leaving the condenser. The pressure controller,
complete with terminal connection blocks for wiring, attaches to a field-installed mounting bracket.
The kit includes an appropriate mounting hardware for the pressure control module and the
damper actuator motor. There is also a routing hole in the condenser corner panel, near the
actuator mounting location, for installation of the plenum-rated cable between the motor and the
control module.
Note:
On dual compressor units, the actuator MUST be connected to the #1 circuit liquid line
fitting. Connection to the second stage refrigerant circuit will result in system malfunction.
For detailed installation instructions, refer to the supplementary
Low Ambient Damper Kit Installation
and Operation Instructions (Form 145.10-IOM4)
.
Kit #
Model
A
B
C
LADK-036C-1
DSH024C/036C
25.875 inches
5.0 inches
23.625 inches
LADK-060C-1
DSH048C/060C
27.875 inches
5.0 inches
26.625 inches
LADK-100C-1
DSH096C
48.0 inches
5.0 inches
29.25 inches
LADK-120C-1
DSH120C
60.75 inches
5.0 inches
29.125 inches
Figure 17: Low ambient damper
37
Model DSH024C–120C Horizontal R-410A Air Conditioning Units C-Generation Smart Equipment Controller