Figure 1: Securing straps and brackets
Table 1: Operating weight
Unit
Operating weight
(condenser only)
Shipping weight
(condenser only)
DSH024C
675 (390)
715 (430)
DSH036C
680 (400)
720 (440)
DSH048C
955 (568)
1015 (608)
DSH060C
995 (593)
1065 (633)
DSH096
1470 (815)
1560 (855)
DSH120C
1800 (1020)
1870 (1060)
Note:
All weights are in lbs.
Units may be either hung or floor mounted. If the unit is hung, use all the indicated mounting
points, whether the unit is installed as a package or split system (see Figure 4 on page 13 and
Figure 5 on page 14). Hanger rods with a minimum 1/2-inch diameter are strongly recommended.
Ensure the attachment point of the rods to the building structure is sufficient to support the unit
weight. To ensure efficient condensate drainage, the unit can be pitched towards the evaporator
end of the unit.
A minimum of 4-inch clearance is required under the unit to allow for trapping of the evaporator
condensate drain. See Typical Service Clearances on page 20 for more unit clearance information.
Separation of the units
All models can be ordered with refrigerant shut-off valves or couplings. These components allow
the evaporator and condenser sections to ship factory-split. The evaporator and condenser can
then be assembled onsite without requiring the entire unit refrigerant charge be reclaimed.
Model DSH024C–120C Horizontal R-410A Air Conditioning Units C-Generation Smart Equipment Controller
12
Johnson Controls