English
IS_DP0100 / DP0250 Rev. A_11 2009
This document is subject to change without notice
1
READ THIS INSTRUCTION SHEET AND THE SAFETY WARNINGS CAREFULLY BEFORE
INSTALLING AND SAVE IT FOR FUTURE USE
General Features
Each device has 2 selectable measuring ranges. Each device is individually temperature compensated.
* %/FS
from highest pressure range (including: general accuracy, temperature drift, linearity, hysteresis
and repetition error).
The Differential Pressure Transmitter is delivered individually packed with standard accessories
(see accessories).
Dimensions
Figure 1: Dimensions in mm
Mounting Instructions
Figure 2: Installation
(a).
without jumper
(b).
jumper
(c).
The pressure values on the sticker depends on the model
(d).
Push button for zero - Zero push button zero
Figure 3: Electrical Connection
Accessories
Standard accessories:
• 2 fixing screws
• 2 plastic duct connectors
• 2 m tube
∅
4 / 7 mm
Optional accessories:
• Metallic duct connectors
2 range model
- D for display
Measuring
range 1
Measuring
range 2
Accuracy %/FS *
over operation temp.
-10...+50 °C
range 1 and range 2
Long term
stability
typical 1 year
- AZ
DP0100-AZ (-D)
-50...+50 Pa
-100...+100 Pa
±1,5%
±1 Pa
DP0250-AZ (-D)
0...100 Pa
0...250 Pa
±1,5%
±1 Pa
0-10 V
Output 0...10 V
4-20 mA
Output 4...20 mA
24 V
Supply 24 VAC or VDC
GND
Ground