FORM 145.15-IOM7 (412)
JOHNSON CONTROLS
17
FAN PERFORMANCE
CSV060B
CSV096B
CSV120B
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1600
645 0.29 733 0.36 814 0.43 888 0.50 958 0.57 1024 0.64 1087 0.72 1154 0.83 1211 0.91 1245 0.99
1800
708 0.40 788 0.48 863 0.55 933 0.63 999 0.71 1061 0.79 1121 0.87 1178 0.95 1233 1.04 1295 1.17
2000
763 0.52 837 0.61 907 0.69 973 0.77 1035 0.86 1095 0.95 1152 1.04 1207 1.13 1260 1.22 1311 1.31
2200
836 0.69 904 0.78 969 0.87 1030 0.97 1089 1.06 1145 1.15 1199 1.25 1252 1.35 1303 1.45
~
~
2400
898 0.88 961 0.98 1021 1.08 1079 1.18 1135 1.28 1188 1.38 1240 1.48
~
~
~
~
~
~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
0.2
0.4
0.6
0.8
1.0
1.2
Optional Hi-Static Drive + 1.5 HP
Standard Drive + 1 HP
Field Supplied Low Static
Drive
1.4
1.6
1.8
2.0
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2400
510 0.31 600 0.45 672 0.60 741 0.78 810 0.96 878 1.14 936 1.33 982 1.54 1033 1.76 1074 2.00
2800
538 0.44 628 0.57 700 0.71 778 0.89 830 1.10 890 1.29 950 1.50 1010 1.72 1048 1.92
~
~
3200
599 0.62 675 0.79 745 0.98 815 1.18 875 1.38 927 1.58 985 1.78 1037 1.99
~
~
~
~
3600
661 0.86 730 1.03 795 1.23 853 1.43 915 1.64 973 1.85
~
~
~
~
~
~
~
~
4000
712 1.10 773 1.28 830 1.50 888 1.72 946 1.95
~
~
~
~
~
~
~
~
~
~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
Standard Drive + 1.5 HP
Field Supplied Low Static
Drive
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
Optional Hi-Static Drive + 2 HP
1.4
1.6
1.8
2.0
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3200
599 0.62 675 0.79 745 0.98 815 1.18 875 1.38 927 1.58 984 1.78 1037 1.99 1082 2.22 1128 2.42
3600
661 0.86 730 1.03 795 1.23 853 1.43 915 1.64 973 1.85 1020 2.10 1070 2.37 1114 2.67 1160 2.89
4000
712 1.10 773 1.28 830 1.50 888 1.72 946 1.95 1004 2.19 1062 2.44 1098 2.70 1146 2.97
~
~
4400
768 1.42 824 1.62 877 1.82 930 2.04 985 2.30 1035 2.60 1085 2.90
~
~
~
~
~
~
4800
822 1.78 875 1.98 925 2.20 975 2.43 1026 2.68 1078 2.96
~
~
~
~
~
~
~
~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
Field Supplied Low Static
Drive
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
Optional Hi-Static Drive + 3 HP
Standard Drive + 2 HP
1.4
1.6
1.8
2.0
Содержание CSV060B-240B
Страница 6: ...FORM 145 15 IOM7 412 6 JOHNSON CONTROLS CSV060 DIMENSIONAL DATA ...
Страница 7: ...FORM 145 15 IOM7 412 JOHNSON CONTROLS 7 CSV096 120 DIMENSIONAL DATA ...
Страница 8: ...FORM 145 15 IOM7 412 8 JOHNSON CONTROLS CSV180 DIMENSIONAL DATA ...
Страница 9: ...FORM 145 15 IOM7 412 JOHNSON CONTROLS 9 CSV240 DIMENSIONAL DATA ...
Страница 12: ...FORM 145 15 IOM7 412 12 JOHNSON CONTROLS TYPICAL WIRING SCHEMATIC ...
Страница 13: ...FORM 145 15 IOM7 412 JOHNSON CONTROLS 13 ...
Страница 14: ...FORM 145 15 IOM7 412 14 JOHNSON CONTROLS ...
Страница 15: ...FORM 145 15 IOM7 412 JOHNSON CONTROLS 15 ...