CK721-A Network Controller

Hardware Installation 

24-10025-237 Rev. – 

 

13

To enter the recommended Static Route:

1. From the Main menu select 

Route Info

.

2. From the Route Configuration screen, select 

net

.

 (Use the spacebar to toggle between Host/

Net and use the enter key to move to the next column.)

3. Specify the 

Destination

 address of 0.0.0.0.

4. For the 

Gateway

 address enter the router IP address

.

5. Select 

Save

 and press <

Enter

>.

6. Press <

Esc

>.

7. Reboot the CK721-A panel.

For other route configurations and troubleshooting ,refer to the 

CK721-A Installation and 

Operation Manual

.

M

AINTENANCE

This section provides maintenance instructions, operational testing procedures, troubleshooting 
guidelines, and instructions on how to obtain replaceable parts for the CK721-A system.

To perform the following routine maintenance on the CK721-A:

1. Periodically check the continuity of the grounding circuit.

2. Perform operational testing monthly (check for proper operation).

3. Replace the lithium battery every five years or after extended (five days) power interruption 

(Panasonic CR 2025 or equivalent).

4. If installed, replace the lead-acid backup batteries every three years (either Power Sonic 

PS-1270, 12 VDC, 7 Ah or equivalent; or Power Sonic PS-1228, 12 VDC, 2.8 Ah or 
equivalent.)

To check for proper operation of the CK721-A:

1. Verify POWER LED on the CK721-A.

2. Verify that the FAULT LED on the CK721-A is not on.

3. Verify that the RS485B LED is flashing to show activity on the bus.

4. Present a 

valid

 card to a reader, and then verify that access is granted (green lamp lights).

5. Present an 

invalid 

card to a reader, and then verify that access is denied (red lamp lights).

To check backup battery operation (if installed):

1. Disable primary AC input voltage to the enclosure.

2. Verify that the CK721-A continues to operate.

3. Reapply primary AC voltage to the enclosure.

Содержание CK721-A

Страница 1: ...24 10025 237 Revision December 2017 CK721 A Network Controller hardware installation manual...

Страница 2: ...erial returns contact the branch if the material was purchased through a Johnson Controls branch or through the Product Sales Operations Team if ordered through the Advanced Order Management System AO...

Страница 3: ...nt must be maintained between 13 35 C 55 95 F and relative humidity of 85 5 by the HVAC system Twenty four hour standby power shall be provided for the HVAC system 6 The installer shall incorporate a...

Страница 4: ......

Страница 5: ...rds and 8 000 off line transactions Note When the number of badges exceeds 120 000 the number of access groups should be limited to 50 000 All CK721 A panels are connected to the server via a 10 100Ba...

Страница 6: ...cate 2398 cryptographic module version 2 0 9 from the Open Source Software Institute http www oss institute org CK721 A controller peer to peer User Datagram Protocol UDP broadcast messages are not en...

Страница 7: ...g CK721 A to a Terminal Emulator RS232 Serial Null Modem Cable Wiring on page 6 RS232 B KONE serial server elevator or OTIS serial server elevator controller communications port or ThyssenKrupp serial...

Страница 8: ...power is not supplied before you remove the lithium battery the realtime clock will be incorrect LEDs POWER ON is steady when power is applied FAULT OFF indicates normal operation ON indicates a gener...

Страница 9: ...l and snap on To remove a module pull the white clips two are located at the bottom and one on top of the module then pull the bottom of the module out and lift it up Wiring Between RS485B and the Fie...

Страница 10: ...Listed 22 AWG Stranded Hook up wire Limited to within cabinet Listed 18 AWG 3 cond stranded shielded 4000 ft 1215 m All modules connected to a single CK721 A panel must be within 4000 feet of the pan...

Страница 11: ...71 latest edition must be followed for installations in Great Britain Additional information is given in the Cardkey Installers Code of Practice Conduit ground cold water pipes unbrazed joints or diss...

Страница 12: ...tant Notes As a security precaution Johnson Controls strongly suggests changing the default controller password during the installation process The CK721 A panel must be set up first using Terminal Em...

Страница 13: ...you will be following Serial cable between RS232C A J3 of the CK721 A controller and your laptop or PC serial port or Ethernet cable 2 Start your terminal emulator software 3 For serial communication...

Страница 14: ...2000 server Version 3 8 Build 57 with SP2 or later These steps set the IP address and netmask the preferred primary comm path and the network polling of the CK721 A which are required for communicatio...

Страница 15: ...LAN setting which specifies the frequency in seconds that the CK721 A panel polls the P2000 server during LAN connections The recommended value is 30 seconds The Network Polling Dup value is not curr...

Страница 16: ...ondary IP interface Primary Host IP Address User Def The primary IP address used by the primary server network interface An IP address is a 32 bit number that is notated by using four numbers from 0 t...

Страница 17: ...1 A 1 Periodically check the continuity of the grounding circuit 2 Perform operational testing monthly check for proper operation 3 Replace the lithium battery every five years or after extended five...

Страница 18: ...Impaired Performance Conditions A list of conditions that may cause impaired performance is provided in the following table with reference pages Field Servicing Troubleshoot the CK721 A by substitutin...

Страница 19: ...We welcome your comments at BE techpubs security jci com Security Solutions 805 522 5555 www johnsoncontrols com...

Отзывы: