PMGB0374
15
NOTICE
Indoor Unit
Auxiliary Condensate Pan
(Field-Supplied)
To the Atmosphere
Figure 7.2 Auxiliary Condensate Pan
NOTE:
If the relative humidity of ambient air exceeds
80%, install an auxiliary condensate pan
(field-supplied) beneath the indoor unit as
shown in Figure 7.2.
Checking Unit without Drain-up Mechanism
● Pour 61oz (1.8 liters) of water into the condensate pan.
● Check to ensure that the water flows smoothly and no water leakage occurs. When water cannot be
found at the end of the condensate piping, pour another approximately 61oz (1.8 liters) of water into the
condensate pan.
● Be aware of the thickness of the insulation when the left side piping is performed. If it is too thick, piping
cannot be installed in the unit.