Johnson Controls Unitary Products
Blower Speed Selection
The variable speed blowers are designed to deliver constant
CFM regardless of the external static pressure (ESP) in the
ductwork. Therefore, if too many supply registers are closed, a
filter becomes clogged, or there is a restriction in the ductwork,
the motor will automatically operate at a higher speed to
compensate for the higher ESP. This may result in a higher
operating sound level.
These units have variable speed motors that automatically adjust
to provide constant CFM from 0.2" to 0.6" w.c. static pressure.
From 0.6" to 1.0" static pressure, CFM is reduced by 2% per 0.1"
increase in static. Operation on duct systems with greater than
1.0" w.c. external static pressure is not recommended.
To Set Cooling CFM:
Refer to Tables 7 and 8 for the possible high speed cooling and
heat pump CFM selections.
Find the recommended system airflow for the unit model.
Set “COOL” and “ADJ” Jumpers on the CFM selection board as
indicated in Tables 7, 8 and Figure 9.
NOTE:
CFM indicator light flashes once for every 100 CFM
(i.e., 12 flashes = 1200 CFM).
Table 10: Electric Heat Minimum Supply Air
Size
(Tons)
Voltage
Minimum Supply Air (CFM)
Heater kW
3.8/5.0
5.6/7.5
7.5/10.0
11.3/15.0
15.0/20.0
18.8/25.0
024
(2.0)
208/230-1-60
720
720
720
-
-
-
030
(2.5)
208/230-1-60
1000
1000
1000
1000
-
-
208/230-3-60
1000
1000
1000
1000
-
-
460-3-60
1000
1000
1000
1000
-
-
036
(3.0)
208/230-1-60
1080
1080
1080
1080
-
-
208/230-3-60
1080
1080
1080
1080
-
-
460-3-60
1080
1080
1080
1080
-
-
042
(3.5)
208/230-1-60
-
-
1400
1400
-
-
208/230-3-60
-
-
1400
1400
-
-
460-3-60
-
-
1400
1400
-
-
048
(4.0)
208/230-1-60
-
-
1440
1440
1440
1440
208/230-3-60
-
-
1440
1440
1440
1440
460-3-60
-
-
1440
1440
1440
1440
060
(5.0)
208/230-1-60
-
-
1900
1900
1900
1900
208/230-3-60
-
-
1900
1900
1900
1900
460-3-60
-
-
1900
1900
1900
1900
Table 11: Indoor Blower Specifications
Size
(Tons)
Motor
HP
RPM
Eff.
SF
Frame
024
(2.0)
1/2
Variable
0.8
1.0
48
030
(2.5)
1/2
Variable
0.8
1.0
48
036
(3.0)
3/4
Variable
0.8
1.0
48
042
(3.5)
3/4
Variable
0.8
1.0
48
048
(4.0)
3/4
Variable
0.8
1.0
48
060
(5.0)
1
Variable
0.8
1.0
48
Table 12: Electric Heat Multipliers
Voltage
kW Capacity Multipliers
1
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Nominal
Applied
240
208
0.75
230
0.92
480
460
0.92