Johnson Controls B1HA036 Скачать руководство пользователя страница 4

341849-YIM-A-0108

4

Johnson Controls Unitary Products

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the
following national and local safety codes.

1.

National Electrical Code ANSI/NFPS No. 70 or Cana-
dian Electrical Code Part 1, C22.1 (latest editions).

2.

Local plumbing and waste water codes and other
applicable local codes.

Refer to Table 1 for unit application data and to Table 4
for electric heat application data.

If components are to be added to a unit to meet local
codes, they are to be installed at the dealer's and/or
the customer's expense.

Size of unit for proposed installation should be based
on heat loss/heat gain calculations made in accor-
dance with industry recognized procedures identified
by the Air Conditioning Contractors of America.

LOCATION

Use the following guidelines to select a suitable loca-
tion for these units.

1.

Unit is designed for outdoor installation only.

2.

Condenser must have an unlimited supply of air.
Where a choice of location is possible, position unit
on either north or east side of building.

3.

For ground level installation, a level pad or slab
should be used. The thickness and size of the pad
or slab used should meet local codes and unit
weight. Do not tie the slab to the building foundation.

4.

For roof top installation, be sure the structure will
support the weight of the unit plus any field

installed components. Unit must be installed on a
level roof curb or appropriate angle iron frame pro-
viding adequate support under the compressor/
condenser section.

5.

Maintain level tolerance of unit to 1/8" maximum.

RIGGING AND HANDLING

Care must be exercised when moving the unit. Do not
remove any packaging until the unit is near the place of
installation. Rig unit with slings placed under the unit.
Spreader bars of sufficient length should be used
across the top of the unit.

BEFORE LIFTING A UNIT, MAKE SURE THAT ITS
WEIGHT IS DISTRIBUTED EQUALLY ON THE
CABLES SO THAT IT WILL LIFT EVENLY.

Units may also be moved or lifted with a fork-lift. Slot-
ted openings in the skid are provided for this purpose.
Forks must pass completely through the base.

Refer to Table 2 for unit weights and to Figure 1 for
approximate center of gravity.

FIGURE 1 - Center of Gravity

CLEARANCES

All units require certain clearances for proper operation
and service. Refer to Figure 4 for the clearances
required for construction, servicing and proper unit
operation.

TABLE 1: Unit Application Data

Voltage Variation,

Min./Max.

1

1. Rated in accordance with ARI Standard 110, utilization 

range “A”.

208/230 V

2

2. “T1" transformer primary tap must be moved from the 230 

volt connection to the 208 volt connection for low voltage 
applications of 208 volt and below.

187/253

460 V

414/504

575 V

518/630

Wet Bulb Temperature (

°

F) of Air on

Evaporator Coil, Min./Max.

57/72

Dry Bulb Temperature (

°

F) of Air on

Condenser Coil, Min.

3

/Max.

3. A low ambient accessory is available for operation down to 

0°F.

45/120

TABLE 2: Unit Dimensions

Size

Shipping 

Weight 

(lbs.)

Operating 

Weight 

(lbs.)

Dimensions

“A”

“B”

“C”

“D”

036

367

362

100

96

84

87

042

394

389

107

103

90

93

048

445

440

121

117

102

105

060

490

485

133

129

112

116

Do not permit overhanging structures or shrubs
to obstruct the condenser air discharge outlets.

25

22

CENTER OF GRAVITY 

FRONT 

OF 

UNIT 

“A” 

“B” 

“C” 

“D” 

49 1/8

49 1/4

Содержание B1HA036

Страница 1: ...ENT PARTS 3 PRODUCT NOMENCLATURE 3 INSTALLATION 4 SEQUENCE OF OPERATION 13 MAINTENANCE 15 See the following page for a complete Table of Contents NOTES CAUTIONS AND WARNINGS Installer should pay parti...

Страница 2: ...ND 575 3 60 POWER SUPPLY 17 7 TYPICAL WIRING DIAGRAM LEGEND 18 8 TYPICAL WIRING DIAGRAM NOTES 18 LIST OF TABLES Tbl Pg 1 UNIT APPLICATION DATA 4 2 UNIT DIMENSIONS 4 3 PHYSICAL DATA 6 4 ELECTRICAL DATA...

Страница 3: ...ormation on the design installation oper ation and service of this equipment is available in the following reference forms 341849 General Installation 035 16605 003 Electric Heater Accessory REPLACEME...

Страница 4: ...ain level tolerance of unit to 1 8 maximum RIGGING AND HANDLING Care must be exercised when moving the unit Do not remove any packaging until the unit is near the place of installation Rig unit with s...

Страница 5: ...ing compound on male pipe threads Install the condensate drain line 3 4 NPTF to spill into an open drain SERVICE ACCESS Access to all serviceable components is provided by the following removable pane...

Страница 6: ...heat CONTROL WIRING NOTE HEAT ANTICIPATOR SHOULD BE SET AT 0 25 AMPS FOR ALL MODELS PROGRAMMABLE THERMOSTAT ONLY REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH WIRING OVERCURRENT PROTEC...

Страница 7: ...04501058 1 10 05 9 6 19 6 20 20 2NH04501558 1 15 05 14 4 25 6 30 30 042 575 3 60 5 8 44 0 0 4 1 5 2NH04501058 1 10 05 9 6 21 1 25 25 2NH04501558 1 15 05 14 4 27 2 30 30 048 575 3 60 5 6 44 0 0 6 1 6 2...

Страница 8: ...1097 604 1004 480 912 456 Medium 1465 631 1395 512 1325 492 1255 473 1167 446 1079 419 952 392 Low 1316 473 1260 455 1204 438 1148 420 1069 396 990 372 911 348 042 High 1728 725 1633 697 1527 666 142...

Страница 9: ...l under field conditions would be inaccurate To ensure a dry coil the compressors should be deac tivated while the test is being run 4 Knowing the pressure drop across a dry coil the actual CFM throug...

Страница 10: ...10 1 10 7 11 8 13 7 17 0 22 6 32 2 70 4 6 7 8 13 4 23 0 80 7 3 16 9 TABLE 11 Cooling Superheat at Compressor Suction Airflow 1 400 CFM B1HA042 Outdoor Temperature F Indoor WB Temperature F 55 57 59 6...

Страница 11: ...ompressor Suction F 10 0 10 20 30 40 50 60 55 8 3 8 4 8 6 9 0 10 1 12 4 17 4 28 6 70 4 2 9 2 20 4 80 5 7 16 9 TABLE 15 Cooling Superheat at Compressor Suction Airflow 2 000 CFM B1HA060 Outdoor Tempera...

Страница 12: ...UTDOOR COIL 15 4 BACK SIDE RETURN AIR OPENING SIDE SUPPLY AIR OPENING BOTTOM RETURN AIR OPENING 15 2 1 1 1 15 BOTTOM SUPPLY AIR OPENING 2 LOW VOLTAGE CONN DIA KNOCKOUT HIGH VOLTAGE CONN DIA KNOCKOUT F...

Страница 13: ...here is a call for heating by the thermostat 2 On a call for heating the thermostat will send 24 volts to Y on the fan control board After the anti short cycle period is complete the 24 volts signal w...

Страница 14: ...od the fan responds to thermostat input but the heaters are enabled This is to sense a failed heater relay The limit cycle count is reset at the start of a heat request If the limit remains open for p...

Страница 15: ...COIL Dirt should not be allowed to accu mulate on the outdoor coil surface or other parts in the air circuit Cleaning should be as often as necessary to keep the coil clean Use a brush vacuum cleaner...

Страница 16: ...ohnson Controls Unitary Products FIGURE 5 Typical Wiring Diagram 230 3 60 Power Supply M R C COMPR RELAY DFST STAT M1 DETAIL A 222 Y BLU BLU DS DEFROST CONTROL 031 01268 000B FOR DEFROST CONTROL 031 0...

Страница 17: ...341849 YIM A 0108 Johnson Controls Unitary Products 17 FIGURE 6 Typical Wiring Diagram BHA Models 460 3 60 and 575 3 60 Power Supply...

Страница 18: ...R FAN RUN CAPACITOR COMPRESSOR START CAPACITOR ALTERNATE OUTDOOR FAN RUN CAPACITOR ALTERNATE INDOOR FAN RUN CAPACITOR REVERSING VALVE SOLENOID SOCKET PLUG CONNECTION ON FAN CONTROL BOARD LOW VOLTAGE S...

Страница 19: ...341849 YIM A 0108 Johnson Controls Unitary Products 19...

Страница 20: ...hout notice Printed in U S A 341849 YIM A 0108 Copyright 2007 by Johnson Controls Inc All rights reserved Supersedes 66269 YIM A 0104 035 16004 002 A 0104 Johnson Controls Unitary Products 5005 York D...

Отзывы: