Johnson Controls Unitary Products
FIGURE 7 - Typical Wiring Diagram Legend (See Pages 16 and 17)
FIGURE 8 - Typical Wiring Diagram Notes (See Pages 16 and 17)
CB
CCH
COMPR
DS
F1 F2 F3
F4 F5 F6
F7 F8 F9
F24
FS
HP
HTR 1
HTR 2
HTR 3
HTR 4
HTR 5
HTR 6
K1
K2
K3
K7
LP
LS
M1
M2
M3
PTCR
RC1/RC2
RC1
RC2
RC3
RVS
S2/P2
S3/P3
S4/P4
S3/P3
T1
TB2
CIRCUIT BREAKER 24V, 3 AMP
CRANKCASE HEATER (OPTIONAL)
COMPRESSOR
DEFROST SENSOR, CLOSES @ 31°F, OPENS @ 55°F.
FUSES, LINE VOLTAGE - 60 AMP (10, 15, 20 & 25 KW ELEC HEAT)
FUSES, LINE VOLTAGE - 30 AMP (10, 15, 20 & 25 KW ELEC HEAT)
FUSES, LINE VOLTAGE - 30 AMP (20, 25 KW ELEC HEAT)
FUSE 24V SECONDARY, 5 AMP
FREEZESTAT SWITCH (OPTIONAL ACCESSORY) OPEN @ 26° F
HIGH PRESSURE SWITCH (OPTIONAL ACCESSORY) OPENS @ 280 PSIG
ELECTRIC HEATER (OPT. ACCSSRY: ALL KW ELEC HEAT)
ELECTRIC HEATER (OPT. ACCSSRY: 7.5, 10, 15, 20 & 25 KW ELEC HEAT)
ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)
ELECTRIC HEATER (OPT. ACCSSRY: 15, 20 & 25 KW ELEC HEAT)
ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)
ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT)
RELAY INDOOR FAN MOTOR
RELAY ELECTRIC HEATER
RELAY ELECTRIC HEATER, 24 VDC COIL
RELAY LIMIT TRIP, 25 VDC COIL
LOW PRESSURE SWITCH (OPTIONAL ACCESSORY) OPEN @ 7 PSIG
LIMIT SWITCH, ELECTRIC HEAT (PART OF ELEC HEAT ACCESSORY)
CONTACTOR, COMPRESSOR & OUTDOOR FAN
CONTACTOR, ELECTRIC HEAT, 230V COIL
CONTACTOR, ELECTRIC HEAT, 230V COIL
START ASSIST (OPTIONAL DEVICE)
COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR
COMPRESSOR START CAPACITOR (ALTERNATE)
OUTDOOR FAN RUN CAPACITOR (ALTERNATE)
INDOOR FAN RUN CAPACITOR
REVERSING VALVE SOLENOID
SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LOW VOLTAGE
SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LINE VOLTAGE
SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 24V
SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 230V
TRANSFORMER, 24V, 40 VA
TERMINAL BLOCK ECM MOTOR "SPEED" CONNECTIONS
IDENTIFIED TERMINAL ON RUN CAPACITOR
ROOM THERMOSTAT 24V CONNECTIONS
TB1 ON FAN/ELEC HEAT CONTROL BOARD
FACTORY WIRING AND DEVICES
OPTIONAL WIRING AND DEVICES
FIELD WIRING
7. IF OPTIONAL SAFETY SWITCH KIT IS INSTALLED,
WIRE 219/BK IS REMOVED.
8. WIRE 204/BR IS REMOVED WHEN ELECTRIC HEAT
IS INSTALLED.
9. ELECTRIC HEAT ACCESSORY WITH DUAL POINT SUPPLY POWER.
SEE DETAIL A
10. SHUNT CONTACT ALSO USED WITH CRANKCASE HEATER. (OPTIONAL)
6. SELECT INDOOR BLOWER SPEED TO OBTAIN APPROX 400
CFM/TON IN COOLING.
5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE AND MINIMUM
CIRCUIT AMPACITY.
4. UNIT FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208
VOLT OPERATION MOVE '108/PR' WIRE FROM 240V TO 208V
ON TRANSFORMER T1.
3. MOTORS ARE INHERENTLY PROTECTED.
2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN
SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER
AND DANGEROUS OPERATION. IF ANY OF THE WIRE AS
SUPPLIED WITH THIS UNIT MUST BE REMOVED, IT MUST BE
REPLACED WITH TYPE 105° C, 600V WIRE OR EQUIVALENT
CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER
OPERATION AFTER SERVICING.
1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY,
LOCAL AND/OR NATIONAL CODES IN EFFECT AT TIME OF
INSTALLATION OF THIS UNIT.