9

 i

4.

All piping should be cleaned of dirt and scale by ham-
mering on the outside of the pipe and blowing out the 
loose dirt and scale. Before initial start-up, be sure that 
all of the gas lines external to the unit have been purged 
of air.

5.

The gas supply should be a separate line and installed in 
accordance with all safety codes as prescribed under 
Limitations. After the gas connections have been com-
pleted, open the main shut-off valve admitting normal 
gas pressure to the mains. Check all joints for leaks with 
soap solution or other material suitable for the purpose. 
NEVER USE A FLAME.

6.

The furnace and its individual manual shut-off valve must 
be disconnected from the gas supply piping system dur-
ing any pressure testing of that system at test pressures 
in excess of 1/2 psig (3.48 kPa).

The furnace must be isolated from the gas supply piping sys-
tem by closing its individual manual shut-off valve during any
pressure testing of the gas supply piping system at test pres-
sures equal to or less than 1/2 psig (3.48 kPa).

FLUE VENT HOOD

The flue vent hood with screen is not shipped attached. This
hood must be installed to assure proper unit operation. The
hood must be fastened to the outside of the side gas control/
electrical compartment with the screws provided in the bag
attached to the inside of the gas control/electrical compart-
ment, see Figure 6.

If flexible stainless steel tubing is allowed by the 
authority having jurisdiction, wrought iron or steel 
pipe must be installed at the gas valve and extend 
a minimum of two (2) inches outside of the unit 
casing.

Natural gas may contain some propane. Propane 
being a excellent solvent, will quickly dissolve 
white lead or most standard commercial com-
pounds. Therefore, a special pipe dope must be 
applied when wrought iron or steel pipe is used. 
Shellac base compounds such as gaskoloc or sta-
lastic, and compounds such as rectorseal # 5, 
Clyde’s or John Crane may be used.

Flue hood surfaces may be hot.

FIGURE 6 -  FLUE VENT OUTLET AIR HOOD

The flue exhaust hood must be properly installed 
and within the recommended clearances. Further 
communications and action must be given to the 
home or building owner(s) to eliminate any unau-
thorized human contact around this area during 
the heating cycle. Flue hood surface and immedi-
ate area are designed to operate at high tempera-
tures during the heating cycle.

V E N T   O U T L E T   S C R E E N

F L U E   V E N T   O U T L E T

A I R   H O O D

Содержание AFFINITY 340968-XIM-A-0108

Страница 1: ...larify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment damage may result if installation procedure is not handled properly CAUTION READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT INSTALLATION MANUAL SAVE THIS MANUAL AFFINITY SERIES SINGLE PACKAGED GAS ELECTRIC AIR COOLED AIR COND...

Страница 2: ...RAL GAS 17 CHECKING SUPPLY AIR CFM 18 TYPICAL WIRING DIAGRAM NOTES 23 LIST OF FIGURES Fig Pg 1 PRODUCT NOMENCLATURE 3 2 UNIT CENTER OF GRAVITY 5 3 TYPICAL FIELD CONTROL WIRING DIAGRAM 6 4 TYPICAL FIELD POWER WIRING DIAGRAM 6 5 EXTERNAL SUPPLY CONNECTION EXTERNAL SHUT OFF 8 6 FLUE VENT OUTLET AIR HOOD 9 7 UNIT DIMENSIONS FRONT 11 8 UNIT DIMENSIONS FRONT BOTTOM 12 9 UNIT DIMENSIONS BACK BOTTOM 12 10...

Страница 3: ...autho rized replacement parts APPROVALS Design certified by CGA and AGA listed as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 For installation directly on combustible flooring or in U S on wood flooring or Class A B C roof covering material 4 For installation on combustible material 5 For use with natural gas and or propane LP gas Not suitable for ...

Страница 4: ...angle iron frame providing adequate support under the compressor condenser section 5 Maintain level tolerance of unit to 1 8 maximum RIGGING OR HANDLING Care must be exercised when moving the unit Do not remove any packaging until the unit is near the place of installation Rig unit with slings placed under the unit Spreader bars of sufficient length should be used across the top of the unit Units ...

Страница 5: ...inst the curb FILTERS Single phase units are shipped without a filter and is the responsibility of the installer to secure a filter in the return air ductowrk or install a Filter Frame Kit 1FF0110 for the DNA018 thru DNA042 and 1FF0112 for the DNA048 and DNA060 Filters must always be used and must be kept clean When filters become dirt laden insufficient air will be delivered by the blower decreas...

Страница 6: ...r terminals during starting and running conditions are indicated on the unit Rating Plate and Table 8 The wiring entering the cabinet must be provided with mechanical strain relief A fused disconnect switch should be field provided for the unit If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram Electrical line must be sized p...

Страница 7: ...elow 55 F TABLE 4 PROPANE1 LP GAS APPLICATION DATA AVAILABLE ON MODELS INPUT MBH 2 OUTPUT MBH GAS RATE3 FT 3 HR NUMBER OF BURNERS TEMP RISE F AT FULL INPUT4 MIN MAX 1 1 2 2 2 1 2 3 3 1 2 TON 45 36 18 2 25 55 2 2 1 2 70 56 28 3 30 60 3 3 1 2 TON 70 56 28 3 25 55 4 5 TON 80 64 32 3 25 55 3 3 1 2 TON 90 72 36 4 30 60 4 5 TON 108 87 43 4 35 65 4 5 TON 135 108 54 5 45 75 1 Propane applications are acco...

Страница 8: ...l codes a manual shut off valve may have to be installed outside of the unit 3 Use wrought iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only FIGURE 5 EXTERNAL SUPPLY CONNECTION EXTERNAL SHUT OFF 1 2 x 1 2 G A S C O C K 1 2 x 1 2 U N I O N A U T O M A T I C G A S V A L V E D R I P L E G 1 2 1 4 N P T TABLE 5 NATURAL GAS PIPE SIZING CHART1 1 Maximum capa...

Страница 9: ...d attached This hood must be installed to assure proper unit operation The hood must be fastened to the outside of the side gas control electrical compartment with the screws provided in the bag attached to the inside of the gas control electrical compart ment see Figure 6 If flexible stainless steel tubing is allowed by the authority having jurisdiction wrought iron or steel pipe must be installe...

Страница 10: ...URNER ORIFICE NO Drill Size 43 43 43 43 43 40 40 PROPANE BURNER ORIFICE NO Drill Size 55 55 55 55 55 53 53 GAS CONNECTION SIZE 1 2 NPTI 1 2 NPTI 1 2 NPTI 1 2 NPTI 1 2 NPTI 1 2 NPTI 1 2 NPTI COMPRESSOR TYPE HERMETICALLY SEALED R RECIPROCATING S SCROLL R R R R R S S 1 See FILTERS on page 5 TABLE 8 ELECTRICAL DATA MODEL DNA POWER SUPPLY VOLTAGE LIMITATIONS1 COMPRESSOR COND FAN MOTOR FLA SUPPLY AIR BL...

Страница 11: ...N A I R I N L E T L O U V E R S F R O N T G A S E L E C T R I C C O N T R O L S E R V I C E A C C E S S C O M P A R T M E N T P A N E L O V E R A L L O V E R A L L All dimensions are in inches They are subject to change with out notice Certified dimensions will be provided upon request TABLE 9 UNIT DIMENSIONS FRONT UNIT SIZE DIMENSION A B 018 thru 042 33 1 2 18 1 4 048 and 060 41 1 2 23 1 8 TABLE ...

Страница 12: ... P P L Y 1 5 8 D I A K N O C K O U T 1 2 N P T I C O N N E C T I O N L O W V O L T A G E C O N N 1 8 D I A K N O C K O U T FIGURE 9 UNIT DIMENSIONS BACK BOTTOM 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5 4 1 4 1 2 3 1 2 3 3 8 1 4 1 2 2 8 3 8 1 4 1 2 C O N D E N S E R C O I L B O T T O M S U P P L Y A I R O P E N I N G B O T T O M R E T U R N A I R O P E N I N G S I D E R E T U R N A I R O P E N ...

Страница 13: ...rge period before de energizing If the pressure switch is lost during an ignition trial period the control immediately de energizes spark and gas The control begins pressure switch proving before an inter purge and re ignition attempt PILOT FLAME STABILIZATION PERIOD The control board de energizes the spark output and waits for a 2 second flame stabilization period before energizing the main gas v...

Страница 14: ...t will be energized during an open rollout condition If the rollout switch closes the control shall remain locked out until power removed or W is removed Rollout switch lockout shall not reset automatically POWER INTERRUPTIONS Power interruptions of any duration shall not cause lockout or any operation requiring manual intervention FLAME PRESENT WITH GAS OFF If flame is sensed for longer than 4 0 ...

Страница 15: ...all for HEAT occurs the circulating fan switches to heat speed after a 30 second delay When the thermostat ends the call for FAN the thermostat terminal G is de energized de energizing the circulating fan START UP PRE START CHECK LIST Complete the following checks before starting the unit 1 Check the type of gas being supplied Be sure that it is the same as listed on the unit nameplate 2 Make sure...

Страница 16: ...ting screw on the automatic gas valve Refer to Figure 10 Adjust as follows 1 Remove the cap from the valve body See Figure 10 for location 2 To decrease the gas pressure turn the adjusting screw counterclockwise 3 To increase the gas pressure turn the adjusting screw clockwise NOTE The correct manifold pressure for natural gas fur naces is 3 5 IWG The correct manifold pressure for propane LP is 10...

Страница 17: ...rature rise decrease the blower CFM to increase the rise DIRECT DRIVE BLOWER All units have direct drive multi speed blower motors Refer to the unit wiring diagram and connect the blower motor for the desired motor speed CHECKING GAS INPUT NATURAL GAS 1 Turn off all other gas appliances connected to the gas meter 2 With the furnace turned on measure the time needed for one revolution of the hand o...

Страница 18: ... inch plugs removed in Step 1 De energize the compressors before taking any test mea surements to ensure a dry indoor coil TABLE 12 GASE RATE CUBIC FEET PER HOUR1 1 EXAMPLE By actual measurement it takes 38 seconds for the hand on the 1 cubic foot dial to make a revolution with just a 100 000 BTUH furnace running Using this information locate 38 seconds in the first column of Table 12 Read across ...

Страница 19: ...ERHEAT AT COMPRESSOR SUCTION F AIRFLOW 400 CFM INDOOR WB TEMP F 55 57 59 61 63 65 67 69 71 73 75 65 17 1 19 5 21 9 24 4 26 8 29 3 31 7 32 7 33 7 34 6 35 6 70 13 6 16 2 18 8 21 5 24 1 26 8 29 4 30 6 31 8 33 1 34 3 75 10 1 12 9 15 7 18 6 21 4 24 3 27 1 28 6 30 0 31 5 32 9 80 6 6 9 6 12 7 15 7 18 7 21 8 24 8 26 5 28 2 29 9 31 6 85 6 3 9 6 12 8 16 0 19 3 22 5 24 4 26 4 28 3 30 2 90 6 8 9 9 13 0 16 1 1...

Страница 20: ... 4 32 1 32 8 33 5 34 2 75 7 8 11 5 15 2 18 8 22 5 26 2 29 8 30 7 31 6 32 6 33 5 80 8 8 12 7 16 6 20 5 24 4 28 2 29 4 30 5 31 6 32 7 85 6 1 10 2 14 3 18 4 22 6 26 7 28 0 29 3 30 6 32 0 90 7 3 11 5 15 7 19 9 24 1 25 9 27 7 29 5 31 3 95 8 6 13 0 17 3 21 6 23 8 26 1 28 3 30 6 100 6 9 10 7 14 5 18 3 21 2 24 0 26 9 29 7 105 5 1 8 4 11 8 15 1 18 5 22 0 25 4 28 9 110 6 2 9 0 11 8 15 9 19 9 24 0 28 0 115 6...

Страница 21: ...6 18 7 19 7 20 7 21 7 22 7 23 7 25 2 26 6 28 1 29 6 75 14 4 15 5 16 6 17 8 18 9 20 0 21 2 22 9 24 7 26 4 28 2 80 11 1 12 4 13 6 14 9 16 1 17 4 18 6 20 7 22 7 24 8 26 8 85 7 8 9 2 10 6 12 0 13 3 14 7 16 1 18 4 20 8 23 1 25 4 90 5 8 7 0 8 2 9 3 10 5 11 7 12 9 15 7 18 6 21 5 24 4 95 5 8 6 7 7 7 8 6 9 6 13 0 16 5 19 9 23 3 100 5 4 6 0 6 7 7 4 8 0 11 6 15 2 18 7 22 3 105 5 3 5 7 6 1 6 5 10 2 13 9 17 6 ...

Страница 22: ...340968 XIM A 0108 22 Johnson Controls Unitary Products FIGURE 14 TYPICAL WIRING DIAGRAM DNA 018 THRU 060 208 230 1 60 POWER SUPPLY ...

Страница 23: ... are connected to ASCT 3 If only LR is present wire 801 BL and 805 BL are connected to M1 coil If only ASCT is present wire 202 Y is connected to ASCT 3 If neither LR or ASCT are present wire 202 Y is connected to M1 coil as shown 7 Shunt contact also used with crankcase heater optional 8 Select indoor blower speed to remain within the temper ature rise range on the nameplate in heating FIGURE 15 ...

Страница 24: ... change without notice Printed in U S A 340968 XIM A 0108 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 286483 XIM B 0807 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 ...

Отзывы: