FANs 125, 121 

 

 

Product/Technical Bulletin 

A25 

 

Issue Date 

0316 

 

©  2016 Johnson Controls, Inc.

 

1

 

 

Part 24-7664-656, Rev. A 

 

Code No. LIT-125118 

 

 

A25 Series Warm Air Control with Manual Reset

 

 

The A25 Series Warm Air Control with Manual Reset 
is designed to shut down fans, burners, dampers, etc., 
when the temperature of the sensed air becomes 
greater than the controller’s setpoint. 

When the sensed temperature increases to the 
controller’s setpoint, the A25’s switch will open.  
Manual reset is required to reclose the electrical 
circuit.  The A25 may be used as a high limit control in 
the supply air duct (or plenum) where a lockout type 
control is desired or required by local code. 

 

Figure 1: The A25 Series Warm Air Control  

with Manual Reset 

 

 

 

 

Features and Benefits 

Trip-free Reset Lever 

Does not allow the reset switch to hold the contacts in a closed (on) 

position 

Pilot Duty Electrical Rating for 
up to 600 Volts Maximum  

Allows direct control of high voltage motor starters 

 Enclosed 

Switch 

Protects switch contacts from dust 

  Rod and Tube Sensing 

Element

Provides maximum response and allows for a high maximum 

sensing element temperature 

  Adjustable Duct  

Mounting Flange

Controls the depth of sensor insertion into the airstream; 

compensates for insulation depth 

  Wide Temperature Range

Allows the A25 to be used with many applications 

 

 

Содержание A25 Series

Страница 1: ...ntrol in the supply air duct or plenum where a lockout type control is desired or required by local code Figure 1 The A25 Series Warm Air Control with Manual Reset Features and Benefits Trip free Rese...

Страница 2: ...ng location refer to Figure 2 3 Using the flange as a template on the duct mark the location for two 1 2 in 13 mm No 10 sheet metal screws 4 Punch or drill both sheet metal screw holes in the duct at...

Страница 3: ...ncrease The red to blue circuit opens on temperature increase Refer to Figures 3 and 4 for terminal identification and typical wiring connections When the reset lever is pressed during normal operatio...

Страница 4: ...nd the alarm or signal if applicable should activate Note The setpoint at shutdown should equal the approximate duct air temperature 3 Turn the setpoint knob clockwise to the desired setpoint Nothing...

Страница 5: ...the sensor above the setpoint or lower the setpoint below the ambient temperature The control should lockout trip To reset after test Lower the temperature at the sensor to 20F 11C below the setpoint...

Страница 6: ...the sensor above the setpoint or lower the setpoint below the ambient temperature The control should lockout trip To reset after test Lower the temperature at the sensor to 20F 11C below the setpoint...

Страница 7: ...n The A25 is not sensing properly The sensing element may not be extended into the airstream or the sensing element is contacting an object inside of the duct or plenum Insert the sensing element as f...

Страница 8: ...8 A25 Series Warm Air Control with Manual Reset Product Technical Bulletin Notes...

Страница 9: ...e reset when the temperature drops 20F 11C below the dial setting Sensing Element Bi metal rod and tube construction Shipping Weight Individual pack 1 8 lb 0 8 kg Overpack of 12 units 23 lb 10 4 kg Wi...

Отзывы: