A11 Series Low Temperature Cutout Controls Product Bulletin

A11 Series low temperature cutout controls are 
available with Single-Pole, Single-Throw (SPST) or 
Single-Pole, Double-Throw (SPDT) contact action. 
Typical applications include the sensing of low 
temperature conditions to avoid over cooling or icing of 
hydronic coils, cooling coils, and liquid-handing pipes. 
The controls are compact and sturdy, and have an 
adjustable temperature setpoint range with a fixed 
differential. The range adjustment screw is accessible 
at the bottom of the control, and at the top of the control 
when the cover is removed.

 

Figure 1:  A11 Series Low Temperature 

Cutout Control

Table 1:  Features and Benefits

Features

Benefits

Precision Repeat Accuracy

Remains unaffected by ambient temperature at the control diaphragm 
cup and 4 ft (1.2 m) capillary (20 ft [6.1 m] sensing bulb must be in the 
controlled area).

Trip-Free Manual Reset

Allows the lever to reset. You must press and release the lever before 
operation resumes.

Recision Snap-Acting Contacts in a Dust 
Protected Enclosure

Enables the A11 to operate to the fullest potential.

Direct Reading Scale

Provides easy to adjust setpoint. Adjustments can be made from the 
top or bottom of the control.

A11 Series Low Temperature Cutout Controls

Product Bulletin

A11A, A11B, A11D, A11E

Code No. LIT-125010

Issued April 2018

Содержание A11A

Страница 1: ...om of the control and at the top of the control when the cover is removed Figure 1 A11 Series Low Temperature Cutout Control Table 1 Features and Benefits Features Benefits Precision Repeat Accuracy Remains unaffected by ambient temperature at the control diaphragm cup and 4 ft 1 2 m capillary 20 ft 6 1 m sensing bulb must be in the controlled area Trip Free Manual Reset Allows the lever to reset ...

Страница 2: ...igure 2 shows the A11 dimensions Figure 2 describes the A11 electrical ratings Table 2 Electrical Rating Motor Rating 120 V 208 V 240 V Motor Description AC Full Load Amperes 16 0 9 2 8 0 AC Locked Rotor Amperes 96 0 55 2 48 0 Non Inductive Amperes 16 0 9 2 8 0 Pilot Duty 125 VA 24 to 277 VAC 27 7 2 30 58 1 38 35 69 17 2 33 59 34 9 97 25 2 25 57 2 11 54 4 69 119 3 19 81 88 22 DIA 2 09 53 5 38 137 ...

Страница 3: ...Low Automatic Recycle A11D SPDT Manual Reset A11E SPDT Automatic Recycle Range Cutout 35 to 45 F 2 to 7 C Differential A11A and A11D Temperature must be 12 F 6 7 C above cutout point before control can be reset A11B and A11E 12 F 6 7 C Ambient Temperature Minimum 0 F 18 C Maximum 140 F 60 C Maximum Temperature at Bulb 250 F 121 C Sensing Element 1 8 in x 20 ft 3 2 mm x 6 1 m or 1 8 in x 40 ft 3 2 ...

Страница 4: ...g Technologies Solutions 507 E Michigan Street Milwaukee WI 53202 Compliance United States UL Listed File SA516 SDFY FCC Compliant to CFR 47 Part 15 Subpart B Class A Canada UL Listed CSA Class No 1222 01 File LR948 Industry Canada ICES 003 The performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these specifications consult the l...

Отзывы: