341426-BIM-A-0108
Johnson Controls Unitary Products
11
FIGURE 7 - UNIT DIMENSIONS - FRONT
3-3/4
2-1/2
47-1/4
1-1/2
2-5/8
3-1/3
5-3/8
11
12-3/4
49-1/8
A
2-3/8
VENTAIROUTLETHOOD
BLOWERSERVICE
ACCESSCOMPARTMENT
PANEL
GASSUPPLY1-1/4"DIA.
HOLE(1/2"NPTI
CONNECTION)
UNITCONDENSATE
CONNECTION3/4"NPTI
(TRAPRECOMMENDED)
B
HIGHVOLTAGE
CONN.1-3/8"DIA.
KNOCKOUT
HIGHVOLTAGE
CONN.7/8"DIA.
KNOCKOUT
GASSUPPLY1-1/4"DIA.
KNOCKOUT(1/2"NPTI
CONNECTION)
LOWVOLTAGECONN.
1-3/8"DIA.KNOCKOUT
X7/8"HOLE
CONDENSERCOIL
REFRIGERANT
CONNECTIONS
COMBUSTIONAIR
INLETLOUVERS
FRONT
GAS/ELECTRICCONTROL
SERVICEACCESS
COMPARTMENTPANEL
(OVERALL)
(OVERALL)
All dimensions are in inches.
They are subject to change with-
out notice. Certified dimensions
will be provided upon request.
TABLE 9: UNIT DIMENSIONS FRONT
UNIT SIZE
DIMENSION
“A”
“B”
036 and 042
33-1/2
18-1/4
048 and 060
41-1/2
23-1/8
TABLE 10: UNIT MINIMUM CLEARANCES
1
2
1.
A 1” clearance must be provided between any combustible
material and the supply 7 air ductwork.
2.
The products of combustion must not be allowed to accumulate
within a confined space and recirculate.
CLEARANCES
FRONT
36”
BACK
0”
LEFT SIDE (Filter-Access)
24”
RIGHT SIDE
12”
BELOW UNIT
3
3.
Units may be installed on combustible floors made from wood
or class A, B, or C roof covering material.
0”
ABOVE UNIT
4
4.
Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge outlet.
36” (For Condenser Air Discharge