background image

341426-BIM-A-0108

2

Johnson Controls Unitary Products

TABLE OF CONTENTS

GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
APPROVALS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

LIMITATIONS  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LOCATION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
RIGGING OR HANDLING . . . . . . . . . . . . . . . . . . . . . . . . . 4
CLEARANCES  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
DUCT WORK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ROOF CURB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FILTERS  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CONDENSATE DRAIN . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
SERVICE ACCESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
THERMOSTAT  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
POWER AND CONTROL WIRING . . . . . . . . . . . . . . . . . . 6
COMPRESSORS  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
GAS PIPING  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GAS CONNECTION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FLUE VENT HOOD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

SEQUENCE OF OPERATION. . . . . . . . . . . . . . . . . . . .13

HEATING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

PRESSURE SWITCH PROVING  . . . . . . . . . . . . . . . . . 13
PRE-PURGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
IGNITION TRIAL PERIOD. . . . . . . . . . . . . . . . . . . . . . . 13
PILOT FLAME STABILIZATION PERIOD . . . . . . . . . . . 13
HEAT BLOWER ON DELAY . . . . . . . . . . . . . . . . . . . . . 13
MAIN BURNER OPERATION . . . . . . . . . . . . . . . . . . . . 13
POST PURGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
HEAT BLOWER OFF DELAY . . . . . . . . . . . . . . . . . . . . 14
LOCKOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
HIGH TEMPERATURE LIMIT SWITCH  . . . . . . . . . . . . 14
ROLLOUT SWITCH  . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
POWER INTERRUPTIONS. . . . . . . . . . . . . . . . . . . . . . 14
FLAME PRESENT WITH GAS OFF . . . . . . . . . . . . . . . 14
GAS VALVE STUCK OPEN OR CLOSED  . . . . . . . . . . 14
FLAME SENSE CIRCUIT FAILURE . . . . . . . . . . . . . . . 14
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . 14

COOLING  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
CIRCULATING FAN  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

PRE-START CHECK LIST  . . . . . . . . . . . . . . . . . . . . . . . 15
OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . 15
TO TURN OFF GAS TO UNIT. . . . . . . . . . . . . . . . . . . . . 15
POST-START CHECK LIST (GAS). . . . . . . . . . . . . . . . . 16
MANIFOLD GAS PRESSURE ADJUSTMENT . . . . . . . . 16
BURNER INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . 16
PILOT INSTRUCTIONS  . . . . . . . . . . . . . . . . . . . . . . . . . 16
ADJUSTMENT OF TEMPERATURE RISE . . . . . . . . . . . 17

DIRECT DRIVE BLOWER. . . . . . . . . . . . . . . . . . . . . . . 17

CHECKING GAS INPUT . . . . . . . . . . . . . . . . . . . . . . . . . 17

NATURAL GAS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

CHECKING SUPPLY AIR CFM . . . . . . . . . . . . . . . . . . . . 18

TYPICAL WIRING DIAGRAM NOTES . . . . . . . . . . . . .23

LIST OF FIGURES

Fig. #

Pg. #

1

PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . 3

2

UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . 5

3

TYPICAL FIELD CONTROL WIRING DIAGRAM . . . . . 6

4

TYPICAL FIELD POWER WIRING DIAGRAM . . . . . . . 6

5

EXTERNAL SUPPLY CONNECTION EXTERNAL 

SHUT-OFF  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

6

FLUE VENT OUTLET AIR HOOD. . . . . . . . . . . . . . . . . 9

7

UNIT DIMENSIONS - FRONT. . . . . . . . . . . . . . . . . . . 11

8

UNIT DIMENSIONS - FRONT & BOTTOM . . . . . . . . . 12

9

UNIT DIMENSIONS - BACK & BOTTOM . . . . . . . . . . 12

10 GAS VALVE - FRONT. . . . . . . . . . . . . . . . . . . . . . . . . 16
11 GAS VALVE - REAR . . . . . . . . . . . . . . . . . . . . . . . . . . 16
12 PROPER FLAME ADJUSTMENT . . . . . . . . . . . . . . . . 17
13 DYA COIL DELTA P VS. AIRFLOW . . . . . . . . . . . . . . 19
14 TYPICAL WIRING DIAGRAM DYA 036, 042, 048, 060 

(208/230-3-60 POWER SUPPLY). . . . . . . . . . . . . . . . 21

15 TYPICAL WIRING DIAGRAM DYA 036, 042, 048, 060 

(460-3-60 POWER SUPPLY) . . . . . . . . . . . . . . . . . . . 22

16 WIRING DIAGRAM DETAIL A (460-3-60 POWER

SUPPLY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

17 TYPICAL WIRING DIAGRAM LEGEND . . . . . . . . . . . 24

LIST OF TABLES

Tbl. #

Pg. #

1

UNIT APPLICATION DATA. . . . . . . . . . . . . . . . . . . . . . 4

2

UNIT WEIGHTS AND CENTER OF GRAVITY . . . . . . . 5

3

NATURAL GAS APPLICATION DATA . . . . . . . . . . . . . 7

4

PROPANE (LP) GAS APPLICATION DATA . . . . . . . . . 7

5

NATURAL GAS PIPE SIZING CHART . . . . . . . . . . . . . 8

6

PROPANE (LP) GAS PIPE SIZING CHART . . . . . . . . . 8

7

PHYSICAL DATA  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

8

ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 10

9

UNIT DIMENSIONS FRONT . . . . . . . . . . . . . . . . . . . . 11

10 UNIT MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . 11
11 IGNITION CONTROL BOARD FLASH CODES . . . . . 15
12 GASE RATE - CUBIC FEET PER HOUR . . . . . . . . . . 18
13 SUPERHEAT CHARGING TABLE FOR DYA036. . . . 19
14 SUPERHEAT CHARGING TABLE FOR DYA042. . . . 20
15 SUPERHEAT CHARGING TABLE FOR DYA048. . . . 20
16 SUPERHEAT CHARGING TABLE FOR DYA060. . . . 20

Содержание 341426-BIM-A-0108

Страница 1: ...s are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equipment damage may result if installation procedure is not handled properly CAUTION READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT INSTALLATION MANUAL SAVE THIS MANUAL SINGLE PACKAGED GAS ELECTRIC AIR COOLED AIR C...

Страница 2: ...RAL GAS 17 CHECKING SUPPLY AIR CFM 18 TYPICAL WIRING DIAGRAM NOTES 23 LIST OF FIGURES Fig Pg 1 PRODUCT NOMENCLATURE 3 2 UNIT CENTER OF GRAVITY 5 3 TYPICAL FIELD CONTROL WIRING DIAGRAM 6 4 TYPICAL FIELD POWER WIRING DIAGRAM 6 5 EXTERNAL SUPPLY CONNECTION EXTERNAL SHUT OFF 8 6 FLUE VENT OUTLET AIR HOOD 9 7 UNIT DIMENSIONS FRONT 11 8 UNIT DIMENSIONS FRONT BOTTOM 12 9 UNIT DIMENSIONS BACK BOTTOM 12 10...

Страница 3: ...nter for autho rized replacement parts APPROVALS Design certified by CGA and AGA listed as follows 1 For use as a forced air furnace with cooling unit 2 For outdoor installation only 3 For installation directly on combustible flooring or in U S on wood flooring or Class A B C roof covering material 4 For installation on combustible material 5 For use with natural gas and or propane LP gas Not suit...

Страница 4: ...ron frame providing adequate support under the compressor condenser section 5 Maintain level tolerance of unit to 1 8 maximum RIGGING OR HANDLING Care must be exercised when moving the unit Do not remove any packaging until the unit is near the place of installation Rig unit with slings placed under the unit Spreader bars of sufficient length should be used across the top of the unit Units may als...

Страница 5: ...is tight against the curb FILTERS A filter rack and a high velocity filters are standard Filters must always be used and must be kept clean When filters become dirt laden insufficient air will be delivered by the blower decreasing your units efficiency and increasing operating costs and wear and tear on the unit and controls Filters should be checked monthly especially since this unit is used for ...

Страница 6: ...th mechanical strain relief A fused disconnect switch should be field provided for the unit If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram Electrical line must be sized properly to carry the load Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused Refer to Figure 4 f...

Страница 7: ... below 55 F TABLE 4 PROPANE1 LP GAS APPLICATION DATA AVAILABLE ON MODELS INPUT CAPACITY MBH 2 OUTPUT CAPACITY MBH GAS RATE3 FT 3 HR NUMBER OF BURNERS TEMP RISE F AT FULL INPUT4 MIN MAX 3 3 1 2 TON 45 36 18 2 25 55 3 3 1 2 TON 70 56 28 3 25 55 4 5 TON 80 64 32 3 25 55 3 3 1 2 TON 90 72 36 4 30 60 4 5 TON 108 87 43 4 30 60 4 5 TON 135 108 54 5 35 65 1 Propane applications are accomplished by field i...

Страница 8: ...l codes a manual shut off valve may have to be installed outside of the unit 3 Use wrought iron or steel pipe for all gas lines Pipe dope should be applied sparingly to male threads only FIGURE 5 EXTERNAL SUPPLY CONNECTION EXTERNAL SHUT OFF 1 2 x 1 2 G A S C O C K 1 2 x 1 2 U N I O N A U T O M A T I C G A S V A L V E D R I P L E G 1 2 1 4 N P T TABLE 5 NATURAL GAS PIPE SIZING CHART1 1 Maximum capa...

Страница 9: ...d attached This hood must be installed to assure proper unit operation The hood must be fastened to the outside of the side gas control electrical compartment with the screws provided in the bag attached to the inside of the gas control electrical compart ment see Figure 6 If flexible stainless steel tubing is allowed by the authority having jurisdiction wrought iron or steel pipe must be installe...

Страница 10: ...SOR TYPE HERMETICALLY SEALED R RECIPROCATING S SCROLL R R S S 1 Three phase 036 thru 042 size units are supplied with one 1 filter and on three phase 048 and 060 size units two 2 filters are supplied See FILTERS on page 5 TABLE 8 ELECTRICAL DATA MODEL DYA POWER SUPPLY VOLTAGE LIMITATIONS1 COMPRESSOR COND FAN MOTOR FLA SUPPLY AIR BLOWER MOTOR FLA MINIMUM CIRCUIT AMPACITY MAX FUSE SIZE AMPS2 MAX HAC...

Страница 11: ...N A I R I N L E T L O U V E R S F R O N T G A S E L E C T R I C C O N T R O L S E R V I C E A C C E S S C O M P A R T M E N T P A N E L O V E R A L L O V E R A L L All dimensions are in inches They are subject to change with out notice Certified dimensions will be provided upon request TABLE 9 UNIT DIMENSIONS FRONT UNIT SIZE DIMENSION A B 036 and 042 33 1 2 18 1 4 048 and 060 41 1 2 23 1 8 TABLE 1...

Страница 12: ... P P L Y 1 5 8 D I A K N O C K O U T 1 2 N P T I C O N N E C T I O N L O W V O L T A G E C O N N 1 8 D I A K N O C K O U T FIGURE 9 UNIT DIMENSIONS BACK BOTTOM 1 3 4 1 5 2 9 9 1 6 1 5 3 1 2 1 3 4 1 3 4 1 5 4 1 4 1 2 3 1 2 3 3 8 1 4 1 2 2 8 3 8 1 4 1 2 C O N D E N S E R C O I L B O T T O M S U P P L Y A I R O P E N I N G B O T T O M R E T U R N A I R O P E N I N G S I D E R E T U R N A I R O P E N ...

Страница 13: ...rge period before de energizing If the pressure switch is lost during an ignition trial period the control immediately de energizes spark and gas The control begins pressure switch proving before an inter purge and re ignition attempt PILOT FLAME STABILIZATION PERIOD The control board de energizes the spark output and waits for a 2 second flame stabilization period before energizing the main gas v...

Страница 14: ...t will be energized during an open rollout condition If the rollout switch closes the control shall remain locked out until power removed or W is removed Rollout switch lockout shall not reset automatically POWER INTERRUPTIONS Power interruptions of any duration shall not cause lockout or any operation requiring manual intervention FLAME PRESENT WITH GAS OFF If flame is sensed for longer than 4 0 ...

Страница 15: ...all for HEAT occurs the circulating fan switches to heat speed after a 30 second delay When the thermostat ends the call for FAN the thermostat terminal G is de energized de energizing the circulating fan START UP PRE START CHECK LIST Complete the following checks before starting the unit 1 Check the type of gas being supplied Be sure that it is the same as listed on the unit nameplate 2 Make sure...

Страница 16: ...ting screw on the automatic gas valve Refer to Figure 10 Adjust as follows 1 Remove the cap from the valve body See Figure 10 for location 2 To decrease the gas pressure turn the adjusting screw counterclockwise 3 To increase the gas pressure turn the adjusting screw clockwise NOTE The correct manifold pressure for natural gas fur naces is 3 5 IWG The correct manifold pressure for propane LP is 10...

Страница 17: ...rature rise decrease the blower CFM to increase the rise DIRECT DRIVE BLOWER All units have direct drive multi speed blower motors Refer to the unit wiring diagram and connect the blower motor for the desired motor speed CHECKING GAS INPUT NATURAL GAS 1 Turn off all other gas appliances connected to the gas meter 2 With the furnace turned on measure the time needed for one revolution of the hand o...

Страница 18: ... inch plugs removed in Step 1 De energize the compressors before taking any test mea surements to ensure a dry indoor coil TABLE 12 GASE RATE CUBIC FEET PER HOUR1 1 EXAMPLE By actual measurement it takes 38 seconds for the hand on the 1 cubic foot dial to make a revolution with just a 100 000 BTUH furnace running Using this information locate 38 seconds in the first column of Table 12 Read across ...

Страница 19: ...F 55 57 59 61 63 65 67 69 71 73 75 65 27 1 28 4 29 7 31 1 32 4 33 7 35 0 35 9 36 8 37 6 38 5 70 23 3 24 8 26 2 27 7 29 2 30 6 32 1 33 5 34 9 36 4 37 8 75 19 5 21 1 22 7 24 4 26 0 27 6 29 2 31 2 33 1 35 1 37 1 80 15 7 17 5 19 2 21 0 22 8 24 5 26 3 28 8 31 3 33 8 36 3 85 11 9 13 8 15 7 17 6 19 6 21 5 23 4 26 5 29 5 32 6 35 6 90 8 6 10 6 12 6 14 6 16 6 18 6 20 6 24 1 27 6 31 1 34 6 95 5 3 7 4 9 5 11 ...

Страница 20: ...6 18 7 19 7 20 7 21 7 22 7 23 7 25 2 26 6 28 1 29 6 75 14 4 15 5 16 6 17 8 18 9 20 0 21 2 22 9 24 7 26 4 28 2 80 11 1 12 4 13 6 14 9 16 1 17 4 18 6 20 7 22 7 24 8 26 8 85 7 8 9 2 10 6 12 0 13 3 14 7 16 1 18 4 20 8 23 1 25 4 90 5 8 7 0 8 2 9 3 10 5 11 7 12 9 15 7 18 6 21 5 24 4 95 5 8 6 7 7 7 8 6 9 6 13 0 16 5 19 9 23 3 100 5 4 6 0 6 7 7 4 8 0 11 6 15 2 18 7 22 3 105 5 3 5 7 6 1 6 5 10 2 13 9 17 6 ...

Страница 21: ...341426 BIM A 0108 Johnson Controls Unitary Products 21 FIGURE 14 TYPICAL WIRING DIAGRAM DYA 036 042 048 060 208 230 3 60 POWER SUPPLY ...

Страница 22: ...341426 BIM A 0108 22 Johnson Controls Unitary Products FIGURE 15 TYPICAL WIRING DIAGRAM DYA 036 042 048 060 460 3 60 POWER SUPPLY ...

Страница 23: ...ent wire 801 BL and 805 BL are connected to ASCT 3 If only LR is present wire 801 BL and 805 BL are connected to M1 coil If only ASCT is present wire 202 Y is connected to ASCT 3 If neither LR or ASCT are present wire 202 Y is connected to M1 coil as shown 7 Shunt contact also used with crankcase heater optional 8 Unit factory wired for low or medium speed indoor blower operation To change motor s...

Страница 24: ...R OPTIONAL BR BLOWER RELAY CB CIRCUIT BREAKER CCH CRANK CASE HEATER OPTIONAL COMPR COMPRESSOR DM DRAFT MOTOR FCB FAN CONTROL BOARD GND GROUND FS FREEZE STAT SWITCH OPTIONAL HP HIGH PRESSURE SWITCH OPENS 380 PSIG IDFAN INDOOR FAN MOTOR LP LOW PRESSURE SWITCH OPENS 7 PSIG LS LIMIT SWITCH LR LOCK OUT RELAY OPTIONAL M1 CONTACTOR COMPR AND OD FAN ODFAN OUTDOOR FAN MOTOR PS PRESSURE SWITCH RC1 RC2 COMPR...

Отзывы: