403134-YIM-E-0311
Johnson Controls Unitary Products
23
060
(5.0)
208-1-60 28.8 145.0
45.0
2.3
7.6
10.0
None
-
-
-
55.9
70
E05
4.0
1
19.2
55.9
70
E07
5.6
1
26.9
55.9
70
E10
8.0
1
38.5
70.1
80
E15
11.9
2
57.2
93.5
100
E20
15.9
2
76.4
117.6
125
E30
22.2
2
106.7
155.4
175
230-1-60 28.8 145.0
45.0
2.3
7.6
10.0
None
-
-
-
55.9
70
E05
5.3
1
22.1
55.9
70
E07
7.5
1
31.3
61.1
80
E10
10.6
1
44.2
77.2
80
E15
15.9
2
66.3
104.8
110
E20
21.2
2
88.3
132.4
150
E30
29.6
2
123.3
176.2
200
208-3-60 17.6 123.0
27.5
2.3
5.2
10.0
None
-
-
-
39.5
50
E05
4.0
1
11.1
39.5
50
E07
5.6
1
15.5
39.5
50
E10
8.0
1
22.2
46.8
50
E15
11.9
2
33.0
60.3
70
E20
15.9
2
44.1
74.2
80
E30
22.2
2
61.6
96.0
100
230-3-60 17.6 123.0
27.5
2.3
5.2
10.0
None
-
-
-
39.5
50
E05
5.3
1
12.7
39.5
50
E07
7.5
1
18.0
41.6
50
E10
10.6
1
25.5
50.9
60
E15
15.9
2
38.2
66.8
70
E20
21.2
2
51.0
82.7
90
E30
29.6
2
71.2
108.0
110
460-3-60
9.6
70.0
15.0
1.3
2.6
5.0
None
-
-
-
20.9
30
E07
6.8
1
8.2
20.9
30
E10
10.1
1
12.1
24.7
30
E15
13.6
2
16.4
29.9
30
E20
19.5
2
23.5
38.8
40
E30
28.8
2
34.6
52.8
60
575-3-60
7.5
53.0
11.7
1.3
2.0
4.0
None
-
-
-
16.4
20
E10
10.6
1
10.2
20.2
25
E15
15.9
1
15.3
26.6
30
E20
21.2
2
20.4
33.0
35
E30
30.4
2
29.3
44.1
45
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZR036-060 With Powered Convenience Outlet (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA
LRA
MCC
FLA
FLA
FLA
Model
kW
Stages
Amps