background image

Furnace is multi-position and may be installed in any of the configurations shown.

Ensure that all PVC venting has at least 1/4” per foot slope towards the furnace.

The furnace condensate pan is self priming and contains an internal trap.

.

Do not install an external condensate trap

When drain hose routing changes are required (shown in red), be sure to cap
all unused openings.
If rerouting hoses - excess length should be cut off so that no sagging loops will
collect and hold condensate, which will cause the furnace to not operate.

Move rain gutter hose
to this position

HORIZONTAL LEFT

Move pressure switch
hose to this position.
NOTE: May require the
longer hose that is
provided with wider cabinets

Change condensate drain
connection to the 90° fitting provided

Move condensate drain hose
to this position

Move rain gutter hose to this position
NOTE: May require hose extension that
is provided with wider cabinets

UPFLOW

DOWNFLOW

Move condensate drain
hose to this position

Move rain gutter
hose to this position

Inducer must be rotated
90° in either direction for
this installation

HORIZONTAL RIGHT

Move pressure switch
hose to this position

Change condensate drain
connection to the 90° fitting provided

Move rain gutter hose
to this position

Move condensate drain hose
to this position

Move rain gutter hose
to this position

Move pressure switch
hose to this position.
NOTE: May require the
longer hose that is
provided with wider
cabinets.

AIRFLOW

AIRFLOW

AIRFLOW

AIRFLOW

MOST COMMON INSTALLATION CONFIGURATIONS (MORE OPTIONS AVAILABLE

WHICH IS COVERED IN THE INSTALLATION MANUAL)

WITH INDUCER ROTATION,

Rain
Gutter
Hose

Pressure
Switch
Hose

Condensate
Drain Hose

For

100,

120

&

130K

input

furnaces,

the

condensate

drain

is

factory

set

toward

the

lef

t

casing

outlet

For

040,

060

&

080K

input

furnaces,

the

condensate

drain

is

factory

set

toward

the

right

casing

outlet

MULTI-POSITION CONFIGURATION INFORMATION:

1

2

3

4

1

2

5

4

3

1

2

3

4

In upflow and downflow installation - Condensate drain hose may go out either side.

NOTE:

Only side venting on 130K unit.

Отзывы: