NOTES:
1.
Refer to the condensate management and drain hose
plumbing for different configurations in this document. No
hose clamps are needed for the condensate pan hook up.
2.
Drip leg in the gas line must be installed.
3.
The furnace controls require correct polarity on the power
supply and a proper ground.
4.
Y & G must be connected to the control board for cooling
operation.
5.
To measure total static pressure add supply duct pressure to
the return duct pressure, add pressure drop across the ‘A’
coil, and add pressure drop across the filter. Ignore negative
signs on the readings.
6.
Inlet gas pressure for natural gas should be 7” and that for
propane should be 11” w.c. Nominal manifold gas pressure
is 3.5” for natural gas and 10” w.c. for propane.
7.
If thermoplastic evaporator ‘A’ coil drain pans are to be
installed in the up-flow/horizontal configuration, then extra 2”
minimum spacing may be needed to ensure against drain
pan distortion.
8.
External filters required on all configurations.
9.
Electrical entry is available on both sides of the casing.
10. All 33”, 95% furnaces are approved for single-pipe and 2-
pipe systems. For single pipe systems it is recommended to
install the combustion air coupling provided and install
approximately 18” of PVC pipe on the furnace.
11. Do not install an external condensate trap on these fur-
naces, as it will prevent the unit from operating correctly.
Models
Airflow CFM (Bottom Return without Filters)
Minimum Wire
Size awg @ 75'
One-Way
Total Unit
Amps
Maximum
Over Current
Protection
0.5" ESP (Nominal)
Low
Med-Lo
Med-Hi
High
(T,G)G9S040A08MP11
581
653
818
950 14 8.0
15
(T,G)G9S060A10MP11
769
917
1038
1103 14 10.0
15
(T,G)G9S060B12MP11
713
872
1082
1243 14 10.0
15
(T,G)G9S080B12MP11
854
1008
1179
1370 14 10.0
15
(T,G)G9S080C16MP11
838
1250
1465
1671 14 11.5
15
(T,G)G9S080C22MP11
1285
1586
1937
2162
12 17.0
20
(T,G)G9S100C16MP11
819
1224
1477
1706 14 11.5
15
(T,G)G9S100C20MP11
1183
1430
1712
1934 12 17.0
20
(T,G)G9S120D16MP11
876
1254
1495
1805 14 11.5
15
(T,G)G9S120D20MP11
1190
1430
1739
1977 12 17.0
20
(T,G)G9S130D20MP11
1198
1459
1786
2047 12 17.0
20
Models
Maximum
Vent Equivalent
1
Factory Heating
Speed Setting
2
Temperature
Rise Range
Time For 1 ft
3
Natural Gas
(1030 Btu/Ft
3
)
Seconds On (Rate)
2"
3"
(T,G)G9S040A08MP11
65’
90’
Med-Hi 30°F-60°F
93
(T,G)G9S060A10MP11
65’
90’
High 30°F-60°F
62
(T,G)G9S060B12MP11
65’
90’
Med-Hi 30°F-60°F
62
(T,G)G9S080B12MP11
65’
90’
High 35°F-65°F
46
(T,G)G9S080C16MP11
65’
90’
High 35°F-65°F
46
(T,G)G9S080C22MP11
65’
90’
Med-Hi 35°F-65°F
46
(T,G)G9S100C16MP11
30’
90’
High 35°F-65°F
37
(T,G)G9S100C20MP11
30’
90’
Med-Hi 35°F-65°F
37
(T,G)G9S120D16MP11
30’
90’
High 40°F-70°F
30
(T,G)G9S120D20MP11
30’
90’
Med-Hi 35°F-65°F
30
(T,G)G9S130D20MP11
N/A 85’
High
45°F-75°F
28
1. For venting purposes, one 90° sweep elbow is equal to 5 Ft. of venting length, one 90° standard elbow is equal to 10 equiva-
lent feet of vent length. Vent termination elbows are included in these calculations, minimum required vent length is 5 ft.
2. Must be changed if not in rise range.
This document does not replace the installation instructions, which must be referred to for
detailed information.
CLEARANCES
* 24" clearance in front and 18" on side recommended for
service access.
All furnaces approved for alcove and attic installation.
DIMENSIONS
LED INDICATOR
Slow Green Flash
• Normal operation
Slow Amber Flash
• Normal operation with call for heat
Any Red Flash = Fault condition
Any Rapid 4 Flash = Potential fault codes / conditions
SUPPLY END
RETURN END
LEFT SIDE
Combustion Air Inlet
Condensate Drain
(Downflow)
Vent Connection
Outlet
Thermostat
Wiring
29.5”
28.5”
RIGHT SIDE
Condensate Drain
(Downflow)
14”
1”
1.5”
23”
Combustion Air Inlet
Gas Pipe
Entry
Electrical
Entry
Condensate
Drain
Optional Return Air
Cutout (Either side)
FRONT
A
33”
Clips can be flipped
into the up position
for coil cabinet or
plenum attachment
A-COIL
Follow all national, local codes and standards in addition to this document. The installation
must comply with regulations of the serving gas supplier, local building, heating, plumbing,
and other codes. In absence of local codes, the installation must comply with the national
codes and all authorities having jurisdiction.
B
24.25”
.56”
.56”
20”
3”
23.8”
.56”
Combustion
Air Inlet
2” Diameter
Vent Connection
Outlet
B
DURING INSTALLATION,
DOORS MUST REMAIN ON
FURNACE WHEN MOVING
OR LIFTING.
Vent Connection
Outlet
Application
Upflow
Downflow
Horizontal
Top
1" 0" 0"
Vent
0" 0" 0"
Rear
0" 0" 0"
Side
0" 0" 1"
Front*
0" 0" 0"
Floor
Combustible
Combustible
1
1. For combustible floors only when used with special
sub-base.
Combustible
Closet
Yes
Yes
Yes
Line Contact
No
No
Yes
Cabinet Size
A (in)
B (in)
All 'A' Cabinet Furnaces
14-1/2"
13-3/8"
All 'B' Cabinet Furnaces
17-1/2"
16-3/8"
All 'C' Cabinet Furnaces
21"
19-7/8"
All 'D' Cabinet Furnaces
24-1/2"
23-3/8"
QUICK REFERENCE GUIDE