5156631-UIM-G-0417
22
Johnson Controls Unitary Products
34
DC over Voltage
Software
Protection
Step 1.
High supply line voltage (greater than 253
VAC).
Check supply voltage to the outdoor unit.
(If high, contact utility provider.)
Step 2.
Verify fault clears.
If fault is still persistent; go to step 3.
Step 3.
Validate voltage (230 VAC).
Check supply voltage to the outdoor unit.
(If high, contact utility provider.)
Step 4.
Inverter internal damage.
Change out the inverter drive.
(Validate the fix. If the issue is persistent, reinstall the
original inverter drive, and go to the last step.)
Last Step.
If fault remains.
Contact JCI Technical Services.
35
DC under
Voltage Software
Protection
Step 1.
Low supply line voltage (less than
187 VAC).
Check supply voltage to the outdoor unit.
(If low, contact utility provider.)
Step 2.
Loose wire in control box area.
(Breaker terminal not secure.)
Loose wire: Check for loose wire in outdoor unit.
Verify bench circuit is sized right.
Step 3.
Verify fault clears.
If fault is still persistent, go to step 4.
Step 4.
Validate voltage (230 VAC).
Check supply voltage to the Outdoor Unit.
(If low, contact utility provider.)
Step 5.
Inverter internal damage.
Change out the inverter drive.
(Validate the fix. If the issue is persistent, reinstall the
original inverter drive, and go to the last step.)
Last Step.
If fault remains.
Contact JCI Technical Services.
TABLE 12:
Compressor Control Protection Fault (Continued)
INVERTER
FAULT CODE
FAULT
DESCRIPTION
POSSIBLE CAUSES
ACTIONS