Johnson & Starley LE155 & 250 Mk3ErP Скачать руководство пользователя страница 6

www.johnsonandstarley.co.uk

6

FIGURE 2.  KNOCKING OUT THE 100 mm SPIGOTS

7.  POSITIONING & PREPARATION

7.1 POSITIONING

7.1.1    The unit is best installed wall mounted in a kitchen above a cooker hood, but if this is 

not   practicable, it can positioned in the loft  or any suitable location.

7.1.2    It is not advisable to install the unit so that it is directly above a  bedroom  or  living  room 

ceiling, or in an area that is part of a living area or bedroom. If this is likely to cause a 
problem, please contact Johnson and Starley Ltd.

7.1.3    Consideration must be given to access for servicing, as  servicing  of  the  fans  and 

cleaning of the heat exchanger, which should be carried out annually.

7.2 

REMOTE SPEED CONTROL POSITION

7.2.1   The speed control is a remotely fitted control which can be fitted in a position of your 

choosing. The control is suitable for a single 32 mm deep back gang box which can 
be surface mounted. The front plate assembly can be fitted to an existing back box if 
required.

7.2.2   Remove the 2 screws securing the front plate assembly, and retain.
7.2.3   Follow the fitting instruction for the remote speed control.

7.3 

PREPARATION OF SPIGOTS

7.3.1   The unit is supplied with 100 / 125 mm spigots and for satisfactory operation on the 

unit where the airflow rate is above 33 l/s (see performance curves on page 14), it is 
recommended that  the centre part of the spigot is removed and 125 mm ducting used. 

7.3.2   The centre part of the spigot can easily be removed by placing a flat piece of wood (or 

similar) over the centre part and applying a sharp tap with a hammer (see Figure 2).

NOTE:

  

In situations where it is either not possible or not desirable to use 125 mm ducting, 100 
mm ducting can be used but it MUST be noted, in “BOOST” mode might increase noise 
levels.

7.4 

GENERAL PREPARATION

7.4.1   With reference to Figures 3 & 4, decide whether the unit is to be installed in the right 

or left handed configuration. If the handing of the unit is to be changed, proceed as 
follows: 
a.  Remove the 8 screws securing the blanking cover on the base tray. Remove the front 

cover then remove front sealing plate.

b. Alter wiring according to the circuit diagram (see Figure 9)
c. Swap the positions of the condensate drain blanking grommet, and the condensate 

drain elbow fitting  complete with plastic washers. 

d. Access to the drain elbow nut may be may gained through the extract aperture.
e. Replace the sealing plate, front door and base tray.

Содержание LE155 & 250 Mk3ErP

Страница 1: ...tarley co uk INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS LE155 250Mk3ErP High Efficiency Ventilation System with Heat Recovery These instructions are to be left with the User Publication No ZZ 1...

Страница 2: ...ots General Preparation Condensate 8 Mounting Installation 8 Wall Mounted with Slimline Cooker Hood Mounting in a Loft 9 Duct Duct Connections 9 10 Electrical 10 11 Wiring Diagram 11 12 Commissioning...

Страница 3: ...r The unit is supplied assembled for right hand configuration but may be changed to left hand configuration NOTE For additional ancillary equipment e g ducting grilles etc contact the Sales Dept at Jo...

Страница 4: ...stalling and using this equipment 5 4 Do not install this appliance where it is liable to be subject to water spray or where ducted air ambient temperature may exceed 40 C 5 5 When the unit is used to...

Страница 5: ...ystem Recuperative Thermal Efficiency of Heat Recovery 70 70 Maximum Flow Rate m h 199 241 Electrical Power Input at Maximum Flow Rate W 140 206 Sound Power Level LWA 46 48 Reference Flow Rate m h 139...

Страница 6: ...eed control 7 3 PREPARATION OF SPIGOTS 7 3 1 The unit is supplied with 100 125 mm spigots and for satisfactory operation on the unit where the airflow rate is above 33 l s see performance curves on pa...

Страница 7: ...already be provided as part of the building design The position of this point relative to where the heat recovery unit is to be installed is to be checked for any appreciable connection misalignment a...

Страница 8: ...NOTE For wall types other than masonry prepare the wall to suit a purpose made fixing 8 5 4 Referring to Figure 1 remove the front decor panel and gain access to the electrical panel by removing the...

Страница 9: ...the ventilation recovery system and building layout and suitable fire dampers MUST BE FITTED to protect against fire being transmitted through the ducting 9 4 Where rigid ducting is used it should be...

Страница 10: ...rown blue green yellow 0 75 mm to BS 6500 connected to a terminal block and exiting through a grommet and cable clamp at the right hand top of the unit NOTE If no external switched line is to be used...

Страница 11: ...11 Sales Spares Replacement Help Line 01604 762881 FIGURE 9 LE155 250 Mk 3 WIRING DIAGRAM 11 WIRING DIAGRAM COLOUR CODE BN BROWN BU BLUE BK BLACK GN GREEN GNYE GREEN YELLOW RD RED WH WHITE YE YELLOW...

Страница 12: ...ow rate before commencing 12 6 INSTALLER MODE NOTE The install mode has a time out function If the unit has been powered up but not commissioned within 3 hours then you will not be able to access the...

Страница 13: ...red airflow See Figure 9 12 6 4 On a larger premises when the required airflow has not been reached set JS9 to position 2 and adjust potentiometer RV2 until the required airflow is reached RED LED FLA...

Страница 14: ...3 12 11 1 In warm weather in order to reduce the effectiveness of the heat recovery switch to bypass mode the JS9 switch setting BYPASS reduces the supply fan to the minimum set commissioning speed Th...

Страница 15: ...15 Sales Spares Replacement Help Line 01604 762881 FIGURE 14 LE250 Mk3 FAN PERFORMANCE GRAPH FIGURE 13 LE155 Mk3 FAN PERFORMANCE GRAPH 13 FAN PERFORMANCE GRAPHS...

Страница 16: ...f not clean by washing in a soapy solution or with a light brush NOTE Under no circumstance must any sharp implement that is likely to distort or puncture the air passage walls be used 14 1 4 Refitmen...

Страница 17: ...If fans not speeding up on position one only then preset RV1 on the rear of switches requires adjusting Remove mains wait 20 seconds and reconnect mains Check fuse fuse spur for mains Is there 10 V pr...

Страница 18: ...www johnsonandstarley co uk 18 FIGURE 18 LE Mk3 DIMENSIONS 16 DIMENSIONS...

Страница 19: ...Circulating Fan H160 0199005 LE260 0198005 1 2 Supply Air Circulating Fan H160 0199005 LE260 0198005 1 3 Heat Exchanger 1000 0300175 1 4 Front Decor Panel H250 0210005 1 5 Sealing Plate Assembly H155...

Страница 20: ...n NN4 7LZ sales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 In the interest of continuous development Johnson Starley reserves th...

Отзывы: