Johnson & Starley LE155 & 250 Mk3ErP Скачать руководство пользователя страница 17

17

Sales/Spares & Replacement Help Line 01604 762881

JS9/10 SWITCH NOT WORKING

ONE OR BOTH FANS NOT BOOSTING

FANS NOT RUNNING

NO

YES

YES

YES

YES

YES

YES

BOTH

NO

NO

NO

YES

YES

NO

YES

NO

ONE

NO

BOTH

NO

NO

NO

NO

ONE

NO

YES

YES

YES

NO

One or both fan/s not boosting when both are required to boost?

Only one fan running.

Make sure there is no mains across TB1 2 & 6 i.e. No switched live & unit is not in installer mode (LED indicator should not be flashing)

With bathroom light or boost switch on: 

Is there mains present across terminal block 2 & 6

also across SL & N  on right side of PCB?

Remove  yellow of affected fan, labelled 7 or 8  and 

touch 10 V terminal screw on PCB Does fan now run 

at a fast speed?

Rotate switch from auto to 2. Do fans speed up?

Is switch 3 of dip switch in the on position?

Ether faulty PCB faulty 

or wires between 

terminal block 1 and 

PF1 or PF2 of PCB.  
There should be at 

least 1 V DC present 

on PF1 or PF2. If not 

replace PCB.

If in off position there will be a 2 minute delay

before fan/s will boost.

Open circuit between switched live source e.g. bathroom

light switch and the blue and black wires going into the

right hand side vertical terminal block of main PCB.

Make sure link is connected on underside TB3 1 & 2

Either faulty fan or connector.

Physically swap fans to determine what the issue is.

On the switch check voltage across GND and CTA. 

Is the voltage approximately 5 V DC?

A fan with 9 to 10 V across TB1 7 & 13 (GND) 

should be running at full speed. If not, replace fan.

On the switch, check voltage between GND and  EXT. Is the 

voltage between 2.4 and 5 V DC depending on RV2 setting ?

Switch 1 of dip switch should 

be in the on position.

If  fans not speeding up on position 

one only then preset  RV1 on the rear 

of switches requires adjusting.

Remove mains, wait 20 seconds and reconnect mains.

Check fuse & fuse spur 

for mains.

Is there 10 V present 

across TB1 12 & TB21 13?

Carefully turn RV1 fully clock wise.

Measure DC voltage across TB1 7 & 13

Remove mains cover. Is 

there mains going to the fans 

connectors?

Is there 10 V DC across blue & 

red of fan connector of either 

fan

With switched live still enabled - 

After 10 seconds press installer button.

Remove red wire from  TB1 12 

Does 10 V return to TB12A?

Is the voltage at least 9 to 10 V?

Remove mains supply & check continuity from the 

fan connectors to PCB. Check screws are tight and 

not trapping wire insulation.

One fan could be dragging 10 V DC line down. 

Unplug a fan at a time and see is 10 V line is restored. 

If so the unplugged fan is faulty. Both fans could have 

been damaged if unable to establish 10 V.

Remove mains supply & check continuity from the fan connectors to PCB. Check screws are tight and not trapping wire insulation.

Make sure switch 4 of dip switch in the off position as 

that will prevent supply fan from boosting.

Faulty Main PCB

Faulty Main PCB

One fan running

Is there 230 V AC present across TB2 & 4?

5 V DC is supplied from CTA & GND of 

PCB Via TB1 13 & 15. Check connections 

and cables for an open circuit, insulations 

clamped, etc.

Faulty PCB as it’s not detecting switched live 

is present across N and SL terminals.

2.4 and 5 V DC (depending on 

RV2 setting ) has to go to  is EXT & 

GND of PCB Via TB1 14 & 13. Check 

connections and cables for an open 

circuit, insulations clamped, etc.

Either Switch or PCB is faulty or a short between EXT and GND.  

Remove EXT wire and recheck voltage. 

If voltage goes up then check wiring for shorts.

Check PCB by linking TB1 14 to TB 15

If PCB is working then fans will run at full speed.

15.   TROUBLESHOOTING

Содержание LE155 & 250 Mk3ErP

Страница 1: ...tarley co uk INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS LE155 250Mk3ErP High Efficiency Ventilation System with Heat Recovery These instructions are to be left with the User Publication No ZZ 1...

Страница 2: ...ots General Preparation Condensate 8 Mounting Installation 8 Wall Mounted with Slimline Cooker Hood Mounting in a Loft 9 Duct Duct Connections 9 10 Electrical 10 11 Wiring Diagram 11 12 Commissioning...

Страница 3: ...r The unit is supplied assembled for right hand configuration but may be changed to left hand configuration NOTE For additional ancillary equipment e g ducting grilles etc contact the Sales Dept at Jo...

Страница 4: ...stalling and using this equipment 5 4 Do not install this appliance where it is liable to be subject to water spray or where ducted air ambient temperature may exceed 40 C 5 5 When the unit is used to...

Страница 5: ...ystem Recuperative Thermal Efficiency of Heat Recovery 70 70 Maximum Flow Rate m h 199 241 Electrical Power Input at Maximum Flow Rate W 140 206 Sound Power Level LWA 46 48 Reference Flow Rate m h 139...

Страница 6: ...eed control 7 3 PREPARATION OF SPIGOTS 7 3 1 The unit is supplied with 100 125 mm spigots and for satisfactory operation on the unit where the airflow rate is above 33 l s see performance curves on pa...

Страница 7: ...already be provided as part of the building design The position of this point relative to where the heat recovery unit is to be installed is to be checked for any appreciable connection misalignment a...

Страница 8: ...NOTE For wall types other than masonry prepare the wall to suit a purpose made fixing 8 5 4 Referring to Figure 1 remove the front decor panel and gain access to the electrical panel by removing the...

Страница 9: ...the ventilation recovery system and building layout and suitable fire dampers MUST BE FITTED to protect against fire being transmitted through the ducting 9 4 Where rigid ducting is used it should be...

Страница 10: ...rown blue green yellow 0 75 mm to BS 6500 connected to a terminal block and exiting through a grommet and cable clamp at the right hand top of the unit NOTE If no external switched line is to be used...

Страница 11: ...11 Sales Spares Replacement Help Line 01604 762881 FIGURE 9 LE155 250 Mk 3 WIRING DIAGRAM 11 WIRING DIAGRAM COLOUR CODE BN BROWN BU BLUE BK BLACK GN GREEN GNYE GREEN YELLOW RD RED WH WHITE YE YELLOW...

Страница 12: ...ow rate before commencing 12 6 INSTALLER MODE NOTE The install mode has a time out function If the unit has been powered up but not commissioned within 3 hours then you will not be able to access the...

Страница 13: ...red airflow See Figure 9 12 6 4 On a larger premises when the required airflow has not been reached set JS9 to position 2 and adjust potentiometer RV2 until the required airflow is reached RED LED FLA...

Страница 14: ...3 12 11 1 In warm weather in order to reduce the effectiveness of the heat recovery switch to bypass mode the JS9 switch setting BYPASS reduces the supply fan to the minimum set commissioning speed Th...

Страница 15: ...15 Sales Spares Replacement Help Line 01604 762881 FIGURE 14 LE250 Mk3 FAN PERFORMANCE GRAPH FIGURE 13 LE155 Mk3 FAN PERFORMANCE GRAPH 13 FAN PERFORMANCE GRAPHS...

Страница 16: ...f not clean by washing in a soapy solution or with a light brush NOTE Under no circumstance must any sharp implement that is likely to distort or puncture the air passage walls be used 14 1 4 Refitmen...

Страница 17: ...If fans not speeding up on position one only then preset RV1 on the rear of switches requires adjusting Remove mains wait 20 seconds and reconnect mains Check fuse fuse spur for mains Is there 10 V pr...

Страница 18: ...www johnsonandstarley co uk 18 FIGURE 18 LE Mk3 DIMENSIONS 16 DIMENSIONS...

Страница 19: ...Circulating Fan H160 0199005 LE260 0198005 1 2 Supply Air Circulating Fan H160 0199005 LE260 0198005 1 3 Heat Exchanger 1000 0300175 1 4 Front Decor Panel H250 0210005 1 5 Sealing Plate Assembly H155...

Страница 20: ...n NN4 7LZ sales johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 Fax 01604 767408 In the interest of continuous development Johnson Starley reserves th...

Отзывы: