4

3. 

BUILDING STANDARDS & REGULATIONS

NOTE:

 Installation shall be in accordance with the following

•  Building Standards (Scotland) (Consolidation) Regulations
•  Building Regulations Part L
•  The Water Fittings Regulations or Water byelaws in Scotland
•  Model and Local Authority Byelaws

 

•  BS 5720

 Mechanical Ventilation and Air Conditioning in Buildings

•  BS 7671 

Institute of Electrical Engineers (I.E.E) Wiring Regulations

•  Health & Safety Document No. 635.
•  The Electricity at Work Regulations, 1989.

IMPORTANT:

 This appliance is CE certificated for safety and performance. It is important that no modifications are made 

to this appliance, unless fully approved in writing by Johnson & Starley Ltd. 
If in doubt please Ring Johnson & Starley Ltd on Telephone: 01604 762881.

The manufacturers instructions supplied must not be taken as overriding any statutory requirements.

4. 

SAFETY INFORMATION

4.2 

HANDLING THE UNIT

4.2.1  The weight of the this appliance exceeds that recommended for a one-man lift. It will therefore be 

necessary to gain assistance at times during the removal from its packaging and during installation 
procedure. Manoeuvring the boiler may include the use of a sack truck and involve lifting, pushing and 
pulling.

4.2.2 

 It should be noted that this appliance may contain sharp edges. Care 

MUST

 be taken when handling 

the appliance to prevent injury. We advise the engineer to wear suitable P.P.E.

4.2.3 

Once the appliance has been fired beware that certain parts will be hot to the touch.

4.2.4 

Do not install flues during rain, high winds or in severe weather conditions.

4.1  

ELECTRICAL SUPPLY

4.1.1 

Ensure the mains supply voltage, frequency, number of phases and power rating comply with details 
on the rating label.

4.1.2 

All wiring must be in accordance with the appropriate standards. 

4.1.3 

Ensure safety regulations and practices are adhered to when installing and using this appliance.

5.    

TECHNICAL DATA

  TABLE 1                   ITEM

S-25

Nominal Rated Output

kW

25

Air on Temperature

˚C

20

Air off Temperature

˚C

67

Water Supply Temperature

˚C

80

Water Return Temperature

˚C

55

Water Flow Rate

l/s

0.25

Air Volume

m³/h

1584

Water Connections

bsp

¾

Maximum Water Pressure

Bar

3

Maximum Power Consumption        

W

530W

Dimensions mm

H/W/D

1078 x 480 x 710

Return Air Frame

mm

587 x 400     

Electrical Supply

A

230V, 50Hz, fuse rated at 3A

Weight

kg

70kg

Содержание AQUAIR S-25

Страница 1: ...Ltd Rhosili Road Brackmills Northampton NN4 7LZ Aquair Water To Air Space Heaters Aquair S 25 These instructions are to be left with the User INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS AQUAIRS...

Страница 2: ...ical Data 4 6 Positioning Preparation 5 7 Installation Instructions 5 Downflow Installation Water Connections Electrical Harness 8 Return Air System 5 9 Electrical 6 10 Circuit Diagram 6 11 Fan Perfor...

Страница 3: ...ter or Cleanflow air cleaner if fitted and the heat exchanger by a centrifugal fan and is discharged through the opposite end of the unit A Summer Air Circulation switch optional provides the facility...

Страница 4: ...removal from its packaging and during installation procedure Manoeuvring the boiler may include the use of a sack truck and involve lifting pushing and pulling 4 2 2 It should be noted that this appl...

Страница 5: ...ter cover to expose the two screw holding the door in place Remove the screws and gently pull and lift the door off the unit 7 3 2 Lift the appliance onto the plenum or base support and position corre...

Страница 6: ...ough the casing at the top left hand front The cable is suitable for a 230V 50Hz single phase supply 9 2 The means of isolating the appliance MUST be via a double pole switch with a contact separation...

Страница 7: ...pipe sensor and adjusted the fan speed as required remove short 13 5 WITH THERMISTA STAT FITTED 13 5 1 Turn up thermista stat to call for heat 13 5 2 Check for 230V on switch live out 13 5 3 With the...

Страница 8: ...250VAC across High Voltage terminals 2 4 Open circuit between clock out High Voltage terminal block 1 Unit mains supply is missing Check spur e g fuse is intact Check connections to high voltage term...

Страница 9: ...n 28K YES YES NO In there 230 250 VAC across high voltage terminals 1 2 If there 230 250 VAC across High Voltage terminals 1 2 Make sure mains is present across High Voltage terminals 2 3 Is the MAF s...

Страница 10: ...IST ITEM DESCRIPTION QTY S 25 1 Air filter 2 AQ25 0185005 2 Air circulation fan with EC technology 1 1000 0525980 3 PCB control board 1 1000 0526275 4 Temperature flow sensor 1 1000 0526505 5 Front Co...

Страница 11: ...lacement Help Line 01604 752881 18 EXPLODED DIAGRAM 1 2 5 3 6 4 SPIGOT FRAME FAN SLIDER SIDE KNOCKOUTS FLYING LEAD HOT WATER FLOW FROM HEAT SOURCE HOT WATER RE TURN FROM HEAT SOURCE FIGURE 8 AQUAIR S...

Страница 12: ...arley co uk customer service johnsonandstarley co uk service johnsonandstarley co uk marketing johnsonandstarley co uk Reception Customer Service 01604 762881 In the interest of continuous developemen...

Отзывы: