23
INDEX
1
Components Plate
2
Electromagnetic Valve
3
Connection Flange
4
Photoresistance
5
Release Button
6
Electrodes set
7
Nozzle Line
8
Automatic air flap
9
Control box
10
Pump
11
Motor
12
Body
13
Fan
14
Deflector
15
Transformer
16
Draught tube
MAIN COMPONENTS
16
6 7
8
9
10
11
12
13
14
1009DIS205
15
5
4
3
2
1
1009DIS391
DIAGNOSIS OF LMO EQUIPMENT FAULTS AND LOCK OUT
Description of operating anomalies
Visual indication
Possible causes
2 flashes
No flame signal
-
Faulty fuel valves
-
Faulty flame detector
-
Incorrect burner setting, no fuel
-
No ignition
3 flashes
Not used
4 flashes
Stray light on ignition
5 flashes
Not used
6 flashes
Not used
7 flashes
No flame signal during operation
-
Faulty fuel valves
-
Faulty flame detector
-
Incorrect burner setting, no fuel
8 flashes
Anomalies in fuel preheating time
9 flashes
Not used
10 flashes
Incorrect electrical connection or damage to equipment