background image

NBT

series Acidic Condensate pH Treatment Kits –– Installation/Operation & Maintenance

Installation

 

1.  Remove all bolts and nuts from the clear cover.
2.  Remove shipping bubble wrap and safely discard.
3.  Remove “Date of installation label” and the “red warranty tag”.
4.  Remove the pH Power Pellet® bags.
5.    Remove porous pellet bags from plastic shipping bags before placing in the NBT tank.

Floor mounting units: 

1.  Place the NBT tank in a location where it will not be a foot traffic hazard.
2.    Use clamps on inlet & outlet piping.

Operational Flow: 

1.  Once the heating unit is fired and acidic condensate is produced the condensate will flow from the heater condensate drain down 

into the NBT tank’s inlet port. The acidic condensate enters the bottom chamber of the tank below the flow baffle. The acid will now 

flow up through the baffle ports via gravity and slight head pressure at which point it comes in contact with the Magnesium Hydroxide 

Pellet bag (pH Power Pellets®). A chemical reaction now takes place in which ions from the acid and pellets are exchanged raising 

the ph level of the acid in the range of 5.0 to 9.0 pH. In this ranged the condensate can be safely be put to a waste drain via the NBT’s 

outlet port and piping. 

3

Содержание NBT Series

Страница 1: ...ion Maintenance Models NBT 610 NBT 230 14 Coleman Ave Westfield MA 01085 413 527 1893 690 Island Way Unit 206 Clearwater FL 33767 413 427 3373 jjmboilerworks com Revised August 2018 Acidic Waste Water...

Страница 2: ...sedbythefollowing A Improper Combustion B Contaminated Combustion Air C High Sulfur Content in Gas Supply D pH below 2 0 is considered hazardous waste by EPA Contact JJM Technical Service at 413 427 3...

Страница 3: ...BT 230 outlet level falls below 5 0 At a minimum the media bags must be changed once a year Use only JJM pH Power Pellet media bags DO NOTE USE LIMESTONE OR MARBLE CHIPS What is pH The pH measurement...

Страница 4: ...ing Operational Flow 1 Once the heating unit is fired and acidic condensate is produced the condensate will flow from the heater condensate drain down into the NBT tank s inlet port The acidic condens...

Страница 5: ...Boiler Works Inc 4 3 4 A B C D 7 8 3 5 INLET 7 8 From Base to Center 4D Outlet 3 1 2 Base to Center A E 6 50 E 1 NBT 610 pH Treatment Tank Part No 2010 NBT 23 pH Treatment Tank Ratings Dimensions in i...

Страница 6: ...nt Tank Single Unit Condensate Pump igure 3 Key A Rev 01 2016 NBT 23 pH Treatment Tank B C D E F Boilers Hot Water Heaters Furnaces Condensate Drains Trap Flue Pipe Trap Floor Drain Note Contact Facto...

Страница 7: ...d Piping Sizing D G Gas Water Trap G G C F F F F B E Piping Multiple Heating Units Single NBT 23 pH Treatment Kit Common Vent Piping Common Condensate Drain Figure 5 Key A Flue Drain B C D E Boilers H...

Страница 8: ...nd install electric heat tape provide and install electric heat tape and insula tion on the condensate drain lines and around the NBT tanks to prevent possibility of neutralizer tube damage or line bl...

Страница 9: ...rs dur ing re charging for cleaning of the tank bottom This should be done by a trained technician Contact your local wholesaler or manu facturer s representative for replacement parts Dealerlistingat...

Страница 10: ...your neutralizer pellets are incased in a porous pellet bag there are three methods to agitating the pellets 1 Remove the pellet bag or bags from the tank and using your hands move the pellets around...