How much fireside condensate will my equipment develop?

Hot water heaters / Boilers / Furnaces / Economizers

Multiple Boiler Common Flue drains:  33.3% of total BTU input of connected equipment. 
Example: (3) Boilers @ 100,000 BTU Input would need a pH treatment kit rated @ 100,000 

BTU for the stack drain and a flow rate of .725 to .798 depending on efficiency.

Consider the following when choosing a neutralizer for less maintenance during operation 

of your heating equipment.

1. Your location in relation to weather (Very Cold, Cold, Moderately Cold)

2. System Design (Process, Radiate, Snow Melt, Heating, etc.)

3. Yearly Operating Hours

4. pH level out of heating equipment (3.2 to 4.0 is normal)

5. If pH out of the heating equipment is below 3.2 pH contact the factory for sizing.

6. Abnormally low pH out of the equipment condensate drain can be caused by the following:

  A. Improper Combustion

  B. Contaminated Combustion Air

  C. High Sulfur Content in Gas Supply

  D. pH below 2.0 is considered hazardous waste by EPA. Contact JJM Technical 

       Service at 413-427-3373 or 413-527-1893

JJM® highly recommends operating your heating equipment for 24-48 

hours prior to connecting a neutralizer so as to flush out dirt, grease, and 

oils from connected piping and the heater. This is also the best time to check 

the heater condensate pH level for sizing your neutralizer.

 

!

WARNING

JJM® neutralizers are sized by BTU input to establish a flow rating. 

Job site conditions will determine neutralizer design.  See GPH chart below.

Equipment Efficiency

GPH Condensate

90%

.725 / Per 100,000 BTU Input

91%

.733 / Per 100,000 BTU Input

92%

.741 / Per 100,000 BTU Input

93%

.750 / Per 100,000 BTU Input

94%

.758 / Per 100,000 BTU Input

95%

.766 / Per 100,000 BTU Input

96%

.774 / Per 100,000 BTU Input

97%

.782 / Per 100,000 BTU Input

98%

.790 / Per 100,000 BTU Input

99%

.798 / Per 100,000 BTU Input

ALL JJM NEUTRALIZING PRODUCTS

1

Содержание CBM-227

Страница 1: ...tfield MA 01085 413 527 1893 690 Island Way Unit 206 Clearwater FL 33767 413 427 3373 jjmboilerworks net Revised April 2019 CBM 227 Installation Operation Maintenance Model CBM 227 Acidic Condensate p...

Страница 2: ...sedbythefollowing A Improper Combustion B Contaminated Combustion Air C High Sulfur Content in Gas Supply D pH below 2 0 is considered hazardous waste by EPA Contact JJM Technical Service at 413 427 3...

Страница 3: ...nal injury death or major property damage CAUTION Indicates a condition or hazard which will or can cause minor personal injury or property damage NOTICE Indicatesspecialattentionisneeded butnotdirect...

Страница 4: ...densate pH needs to be increased made more neutral to prevent possible damage to cast iron soil pipe ABS pipe septic tanks plants wastewater treatment plants and other materials handling waste water C...

Страница 5: ...ove the CBM inlet and outlet hose barb fittings and replace with threaded PVC fittings Include unions in the piping to allow removal of the CBM tube for inspection and service Secure pipe or tubing in...

Страница 6: ...technician immediately if flow through the overflow line is frequent or steady Make sure the installation complies with all local code requirements Piping for multiple boilers furnaces vent see figure...

Страница 7: ...s Individual pH Treatment Kits Common Piping C D E F Boilers Hot Water Heater Condensate Common Drain Common Flue Vent Neutralizer Tube or Tank House Drain Boilers Hot Water Heaters Furnaces Note Cont...

Страница 8: ...let falls below 5PH Local codes may have different requirement check with local authority Replacement parts Contact your local wholesaler or manu facturer s representative for replacement parts Dealer...

Страница 9: ...water to flush out the tank If your neutralizer pellets are incased in a porous pellet bag there are three methods to agitating the pellets 1 Remove the pellet bag or bags from the tank and using your...

Отзывы: