Installation
!
WARNING
THE INSTALLATION OF THIS APPLIANCE MUST BE CARRIED OUT AS PER THIS
MANUAL.
WE RECOMMEND THAT YOU USE A QUALIFIED INSTALLER TO CARRY OUT
THE INSTALLATION IN ACCORDANCE WITH AS 5601/AG 601 (GAS
INSTALLATION CODE), MANUFACTURER’S INSTALLATION INSTRUCTIONS,
LOCAL GAS FITTING REGULATIONS AND MUNICIPAL BUILDING CODES.
If you have any other enquiries, please contact the dealer from whom you
purchased your heater.
THIS APPLIANCE PANEL WEIGHT IS 59 KILOGRAMS. EXTREME CARE SHOULD BE
TAKEN WHEN HANDLING THE APPLIANCE.
Installation
The Jindara Derwent Inbuilt Heater is a zero clearance appliance and can be optionally installed in a false fireplace
or wall cavity made of combustible materials such as wood or chipboard. Jindara provide the heater with their own
flue kit, of flexible pipes of 60mm and 50mm diameter for the inlet and exhaust. For the gas supply a flexible hose
is provided and must be used.
ONLY TO BE CARRIED OUT BY AN AUTHORISED PERSON!
1.
Carefully remove the carton from the heater.
2.
Carefully unpack flue kit and logset (positioned at rear of heater.)
3.
Remove heater from pallet by undoing 3 x teck screws on sides and rear.
(a)
Remove the 2 screws holding lower fascia panel to the heater surround. (Refer Figure 1 on page 6.)
(b)
Disconnect connector from rear of controls and remove lower fascia. (Refer Figure 2 on page 26.)
(c)
Remove the 4 screws holding door assembly to the heater. Remove the door. (Refer Figures 2 & 3 on page 6.)
4.
Check the label on the inside of lower fascia panel to confirm gas type is appropriate for the gas supply available.
5.
Unpack the log set from its separate carton and ensure all components are undamaged and complete as per
diagrams. Position them in the firebox as per diagrams. (Refer to the diagrams on pages 6 & 7.)
6.
Replace the door assembly as per reverse of removal. Ensure arrows on door tabs are facing bottom. (Refer Figure 9
on page 7)
7.
Install the flue (Refer to diagrams on pages 8, 9,10 &11).
8.
Locate the heater body into the fireplace cavity, or pre-built wall cavity. (Refer to pages 8, 9,10 &11)
9.
Connect the gas supply, purge gas lines, check all connections for leaks, check pressures (Refer to diagram on page 27)
10.
Fix the appliance firmly in position using the 2 angle brackets fixed to the heater body.
11.
Connect the air inlet and exhaust flexible pipes to the outlets on the heater body. (Refer to diagram on next pages 8,
9,10 &11.) Use clamps to secure flexible pipes to outlets.
NOTE – The EXHAUST flue is colour coded RED at the heater body, both ends of the flexible flue pipe and at the collector
box on the flue terminal assembly. Both ends of both flexitubes may need to be expanded to allow clamps to firmly secure
tubes to outlets.
12.
Re-assemble heater in reverse order of above. Connect electrical cord to correctly wired and earthed 240 Volt AC
power point.
13.
Operate heater, check operation on both, Hi and Low settings. Ensure fan operates after initial warm-up period. (Refer
to the Trouble Shooting Guide on page 29 should any problems occur.)
HEATER INSTALLATION OVERVIEW - REFER TO 10 POINT COMMISSIONING CHECKLIST
Derwent High Efficiency Gas Log Fire
5