3.7.2
Digital inputs at X11 (safe digital inputs)
Safe digital inputs are connected to terminal X11.
Fig.
X11
type
Features
X11/Safe DI
SDI00 Safe digital input
STO 1 CH1
SDI00
SDI02
SDI01
SDI03
GND
GND
X11 / Safe - DI
SDI01 Safe digital input
STO 1 CH2
SDI02 Safe digital input
STO 2 CH1
SDI03 Safe digital input
STO 2 CH2
GND
Ground reference
GND
GND
Ground reference
GND
Table 3.17
Specification of the control inputs X11/Safe DI
Note:
Further details on the S1 function in conjunction with the DIP switch S-ADR
can be found in the document "JM-3000 - Integrated Safety Function S1"
(Item number: 60880300).
Specification of the
terminals
The X11 safety terminal is implemented with a 2-level 2x 3-pole plug-in
terminal with 3.5 mm pitch from Phoenix contact.
−
Type: MCDN 1.5/3-G1-3.5
CAUtIoN
In the case of high currents flowing across the ground terminals, a high-
impedance separation from the device ground is possible. This can lead to
malfunction of the drive (avoid circuit currents in the wiring).
Jetter AG
59
JetMove 3000
Electrical installation