Final Inspec�on

Once the flue system has been installed, a final inspection should be carried out.
Particular a�ention should be paid to:

50mm clearance requirement to combustibles from Safety Vent AIR pipe

100mm clearance requirement to combustibles from stove pipe

150mm clearance from transi�on to ceiling (stove pipe to safety vent) requirements

Flue height requirements per AS/NZS 2919

Elbow support bracket kit

VF-3-60-246

Use of bends

45o Bends can be used on this flue system. Either the stove pipe flue or the VisionLINE safety vent
flue can be offset. A maximum of two (2) sets of 45o elbows can be used. A maximum of 1800mm in
total can be run at a 45o angle.
If you are offse�ing VisionLINE safety vent pipe, you MUST brace the offset appropriately. 2
VisionLINE braces must be used to support the flue. (See fig 7) Furthermore, the joins must be sealed
using VisionLINE clamp braces (See fig 7)

FIG 7

PAGE 6

Содержание VisionLINE AIR

Страница 1: ...Safety Vent AIR Instruc on Manual...

Страница 2: ...sis ng of flues in 150 mm of 0 6 mm 316L stainless steel insulated with 25 mm Morgan Frax ceramic insula on with a density of 128 kg m air gap of 20 mm 20 mm Morgan Frax ceramic insula on 128 kg m and...

Страница 3: ...ystems and Flue System Clearances In Australia and New Zealand this flue system can ONLY be used for solid fuel systems Wood Preparation Before installation planning is essential for an efficient safe...

Страница 4: ...cannot be achieved additional frame work in the roof will be required to house the flue bracing bracket Please ensure clearances are met when fi ing the flue bracing bracket and constructing any addit...

Страница 5: ...he locked position VisionLINE safety vent AIR CANNOT be cut if you require smaller sections please contact your distributor Roof Penetration Once the safety vent AIR flue has passed though the roof th...

Страница 6: ...the flue system is compatible with direct spigot air intake If the fireplace uses a rear or floor entry intake system a T piece section can be used Part number VF 3 60 090 as the final VL stove pipe s...

Страница 7: ...eight requirements per AS NZS 2919 Elbow support bracket kit VF 3 60 246 Use of bends 45o Bends can be used on this flue system Either the stove pipe flue or the VisionLINE safety vent flue can be off...

Страница 8: ...UPPORT 2 8 VF 3 60 002 AIR FLUE SUPPORT 1 9 VF 3 60 108 AIR FLUE STOVE PIPE TO SAFETY VENT TRANSITION 10 VF 3 60 105 AIR FLUE STOVE PIPE 620 1080MM ADJUSTABLE 11 VF 3 60 104 AIR FLUE STOVE PIPE 420 61...

Страница 9: ...D 65 mm E 193 mm 148 5 Ceiling Ring VF 3 60 110 Flush spigot adapter 193 L 30 Adjustable Stove pipe 193 L 30 Stove pipe Part number Joined length Total length VF 3 60 100 220mm 250mm VF 3 60 106 970mm...

Отзывы: