Construction Specifications - Jetmaster Installation Using Hebel

Models 400 to 700D 26mm Models 850 to 1500  100mm

Содержание UNIVERSAL 440

Страница 1: ...ION INSTRUCTIONS JETMASTER VIC PTY LTD ACN 005 872 159 ABN13 659 821 337 444 Swan St Richmond VIC 3121 PO Box 5051 Burnley 3121 Phone 03 9429 5573 Fax 03 9427 0031 Website www jetmastervic com au Emai...

Страница 2: ...Specifications Jetmaster Brick Veneer Installation 7 Construction Specifications Jetmaster Installation Using Hebel 8 Construction Specifications Jetmaster Traditional Space Saver 9 Construction Speci...

Страница 3: ...Heating capacity Cu Meters MODEL A A1 B C D E Wood 440 470 510 330 610 200 200 75 500 570 600 350 650 200 200 85 600 670 700 350 650 200 200 100 600 LOW 670 700 350 600 200 200 100 700 SH 770 800 350...

Страница 4: ...be minimum 100mm thick This includes selected finish such as ceramic tiles marble or granite Must project forward of aperture by a minimum of 300mm Must project either side of aperture by a minimum of...

Страница 5: ...tapping screws through outer casing at bottom at each join and at top Also ensure that flues are ventilated at top and bottom and when using a cover cone drill a series of holes into the outer flue b...

Страница 6: ...ney If the height is too low remove the lintel and replace it at the required height Step 2 Check that your chimney is clean and free from obstructions From the measurements taken select the size of y...

Страница 7: ...fing materials any other combustible materials Flashing OPEN WOOD JETMASTER Minimum Flue Height Ridge Line Rotating Cowl Hearth Flue Termination The minimum flue length is 3 6 metres or above the ridg...

Страница 8: ...6 Construction Specifications Jetmaster Traditional Victorian...

Страница 9: ...7 Models 400 to 700D 26mm Models 850 to 1500 100mm FREE ROTATING COWL Construction Specifications Jetmaster Brick Veneer Installation...

Страница 10: ...8 Construction Specifications Jetmaster Installation Using Hebel Models 400 to 700D 26mm Models 850 to 1500 100mm...

Страница 11: ...9 Construction Specifications Jetmaster Traditional Space Saver Models 400 to 700D 26mm Models 850 to 1500 100mm Models 400 to 700D 26mm Models 850 to 1500 100mm...

Страница 12: ...10 Construction Specifications Jetmaster Traditional Edwardian On Stud Wall...

Страница 13: ...master allow 350mm minimum rafters Outer flue must be ventilated Side of firebox to edge of hearth minimum 200mm 12mm fibre cement sheet one course of brick Front of firebox to edge of hearth minimum...

Страница 14: ...el to recess firebox by maximum of one brick important allow 2mm expansion selected tile finish 12mm fibre cement sheet concrete hearth min 100mm high do not obstruct air intake raise firebox to level...

Страница 15: ...nce Do not block or restrict chimney or flue opening After installing the appliance check that the chimney flue system draws well Jetmaster recommends that all gas fires be serviced every 2 years All...

Страница 16: ...en fires require fresh air vents as per Clause 6 10 9 5 in AS NZS5601 1 2013 One or more ventilation openings with a combined free ventilation area of not less than the equivalent cross sectional area...

Страница 17: ...horter than 3 5 metres Maintain a minimum of 500mm from the bottom of the flue cowl to the nearest part of the roof if the flue cowl is at least 1m from a neighbouring structure If less than 1m the fl...

Страница 18: ...t will depend on the type of wood used and the general weather conditions Experience will soon show you how far however the damper should never be closed more than half way 6 When the fire has gone ou...

Страница 19: ...ls 1 Medium density woods are preferred for open fireplaces Softer woods Pines etc burn fast leaving a lot of ash and creosote Hard woods Red Gum etc can be best used when mixed with medium woods and...

Страница 20: ...18 JM 120 07 18 Specifications subject to change contact Jetmaster prior to commencement...