background image

Page 11

Please read these instructions before beginning

Step by step checklist

1.

Check the chimney for cracks, cavities and blockages and

repair these. The size of the Jetmaster Firebox is determined
by the minimum dimensions of the chimney flue. Minimum
flues areas are:

Model 500, 600, 700sh- 400 cm2

Model 700D, 850-450 cm2

Ensure that this area is maintained throughout the entire
chimney. Flues that are 10% smaller than this will work
depending on the height of the chimney. Chimney pots that
are too small should be removed. Conduct a smoke test prior
to a Jetmaster install to ensure the chimney properly draws.

If the chimney does not draw, do not proceed with the
installation. Further repairs may be required.

2.

Measure the width, depth height of the recess. The

following table lists the minimum dimensions of the recess

for each unit.

• Allow 25mm on each side of the firebox for insulation

A.

If recess is too large:

The recess can be reduced by inserting bricks or Hebel at
the sides and/or back, and where necessary between the
top of the unit and the underside of the lintel. The
existing hearth can also be built up either with bricks or
by forming a plinth.
Use Jetmaster fascias and trims to seals gaps less than
75mm between sides and top of the unit and masonry.

B.

If recess is too small:

The recess can be made deeper by removing the rollback
and smoke shelf. If the height is too low, remove the
lintel and replace at the required height.
If the sides have to be removed it is suggested an
experienced builder to do the work as the sides support
inner flues of the chimney.

NOTE: Allow 1-5mm expansion gap for all materials.

3.

Repair any cracks or cavities in the recess especially if it

has been chopped out to accommodate a specified unit size,
and the cavity between a double brick wall has been
exposed.

Note: No metal gather or flue is required if the chimney passes a
smoke test.

4.

Tape the insulation to back and sides of the Jetmaster

and slide into position, taking care not to snag the fibreglass
insulation against the sides.

Note:

A. Do not recess the unit by more than 110mm.

B. The two smoke outlets on the firebox marry up with the
existing chimney. (There must be a 200mm minimum to any
overhang above smoke outlets).

C. Do not obstruct air intake at the bottom of the unit.

5.

Use foil tape and cardboard to temporarily seal outer

edges of the unit to the chimney face then have a test fire
using a mixture of dry and damp paper to create a smokey
fire.

If continuous smoke spillage occurs, check the size of the
chimney pots and the chimney for blockages.

“Downdraught” (wind blowing down the chimney) is
recognised by occasional puffs of smoke. In this case use a
Jetmaster rotating cowl or a high wind cowl.

6.

Seal unit into position with the masonry, fascias or trims,

ensuring any air leak around frame is limited. Allow masonry
work to cure for a minimum of three days.

See next page for diagrams.

UNIT SIZE

WIDTH

DEPTH

HEIGHT

500

570

350

640

600

670

350

640

600 LOW

670

350

590

700SH

770

350

640

700 LOW

770

350

590

700D

770

400

690

850

920

450

740

850 LOW

920

450

690

1050

1100

500

790

1050 LOW

1100

500

690

6. Existing brick chimney installation

Содержание MARK 2 COAL 700SH LOW

Страница 1: ... only Other fuels may over fire and generate poisonous gases i e carbon monoxide Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Do not over fire If appliance or chimney connector glows you are over firing Over firing will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause ...

Страница 2: ...uction and contents WARNING Page Section Information 2 3 1 Getting started 4 2 Components and specifications Unit and Gather 5 2 Components and specifications Surround Cowl Logpan and Screen 6 3 Timber framing specs All units 7 4 Clearance requirements Hearth 8 4 Clearance requirements Enclosure construction 9 5 Flue Chimney requirements General requirements 10 5 Flue Chimney requirements Installa...

Страница 3: ... height of chimney between 14 16 feet 4 26 4 88m measured from the base of the appliance C Negative Pressure Negative pressure results from the imbalance of air available for the appliance to operate properly It can be strongest in lower levels of the house Causes include Exhaust fans kitchen bath etc Range hoods Combustion air requirements for furnaces water appliances and other combustion applia...

Страница 4: ...uate outdoor air for all combustion appliances and exhaust equipment Ensure furnace and air conditioning return vents are not located in the immediate vicinity of the appliance Avoid installing the appliance near doors walkways or small isolated spaces Recessed lighting should be a sealed can design Attic hatches weather stripped or sealed Attic mounted duct work and air handler joints and seams t...

Страница 5: ... 230 120 600 LOW 670 700 350 600 200 200 90 230 120 700S 770 800 350 650 200 200 90 230 120 700SH LOW 770 800 350 600 200 200 90 230 120 700 D 770 800 400 700 200 225 100 250 150 850 920 950 450 750 220 250 130 300 150 850 LOW 920 950 450 700 220 250 130 300 150 1050 1120 1150 500 800 240 300 150 320 180 1050 LOW 1120 1150 500 750 240 300 150 320 180 1050 LOW LOW 1120 1150 500 700 240 300 150 320 ...

Страница 6: ...achieve a visual design and such cowls can be used but must not restrict airflow from the flue pipe casings For gas applications an AGA approved cowl must be used C D Measurements are in mm and provided as a reference only Due to the nature of thick welded steel it is normal and expected for some imperfections and slightly out of square components It is recommended to not begin construction of cav...

Страница 7: ...50 1375 1170 575 850 LOW 1325 1170 575 1050 1425 1370 625 1050 LOW 1375 1370 625 1050 LOW LOW 1325 1370 625 Note Timber framing should be constructed using normal framing methods Image above is an example only Do not install finishing materials around the cavity until after the fireplace has been installed Frame height from top of the 100mm hebel hearth base Refer to the following page for hearth ...

Страница 8: ...k Hebel Powerpanel Clay bricks 75mmx110mmx230mm if used as a hearth must be laid on the 110mm edge combined with 12mm cement sheet See joint AS NZS 2918 2018 3 3 2 Bricks on the 75mm face is insufficient in terms of thermal resistivity to be compliant 200mm Brick Hebel 600mm min above firebox Powerpanel 75 preferred to reduce heat leakage between joins 50mm min clearance to outer flue to combustib...

Страница 9: ... to outer flange to 300mm above opening and 150mm to the sides Optional 3 or 4 sided 100mm surrounds are available If elevating unit above finished hearth level lower wall finishing must also be non combustible Clearance to an adjacent wall for units 440 1050 and should be installed to 1200mm as per clause 3 2 2 b 2918 2018 Wrap entire firebox and gather in 25mm fibreglass insulation to 200mm abov...

Страница 10: ...ation cap away from trees adjacent structures uneven roof lines and other obstructions Your local dealer is the expert in your geographic area and can usually make suggestions or discover solutions that will easily correct your flue problem Minimum height of flue system exit Solid fuel AS NZS 2918 2018 NOTICE Chimney performance may vary Trees buildings roof lines and wind conditions affect perfor...

Страница 11: ...er at crimped joins Fix outer non active flues to active inner flues use 3 x 25mm self tapping screws through outer flue at bottom at each join and on top at each join As an alternative rivet 4 x 25mm conduit saddles at each join top and bottom Ventilate the flues cut 4 x 25mm notches at bottom of first length of outer flue and top of outer flue in either the ceiling cavity or just below the ceili...

Страница 12: ...it is suggested an experienced builder to do the work as the sides support inner flues of the chimney NOTE Allow 1 5mm expansion gap for all materials 3 Repair any cracks or cavities in the recess especially if it has been chopped out to accommodate a specified unit size and the cavity between a double brick wall has been exposed Note No metal gather or flue is required if the chimney passes a smo...

Страница 13: ... masonry overhangs the smokeholes ensure at least 200mm clearance above the unit Ensure seal between brick edge and firebox front optional surround likely required to assist forming this seal as per below Fibreglass insulation to be packed all around firebox Do not cover smoke outlets Optional surrounds available to cover this gap No surround With optional surround to cover opening ...

Страница 14: ...t side towards you with the steel handle provided 2 In firebox lay your fire lighters 10 to 15 centimetres apart depending on the size of your firebox Do not use newspaper as a fire lighter On units that are installed with a dual spigot gather it is recommended to light 2 fires directly underneath the two separate flues 3 Add soft wood kindling in a criss cross pattern above the firelighters Softw...

Страница 15: ...AS NZS 2918 General notes Fuels The quality of firewood is extremely important How long a tree has been felled or dead for does not indicate how dry the wood is The best way to dry wood is to split it and expose the inner core allowing the sun to dry the wood naturally Good wood merchants will split the wood for you but may not season it for you The amount of you pay for your wood does not justify...

Отзывы: