7.    Use the wiring diagram schematic on the  

 

       inside of the control panel cover to  

 

 

       help wire the panel.  The incoming power  

 

       wires are outlined in green on the wiring  

 

       diagram.  Attach the incoming hot (black) 

 

       lead to the terminal block corresponding to  

 

       “L” in the UV control panel. Attach the   

 

       common (white) lead to the terminal block  

 

       corresponding to “N” in the control panel.  The   
       ground (green) lead is to be attached to the  

 

       terminal block corresponding to “GND” in the    
       control panel.
 

a.    The terminals are spring loaded, insert   

 

       a small flat head screw driver into the square 

                   opening of the terminal and use to lever          
 

       terminal open (pry away from round opening)  

 

       while inserting wire into round opening.

 

b.    Once wire is seated in round opening    

 

       release terminal by removing screwdriver 

                  from square opening.
8.    OPTIONAL: The Alarm Relay terminals can be   
       used if desired.  Drill a properly sized hole in    
       the UV control panel enclosure for a correctly                
       sized conduit to be used with the auxiliary 

 

       alarm leads.  The conduit should follow the  

 

       same rules applied to the incoming power wiring. 
       Connect one alarm lead to either the normally open     
       (NO) or normallyclosed (NC) terminal based on the  
       type of signal required by the alarm panel. 

  

       Connect the remaining lead to the common (C)    
       terminal.

WIRE THE CONTROL PANEL

1.  The UV unit operates on 120 VAC  

 

single-phase power.  A 15 amp circuit    
breaker on the main electrical panel  

 

should be used for the UV disinfection    
device. Make sure the breaker is “OFF”   
before continuing. 

2.  Install at least a #14 AWG copper wire    

cable from the specified breaker in the    

main electrical panel to the UV control    
panel.  

3.  The UV control panel is not equipped  

 

with knockouts for electrical conduit  

 

connections.  Drill a properly  

 

 

sized hole in the UV control  

 

 

panel enclosure for the chosen conduit.   
Ideally the conduit should enter from the  
bottom of the enclosure to increase  

 

protection against water infiltration into    

the panel.

NOTE:

 

Flexible conduit is ideal for UV device

 

4.    Attach all conduit and cable connectors   
       to the control panel.  Follow the conduit   
       manufacturer’s instructions for proper    
       connection installation.

 

NOTE:

 ONLY 

PROPER SIZE

 WATERTIGHT 

HUB AND FITTINGS CAN BE USED WHEN 
ATTACHING CONDUIT AND WIRING TO THE 
CONTROL PANEL. 

 Jet recommends using Carlon or T&B liquidtight 

non metallic conduit and fittings for field 

installations.

5.    Verify all connections are properly  

 

        installed and watertight.
6.    Pull all cables and wiring through the    
       conduit and connectors into the control   

       panel.  Allow sufficient wiring to make all  

       connections in the control panel.

JET Model 952 UV Disinfection 

Device Installation Instructions

FIGURE 5

Содержание 952

Страница 1: ...g components should be supplied by the installer 1 All Purpose Cement 2 Clear Cleaner for plastics 3 Drill with Universal Bit 4 Clean soft cloth 5 Isopropyl alcohol 6 Small slotted screwdriver 7 Wire...

Страница 2: ...not flow through the device correctly and the UV disinfection will not be effective See Figure 1 2 Clean the ends of the upstream and downstream piping and the hubs of the UV cross with clear plastic...

Страница 3: ...of the 1 PVC pipe See figure 3 The opposite end will already be glued to the bushing on the control panel UV lamp wire 4 Glue the other end of the 1 PVC pipe into the coupler that is on the UV insert...

Страница 4: ...remaining lead to the common C terminal WIRE THE CONTROL PANEL 1 The UV unit operates on 120 VAC single phase power A 15 amp circuit breaker on the main electrical panel should be used for the UV dis...

Страница 5: ...the disinfection chamber and riser until even with the final grade being no more than 6 below the bottom of the control panel 11 Turn the UV disinfection device on at the main electrical panel 12 The...

Страница 6: ...hose Water in Enclosure Enclosure cover not secure Conduit hub not secure Align and tighten enclosure cover Tighten conduit hub Lamp Active Light Not Lit No power from main breaker panel No power to U...

Страница 7: ...ure to follow the suggestions outlined in any associated product documentation or Owners Manuals Items normally consumed in service such as fuses filter cartridges spin plates grease oil etc are not w...

Отзывы: