BA-40100-02-V17 | 29
Operating instructions
• Setting the controller parameters (Xp, Tn, Tv), basic load, restric-
tion, setpoints, alarm parameters, and calibration data on start-up
with date and time
• Changing the controller parameters (Xp, Tn, Tv), basic load, restric-
tion, setpoints, alarm parameters, and calibration data with date
and time
• Configuration of the digital inputs
This data is stored on the memory card supplied and can be read direct-
ly on the TOPAX DX or with a PC.
The software version is stored together with a file (* LOG) as text file and
DATE (* DAT) as recorder file for each day.
Furthermore, the configuration can be saved.
For the installation of the memory card, refer to chapter “24 Memory
card” on page 54.
For the handling of the logbook, refer to section “19.1.21 Menu 5.6:
Logbook” on page 37.
18 Auto setup (First system self-setting)
Menu for the automatic determination of the parameters of the automat-
ic controller of disinfection
(duration max. 4 hours and 33 minutes)
ATTENTION!
System self-setting starts when the actual value is
stable near the setpoint.
The pH value of the water basin must range between 6.8 and 7.3.
The current settings of the automatic controller parameters are shown
in the self-setting menu. The process includes 4 main functions. Each
function unit must run off in a certain time. If the new value is not
reached within this time, an automatic calculation of the automatic con-
troller data cannot be accomplished and the system self-setting process
is stopped.
NOTE
Do not alter the recirculation capacity during system
self-setting.
Start
(measuring range 1,00 mg/l)
Wait for 3 minutes
(stand-by-time)
Output on 0%
Output on 100%
Confirmed with “OK”
News settings are imported
90 minutes
90 minutes
90 minutes
Stop
Back to the existing
old settings
End of process
Wait till disinfection is 10 %
than the default value.
Minimum wait: 3 minutes
Maximum wait: 90 minutes
Wait till disinfection reaches
the inital value
Maximum wait: 90 minutes
The system displays all parameters
that have been programmed by the
operator and waits for a
confirmation.
The controller keeps operating at
the existing settings till the new
ones are confirmed!
Wait till disinfection reaches
by another 10%
Maximum wait: 90 minutes
Fig. 22: Autosetup process