1. INTRODUCTION 

The Jerguson Model MTII4200 is a 4-20 mA, loop-powered HART compatible level transmitter intended to be used in 
conjunction with the Jerguson Magnicator II magnetic liquid level gage. 

The part number designator for the MTII4200 can be found below. 

MTII4200-#-#-#-#-#-#-###/###

COMM OPTION:

H=4-20mA w/ HART

HOUSING:

A= ALUMINUM w/ WINDOW (STD.)

S= STAINLESS STEEL w/ WINDOW

BA= ALUMINUM w/o WINDOW

TRANSMITTER ORIENTATION:
A= TOP LEFT HAND (STD.)

B= TOP RIGHT HAND

C= BOTTOM RIGHT HAND

D= BOTTOM LEFT HAND

ALARM SETTING:

L= 3.85 mA (DEFAULT)
H= 22.5 mA

MAX SENSING LENGTH
IN INCHES, ON 6 INCH INCREMENTS

LCD DISPLAY:
M= mA OUTPUT (DEFAULT)
I= INCHES
P= PERCENTAGE

ACTIVE SENSING LENGTH

IN INCHES

MOUNTING STYLE:

S= STRAIGHT (STD.)

H= HIGH TEMP EXTENDED

 

 

There are two main components that make up the MTII4200.  These two components are the electronics housing and the 
sensor housing (see Figs. 1 & 2).  These two components are assembled at the factory and should not be separated in 
the field. 
 
Figure 1. MTII4200-H-A-D-x-x-S-xxx/xxx Straight  Bottom Left Hand Assembly 

 

MAX ACTIVE SENSING LENGTH

(3.500)

DETERMINED BY SE

POSITION AT ASSEMBLY

FOR V19961-E1= 9.313 (REF.)

FOR V20816-E6 & V21037-T= 8.688 (REF.)

 

 

 

        Section: 

M500 

        Bulletin: 

M500.31 

            Date:        01-26-12 
Supersedes:        04-22-08

 

MTII4200 level Transmitter

 

Installation, Operation & 

Maintenance Instructions 

Содержание MTII4200 Series

Страница 1: ...D B TOP RIGHT HAND C BOTTOM RIGHT HAND D BOTTOM LEFT HAND ALARM SETTING L 3 85 mA DEFAULT H 22 5 mA MAX SENSING LENGTH IN INCHES ON 6 INCH INCREMENTS LCD DISPLAY M mA OUTPUT DEFAULT I INCHES P PERCENT...

Страница 2: ...II4200 transmitters are available in a single cavity explosion proof enclosure 2 1 MTII4200 Transmitter Specifications PARAMETER SPECIFICATIONS LEVEL OUTPUT Measured Variable Liquid level interface le...

Страница 3: ...f Operation The MTII4200 transmitters precisely sense the position of an external float by applying an interrogation pulse to a waveguide medium This current pulse causes a magnetic field to instantly...

Страница 4: ...Transmitter Always follow applicable local and national electrical codes and observe polarity when making electrical connections Never make electrical connections to the MTII4200 transmitter with powe...

Страница 5: ...how the HART protocol is applied to the MTII4200 level transmitter only Using the HART interface allows for calibration without having to remove the transmitter from the process and position the float...

Страница 6: ...to exit the program mode replace the calibration jumper to the ON position and return your controllers to automatic To set high value You should now be in the Range Values screen To set the 20 mA Upp...

Страница 7: ...n until it is Press the enter button to set the low level of the range At this time position the float magnet at the desired low level point and keep it there while pressing the Enter button and holdi...

Отзывы: