LEAK TESTING XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
GENERAL
Although all gas connections on the grill are leak
tested at the factory prior to shipment, a complete
gas tightness check must be performed at the
installation site. Periodically check the whole system
for leaks following the procedures listed below.
If the smell of gas is detected at anytime you should
immediately check the entire system for leaks.
BEFORE TESTING
Make sure all packing materials have been removed
from the grill, including the burner tie-down straps.
Make a soap solution that consists of one part liquid
detergent and one part water. You will need a spray
bottle, brush, or rag to apply the solution to the
fittings.
TO TEST
1. Turn off all control valves, and turn on the gas
supply.
2. Apply the soap solution to all pipe fittings, from
the natural gas regulator and supply valve or
from the L.P. cylinder up to and including the
pipe that connects to the burners. Soap bubbles
will appear where a leak is present.
3. If a leak is present, immediately turn off the gas
supply and tighten the leaky fittings.
4. Turn the gas back on and recheck.
5. If gas continues to leak from any of the fittings,
turn off the gas supply, and contact customer
service at 1-800-554-5799.
Only those parts recommended by the manufacturer
should be used on the side burner. Substitutions will
void the warranty.
GAS FLOW CHECK
Side burner is tested and adjusted at the factory prior
to shipment. However, variations in the local gas
supply may make it necessary to adjust the burners.
The flames of the burners should be visually
checked. Flames should be blue and stable with no
yellow tips, excessive noise or lifting.
WARNING
Do not use the side burner until all
connections have been checked and do not
leak.
Do not smoke while leak testing.
Never leak test with an open flame.
If any of these conditions exist, first check to see if
the burner is blocked by dirt, debris, spider webs, etc.
It is handy to keep a spray bottle of soapy water
near the shut-off valve of the gas supply line.
Spray all the fittings. Bubbles indicate leaks.
Disconnected LP cylinders must have threaded valve
plugs tightly installed, and must not be stored in a
building, garage or any other enclosed area.
The gas must be turned off at the supply cylinder
when the unit is not in use.
If the appliance is stored indoors the cylinder must be
disconnected and removed from the appliance.
Cylinders must be stored outdoors in a well-
ventilated area out of reach of children.
WARNING
Always check for leaks after every LP tank
change.
10