1.
Press the programming button for more than 10 seconds until the safety led (or error led, depending on the model)
flashes.
2.
Release the programming button. The safety (or error) led will flash between 1 and 10 times. This is the sensitivity level
selected (crush prevention). 1 indicates very sensitive (little crushing force) and 10 indicates very insensitive (a lot of crush-
ing force). See table.
3.
On pressing the START button, the sensitivity level will increase by one to give a stronger crushing force. If pressed again on
reaching level 10, it will return to level 1.
4.
Press the PROG button to exit sensitivity level programming mode.
No. of flashes
Crushing force (sensitivity margin) (approx. percentage)
1
10% (minimum)
2
20%
3
30%
4
40%
5
50%
6
60%
7
70%
8
80%
9
90%
10
100% (maximum)*
* Attention! It may not detect obstacles in some cases
Parameter configuration from programmer
There are different parameters that can be configured by portable programmer. Below is a description of the most basic. Refer
to the programmer instruction manual for further information.
Operation by Time
Indicates if the panel is programmed to operate by time
Operation by Pulses
Indicates if the panel is programmed to operate by pulses
Oper. counter limit
Indicates / selects the limit number of operations for the panel
Operation counter
Indicates the number of operations made to date
Autoclosing time
Indicates / selects the seconds of automatic standby time
Equip.
Shows an equipment identifier
Low speed starting
open
Indicates / selects slow speed at start of opening operation
Low speed starting
clos.
Indicates / selects slow speed at start of closing operation
BackJump Open
Indicates / Selects the back jump function for the opening operation
BackJump Close
Indicates / Selects the back jump function for the closing operation
Last 4cm inh. space
Indicates / selects the seconds or pulses equivalent to 4cm of distance for the disa bling
of the security band
Sec. C. Close
Indicates whether the panel allows for security contact closure
Time-only close
Indicate / select if the door can be time-closed. If the Sec. C. Close parameter is
enabled, closure through activation of the security contact is also possible