4. Install the fireplace onto the smoke pipe with the lower shelf of the fireplace 650mm (26 5/8’’)
above the finished floor. Make sure that all the fasteners are tight
5. Install all the internal components of the fireplace and firescreen to complete the installation.
View of Tatiana 997 Centrally-Located Fireplace
Warning: For centrally-located fireplaces, a minimum clearance to combustibles of 1.2m
(48’’) must be maintained 360
o
around the fireplace. For single wall smoke pipe, a
minimum clearance to combustibles of 45cm (18’’) must be maintained and, when
connected to the Bordelet Load Bearing Support, a minimum 220mm (8 -11/16’’) clearance
from the top of the smoke pipe flange to the ceiling must be maintained, especially with
slanted ceilings. Please adjust the height of the Bordelet Load Bearing Support
accordingly.