Configuring the check function for inputs E1 to E10 on power up
5.1.5
This function is used to check the status of the contacts of the inputs on power up of the transmitter
RSEF
. If a contact is « closed»
on power up, the transmitter will indicate an error by indicator lights
V1
and
V2
(4 flashes).
This function can be activated using
micro-switch No. 7.
1-
Deactivate the safety input of the transmitter
RSEF
(1)
2-
Activate or deactivate the input check function using
micro-switch No. 7
:
3-
Activate the safety input of the transmitter
RSEF
(2) ; the two indicator lights,
V1
and
V2
, flash alternately to indicate
the system is on standby for validation.
4-
Press the
validation
button
BPV
; indicator lights
V1
and
V2
go off.
5-
To exit this configuration mode, deactivate, then activate the safety input (1)(2).
6-
If the transmitter is in « manual » restart mode, press the restart button wired to input
17
(1) If an emergency stop palmswitch is wired on this input, the component must be locked.
(2) If an emergency stop palmswitch is wired on this input, the component must be unlocked.
Example of fault on input No. 3
(NO contact faulty) :
Note :
If the other setting has also been modified during this procedure (
as “Radio channel number” or “restart mode”), each modified
setting have to be performed one by one.