The User Manual of JAC200 Series General Frequency Converter
- 12 -
Chapter 3 Mechanical and Electrical Installation
3.1 Mechanical installation
3.1.1 Installation conditions
1) Ambient temperature: The surrounding ambient temperature has a high influence on the service life
of frequency converter so that the working temperature of frequency converter shall not exceed the
allowable temperature range (-10
℃~
50
℃
).
2) Mount the frequency converter on the surface of flame retardant and keep enough space around for
heat dissipation. The work of frequency converter may bring lots of heat. Then use the screw to
mount the frequency converter vertically on the erection support.
3) Please install the frequency converter in the place almost free from vibration. The vibration shall not
be more than 0.6G. Particularly keep the frequency converter away from the punch and other
equipments.
4) Keep away from the place with direct sunshine, moisture and water drips.
5) Keep away from the site with corrective, combustible and explosive gas in the air.
6) Keep away from the site with oil dirt, much dust and much metal dust.
7) JAC200 series plastic-shell product is a built-in product which must be installed in the final system.
The final system shall be set with fireproof shell, electrical protective enclosure and mechanical
protective enclosure according to local law and regulations as well as IEC standard requirements.
3.1.2Installation space requirements
The installation space reserved for JAC200series frequency converter will be different in
requirements due to different power levels.
The heat dissipation of JAC200 series frequency converter is bottom-up. When many frequency
converter are working, the parallel installation will be generally required. On the occasion that
upper layer-lower layer parallel installation is required, the heat of frequency converter in lower
layer may make the temperature of the equipment in upper layer rise so as to cause failure, therefore,
it is necessary to take measures e.g. installation of thermal insulation guide board.
3.1.3 Precautions in mechanical installation
Please note the following points in the installation of JAC200 series frequency converter:
1.The installation space is a enough heat dissipation space shall be kept for the frequency converter.
Please consider the heat dissipation of other devices in the cabinet when the space is reserved.
2.Please conduct vertical installation of frequency converter to help heat dissipation upwards. If
there are many frequency converts in the cabinet, please install them in parallel. For the occasion
where upper and lower installation is required
3.Make sure to adopt flame retardants as mounting bracket.
4.For application site with metal dust, it is recommended to install the radiator outside the cabinet.
The space in the fully closed cabinet shall be maximized as much as possible.