❻ MOUNTING AND WIRING MODULE
The WF case must be installed indoor use only. It can be fixed against a
wall with the screws supplied with the product.
Cabling of the transformer to the power supply:
-The WF case must be installed the nearest possible of the electric plug
The power plug must be accessible at all time in order to unplug the
device in case of emergency.
- Make sure that the power plug on which the transformer is plugged in
has a overcurrent and short-circuit protection breaker for 16A (20A for
US).
Wiring of the 4 output lines:
- Each line must be protected by a circuit breaker which should be identi
-
fied and easily accessible.
- The 230V (120V in the U.S) cables which are used to power the 4 lines
must have either a double insulation or a reinforced insulation.
- Cables used for wiring must be of type H05VV-F or H03VV-F and of
section 2x1,5mm².
Maximum electric charge :
For a 230V installation : 4000W (16A*) total over all lines and up to only
3500W on one single line.
For a 120V installation : 2000W (16A*) total over all lines and up to only
1700W on one single ligne. Use only power supply provided with product
120V 0.75A
*16A max for resistive load
1,7A max for inductive load
Max operating temperature : 45°C
Содержание WF-OL4
Страница 1: ...DEMO FR P 01 EN P 16 ES P 31 IT P 46 PT P 61 WF OL4 MODULE AUTOMATISME GUIDE D INSTALLATION RAPIDE ...
Страница 16: ...DEMO FR P 01 EN P 16 ES P 31 IT P 46 PT P 61 WF OL4 AUTOMATIQUE DEVICE QUICK INSTALLATION GUIDE ...
Страница 31: ...DEMO FR P 01 EN P 16 ES P 31 IT P 46 PT P 61 WF OL4 MÓDULO DE RIEGOSECTOR MANUAL DE INSTALACIÓN RÁPIDA ...
Страница 46: ...DEMO FR P 01 EN P 16 ES P 31 IT P 46 PT P 61 WF OL4 MODULO AUTOMATISMO GUIDA D INSTALLAZIONE RAPIDA ...
Страница 61: ...DEMO FR P 01 EN P 16 ES P 31 IT P 46 PT P 61 WF OL4 MÓDULO DE REGA SETORIAL GUIA DE INSTALAÇÃO RÁPIDA ...