DS1124     Revised: 10-Sep-2018

MOM-4

Monitored Output Module

© 2011 Janus Fire Systems. All rights reserved (4/2011) Janus Fire Systems® is a registered trademark of Janus Fire Systems.

The MOM-4 module provides a programmable source of power to control and operate output 

devices  including  notification  appliances  and  releasing  devices.  Additionally,  it  continuously 

supervises wiring connected to terminals A+, A- for open or short circuits and 24+ and 24- when 

24VDC is applied.

MOM-4 employs one red LED to indicate the status. In normal condition, the LED flashes. When the 

output is activated, the LED will turn on constantly. In case of trouble, the LED will turn off.
Since the system allows maximum 13 LEDs on devices to turn on constantly, if system already has 

13 lighted LEDs on devices, MOM-4 will not turn on the LED and keep flashing even if the output 

of MOM-4 is activated.

P/N

 99239

•  24 VDC Monitored Output Control

•  5.1k ohm EOL

•  NAC or Releasing Control

•  LED indicates activation of module

•  All terminals are power limited

• 

Listed  with  Potter/Amseco®,  Gentex®,  &  Cooper 

Wheelock®  sync modules and devices

• 

Maximum standby and alarm current 250 μA

•  For JFS-A Series control panels or JFS-IP Series control 

panels using Nohmi protocol

Features

Description

Figure 1: Installation into the compatible electrical box

Installation

Содержание MOM-4

Страница 1: ...When the output is activated the LED will turn on constantly In case of trouble the LED will turn off Since the system allows maximum 13 LEDs on devices to turn on constantly if system already has 13 lighted LEDs on devices MOM 4 will not turn on the LED and keep flashing even if the output of MOM 4 is activated P N 99239 24 VDC Monitored Output Control 5 1k ohm EOL NAC or Releasing Control LED in...

Страница 2: ...of each other and be enclosed within conduit or equivalently protected against mechanical injury When NACs are connected to MOM 4 module each MOM 4 module shall be separated by short circuit isolators SCI to avoid influence from a short circuit of the SLC Signal Line Circuit Wiring Diagram Setting the Address Figure 2 Output Connected to a Notification Appliance Circuit Page 2 of 4 SLC loop wiring...

Страница 3: ... 4 module The Manual Release Function immediately activates the Suppression System in the same zone It overrides Delay Time and Abort Functions for that zone Figure 3 Output Connected to a Releasing Device Before connecting an output device connect the module to the SLC loop and reset it with the FACP This is necessary to ensure that the internal relay is unlatched Connection of the module with th...

Страница 4: ...ated in the seller s sales contract or sales acknowledgment form Every attempt is made to keep our product information up to date and accurate All specific applications cannot be covered nor can all requirements be anticipated All specifications are subject to change without notice Note Approvals Listings maintained by and manufactured by Potter Electric Signal Company Ordering Information Model N...

Отзывы: