37
Measured value
Frequency
Measurement uncertainly
Voltage
15 .. 75Hz
±(0,2% rdg + 0,02% rng)
Current
45 .. 65Hz
±(0,2% rdg + 0,05% rng)
Current
15 .. 75Hz
±(0,6% rdg + 0,05% rng)
Phase
45 .. 65Hz
±0,5°
Phase
15 .. 75Hz
±2,0°
Real power
45 .. 65Hz
±(0,4% rdg + 0,0075% rng
cos
ϕ
= 1,0
Real power
45 .. 65Hz
±(0,75% rdg + 0,0075% rng
cos
ϕ
> 0,8
Real power
45 .. 65Hz
±(1,5% rdg + 0,0075% rng
cos
ϕ
> 0,5
Real power
15 .. 75Hz
±(6,0% rdg + 0,0075% rng
cos
ϕ
> 0,5
Messwert
Messunsicherheiten
Ganggenauigkeit der internen Uhr
±2 Minuten/Monat
Genauigkeitsklasse nach EN61036:1996, VDE0418Teil 7:Mai 1997, IEC1036:1996
mit Stromwandler ../5A
: Class 1
mit Stromwandler ../1A
: Class 2
Measured value
Range
Crest factor at max. rms value
Voltage low
5...140Vrms
1.5
Voltage high
5...500Vrms
1.5
Current low
0.005...1.2Arms
2
Current high
0.02...6Arms
2
The power measurement range is calculated from the voltage and current range.
Measurement uncertainty
The measurement uncertainty specification applies for the specified ranges, assuming the reading inside
the given limits. Beyond the limits the uncertainty is not specified. If not otherwise specified, the frequency
of all inputs is identical and in the range between 15 to 75Hz. The ambient temperature must be in the range
between 18 to 28°C. An additional error is to be calculated for ambient temperatures beyond this range.
Additional error for ambient temperatures outside the specified range:
+/- 0.01% rdg per degC.
Technical data