38
UMG 96RM-P/-CBM
Procedure in the event of faults
Possible fault
Cause
Remedy
No display
See instructions for basic device
No current display
See instructions for basic device
Current displayed is too large or
too small.
See instructions for basic device
Voltage displayed is too large or
too small.
See instructions for basic device
Voltage displayed is too small.
See instructions for basic device
Phase shift ind/cap.
See instructions for basic device
Effective power too large or too
small.
See instructions for basic device
Effective power, draw/supply
transposed.
See instructions for basic device
An output is not reacting.
See instructions for basic device
"EEE" in the display
See instructions for basic device
"EEE bAt" in the display
Battery capacity is too low
See "Battery monitoring function"
and "Replacing the battery"
No connection to device.
Incorrect device address
Correct device address.
Different bus speeds (baud rate)
Correct speed (baud rate)
Incorrect protocol.
Correct protocol.
Termination missing.
Terminate bus with termination
resistor.