28
UMG 96RM-P/-CBM
Screening
Twisted screened cable should be used for connections
via the RS485 interface.
•
Earth the screens of all cables that lead to
the cabinet, upon entering the cabinet.
•
Connect the screens over a generous area and in a
manner that will conduct well, to a low-noise earth.
•
Gather the cables mechanically above the earthing
clamp in order to avoid damage due to cable
movements.
•
Use suitable cable glands to feed the cables
into the cabinet - for example armoured conduit
couplings.
Cable type
The cable used must be suitable for an environmental
temperature of at least 80°C.
Recommended cable types:
Unitronic Li2YCY(TP) 2x2x0.22 (from Lapp Kabel)
Unitronic BUS L2/FIP 1x2x0.64 (from Lapp Kabel)
Maximum cable length
1200m at a baud rate of 38.4k.
Transfer speeds
in Kbit/s
Max.
segment length
9.6; 19.2; 45.45; 93.75
1200m
187.5
1000m
500
400m
1500
200m
3000; 6000; 12000
100m
Table: Segment lengths per Profibus specification.
Cable
Strain relief
Screen braid of the cable
Earthing clamp
Low-noise earth
Fig. Screening procedure at cabinet entry.