background image

 16 / 16

2

Safety

Safety information
The installation manual is not a complete 
directory of all safety measures required to 
operate the device.
Special operating conditions may require further 
measures. The installation manual contains 
instructions that must be observed to ensure 
your personal safety and to prevent damage to 
property.

Symbols used:

c

This symbol is an addition to the 
safety instructions and indicates 
an electrical hazard.

m

This symbol is an addition to the 
safety instructions and indicates 
a potential hazard.

C

This symbol with the word 

NOTE! 

describes:

•  Procedures that do not pose 

any risks of injures.

•  Important information, 

procedures or handling steps.

Safety information is highlighted by a warning 
triangle and is indicated as follows depending 
on the degree of danger:

m

DANGER!

Indicates an imminent danger that 
causes severe or fatal injuries.

m

WARNING!

Indicates a potentially hazardous 
situation that can cause severe 
injuries or death.

m

CAUTION!

Indicates a potentially hazardous 
situation that can cause minor 
injuries or damage to property.

Safety measures
When operating electrical devices, certain parts 
of these devices are invariably subjected to 
hazardous voltage. Therefore, severe bodily 
injuries or damage to property can occur if they 
are not handled properly:

•  Before connecting connections, earth the 

device at the ground wire connection if 
present.

•  Hazardous voltages may be present in all 

switching parts that are connected to the 
power supply.

3

•  Hazardous voltages may also be present 

in the device even after disconnecting the 
supply voltage (capacitor storage).

•  Do not operate equipment with current 

transformer circuits while open.

•  Do not exceed the threshold values specified 

in the user manual and on the rating plate. 
Also adhere to this when inspecting and 
commissioning.

•  Observe the safety and warning instructions in 

the documents that belong to the device! 

Qualified staff

In order to prevent personal injuries and damage 
to property, only qualified staff with electrical 
training may work on the device, with knowledge 
of

•  the national accident prevention regulations
•  the safety engineering standards
•  installing, commissioning and operating the 

device.

Proper use

The device is

•  intended for installation in switch cabinets 

and small installation distributors (please 
observe step 3 "Assembly").

•  not intended for installation in vehicles! 

The use of the device in mobile equipment 
is considered to be non-standard 
environmental conditions and is therefore 
only permitted after separate agreement.

•  not intended for installation in environments 

with hazardous oils, acids, gases, vapours, 
dusts, radiation, etc.

The prerequisites of faultless, safe operation 
of this device are proper transport and proper 
storage, set-up, installation, operation and 
maintenance.

1

Doc. no. 2.040.123.1.a

 

Power Analyser

UMG 96 RM-M

Installation manual

 Installation

 Device settings

Power Analyser

16

17

5

6

8

7

Voltage measurement

The UMG 96 RM-M has 3 voltage measurement 
inputs and is suitable for various connection variants, 
with direct connection or via voltage transformer.

L2
L3
N

L1

Voltage measurement connection variant 

3p 4w

(Addr. 509 = 0, standard setting)

Circuit breaker

Fuse (UL/IEC listed)

m

CAUTION!

Risk of injuries or 
damage to the device

Disregard of the connection conditions for the 
voltage measurement inputs can result in injuries 
or to the device being damaged.
Therefore, note the following:

• 

The voltage measurement inputs

 

-

must not be occupied with DC voltage.

 

-

must be provided with a suitable, labelled 
fuse that is positioned close by and 
a circuit breaker (alternatively: 
a line safety switch).

 

-

are dangerous to touch.

• 

Voltages that exceed the allowed network 
rated voltages must be connected via 
a voltage transformer.

• 

Measured voltages and measured currents 
must derive from the same network!

C

NOTE!
As an alternative to the fuse and circuit 
breaker, you can use a line safety switch.

4

The UMG 96 RM-M is a multi-functional 
network analyser, which

•  measures and calculates electrical variables 

such as voltage, current, power, energy, 
harmonics, etc. in building installations, 
on distribution units, circuit breakers and 
busbar trunking systems.

•  displays and saves measurement results 

and transmits them via interfaces.

Device short description

Install the UMG 96 RM-M in the weatherproof front 
panel of switch cabinets.

Cut-out size:
92

+0.8

 x 92

+0.8

 mm

Ensure! 
Adequate ventilation
•   install the device 

vertically!

•   adhere to clearances from 

neighbouring components!

Fig. Installation situation, 
rear view

Assembly

m

CAUTION!

Damage to property due to 
disregard of the installation 
instructions

Failing to observe the installation instructions can 
damage or destroy your device.
Ensure that there is adequate air circulation in your 
installation environment; if the ambient temperatures 
are high, ensure there is adequate cooling if required.

Connecting the supply voltage

m

CAUTION!

Damage to property due to 
disregard of the connection 
conditions or impermissible 
voltage swells

Your device can be damaged or destroyed 
by a failure to comply with the connection 
conditions or by exceeding the permissible 
voltage range.
Before connecting the device to the supply 
voltage, please check:

• 

Voltage and frequency correspond to the 
details on the ratings plate! Threshold 
values stipulated in the user manual have 
been complied with!

• 

In building installations, the supply 
voltage must be protected with a UL/IEC 
approved circuit breaker / a fuse!

• 

The circuit breaker

 

-

must be easily accessible for the user 
and be installed close to the device.

 

-

must be labelled for the relevant device.

• 

Do not connect the supply voltage to the 
voltage transformers.

• 

Provide a fuse for the neutral conductor 
if the source's neutral conductor 
connection is not earthed.

The supply voltage level for your device is 
specified on the rating plate.
After connecting the supply voltage, an indication 
is shown on the display. If no indication appears, 
check whether the supply voltage is within the 
rated voltage range.

c

WARNING!

Risk of injury due 
to electric voltage!

Serious bodily injury or death can result from:

•  Contact with bare or stripped live wires.
•  Device inputs that are dangerous to touch.

De-energise your device before starting 
work! Check that it is de-energised.

Network systems

Three-phase four-conductor systems

with earthed neutral conductor

Three-phase four-conductor systems

with non-earthed neutral conductor 

(IT networks)

Three-phase, three-conductor systems

Not earthed

Three-phase, three-conductor systems

with earthed phase

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

U

L-N

 / U

L-L

277 VLN / 480 VLL

U

L-N

 / U

L-L

277 VLN / 480 VLL

U

L-L

480 VLL

U

L-L

240 VLL

Single-phase, two-conductor systems

with earthed neutral conductor

Separated single-phase, 

three-conductor systems

with earthed neutral conductor

The device can be used in 

•  2, 3 and 4 conductor 

networks (TN, TT and 
IT networks)

•  Residential and 

industrial applications

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

U

L-N

230 VLN

U

L-N

 / U

L-L

240 VLN / 480 VLL

Voltage measurement connection variants

Current measurement I1, I2, I3

The UMG 96 RM-M

•  enables current measurements via current 

transformer only.

•  enables the connection of current transformers 

with secondary currents of ../1 A and ../5 A.

•  has the current transformer ratio 5/5 A set as 

standard.

•  measures AC currents, does not measure DC 

currents!

c

WARNING!

Risk of injury due 
to electric voltage!

Serious bodily injury or death can result from:

•  Contact with bare or stripped live wires.
•  Current measurement inputs that are 

dangerous to touch on the device and on the 
current transformers.

De-energise your device before starting 
work! Check that it is de-energised.
Earth your system! Use the earth connection 
points with earthing symbols for this! 
Earth the secondary windings of current 
transformers and all of the metal parts of the 
transformer that could be touched!

c

WARNING!

Risk of injury due to 
large currents and high 
electric voltages!

Current transformers operating with an open 
secondary circuit (high voltage peaks) can result 
in serious or even fatal injuries.
Avoid open operation of the current transformers - 
short-circuit unloaded transformers! 

3p 4w

(Addr. 509 = 0, standard setting)

3p 4wu

(Addr. 509 = 1)

3p 4u

(Addr. 509 = 2)

3p 2u

(Addr. 509 = 5)

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

Measurement with 3 phase 

conductors and neutral conductor.

Measurement via voltage 

transformer with 3 phase 

conductors and a neutral 

conductor.

Measurement with 3 phase 

conductors without neutral 

conductor. Measured values which 

require an N, use a calculated N. 

Measurement via voltage 

transformer with 3 phase 

conductors without neutral 

conductor. Measured values which 

require an N, use a calculated N.

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

1p 2w1

(Addr. 509 = 4)

2p 4w

(Addr. 509 = 3)

1p 2w

(Addr. 509 = 6)

3p 1w

(Addr. 509 = 7)

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

Measured values derived from 

voltage measurement inputs V2 

and V3 are taken to be 0 and are 

not calculated.

System with equal loading of the 

phases. The measured values of 

the voltage measurement input V2 

are calculated.

TN-C system with 1-phase, three-

conductor connection. Measured 

values derived from voltage 

measurement input V3 are taken to 

be 0 and are not calculated.

3 systems with equal loading of 

the phases. The measured values 

for the phases that are not created 

(L2/L3, L1/L3, L1/L2) for the 

relevant systems are calculated.

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

L2
L3
N

L1

Load

Connection variant 

3p 4w current measurement

 

(I1, I2, I3) via current transformer

 (Addr. 510 = 0, 

standard setting).

Connection variants for current measurement I1, I2, I3

9

C

NOTE!
With measurement range exceeding, 
the measurement device display shows 

"EEE"

. Further information on this can 

be found in the user manual.

3p 2i

(Addr. 510 = 1)

3p 2i0

(Addr. 510 = 2)

3p 3w3

(Addr. 510 = 3)

3p 3w

(Addr. 510 = 4)

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

System with equal loading of the 

phases. The measured values for 

current measurement input I2 are 

measured.

The measured values for current 

measurement input I2 are 

calculated.

Measurement in the 3-phase 

network with unequal loading. 

Measurement in the 3-phase 

network with equal loading.  

The measured values for current 

measurement inputs I2 and I3 are 

calculated.

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

2p 4w

(Addr. 510 = 5)

1p 2i

(Addr. 510 = 6)

1p 2w

(Addr. 510 = 7)

3p 1w

(Addr. 510 = 8)

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

System with equal loading of the 

phases. The measured values for 

current measurement input I2 are 

calculated.

Measured values derived from 

current measurement input I3 

are taken to be 0 and are not 

calculated.

Measured values derived from 

current measurement inputs I2 and 

I3 are taken to be 0 and are not 

calculated.

3 systems with equal loading of 

the phases. The measured values 

for the phases that are not created 

(L2/L3, L1/L3, L1/L2) for the 

relevant systems are calculated.

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

18

10

11

12

C

NOTE!
For further information on device func-
tions, data and assembly, see the user 
manual.

C

NOTE!
Information on current data and current 
transformer data can be found in the user 
manual.

Suitable network systems and maximum rated voltages (DIN EN 61010-1/A1):

The voltage measurement inputs are designed for 
measurements in low voltage networks, in which 
rated voltages of up to 

•  277 V phase to earth and 480 V phase to phase 

in the 4-conductor system or

•  480 V phase to phase in the 3-conductor system

occur.
The measurement and surge voltages meet 
overvoltage category 300 V CATIII. 

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

Part no. 

33.03.218

Fuse

N

L

Circuit breaker

Fig. Connecting supply voltage.

14

Programming mode

•  Press and hold buttons 1 and 2 simultaneously 

for 1 second to switch between 

display mode

 

and 

programming mode

. The text 

PRG 

appears in the display.

•  Configure the necessary settings for the 

operation of the device in programming mode.

•  The programming mode can be protected with 

a user password.

•  Button 2 switches between the programming 

menus:
1. 

Current transformer

2. 

Voltage transformer

3. 

Parameter list

The device switches from 

programming mode

 to 

display mode

 if

•  no buttons are pressed for 60 seconds.
•  buttons 1 and 2 are pressed simultaneously for 

1 second.

C

NOTE!
The following section contains an 
explanation of the programming menus 
current transformer, voltage transformer 
and parameters.
For further information on the 
programming menus and interfaces, see 
the device's user manual.

C

NOTE!
Changes are only applied after exiting 
programming mode.  

Programming the current transformer

1.  Switch to programming mode.
2.  The symbols for programming mode 

PRG 

and for the current transformer 

CT appear.

3.  Press button 1 - the first digit of the input 

field for the primary current flashes.

4.  Use button 2 to select the value for the 

1st digit.

5.  Use button 1 to move to the 2nd. digit.
6.  Use button 2 to select the value of the 

2nd digit.

7.  Use button 1 to move to the 3rd digit.
8.  Use button 2 to select the value of the 

3rd digit.

9.  Confirm with button 1.
10. The complete number flashes.
11. Use button 2 to select the decimal place and 

thus the unit of the primary current.

12. Confirm with button 1.
13. The input range of the secondary current 

flashes. 

14. Use button 2 to set the secondary current 

(value 1 A or 5 A). 

15. Confirm with button 1.
16. Pressing buttons 1 and 2 simultaneously 

(1. sec.) exits the programming mode. 
Use button 2 to change to the input field for 
the voltage transformer.

Current transformer 

symbol

Unit indicator

Current transformer, 

primary
Programming mode

Current transformer, 

secondary

C

NOTE!

•  Changes are only applied after exiting 

programming mode.

•  For further information on current 

transformers and current transformer 
ratios, see the user manual.

Fig. "Current transformer" input area

15

Programming voltage transformers

1.  Switch to programming mode.
2.  The symbols for programming mode 

PRG 

and for the current transformer 

CT appear.

3.  Use button 2 to change to programming 

mode for the voltage transformer.

4.  The symbols for Programming mode 

PRG

and for the voltage transformer 

VT appear.

5.  Press button 1 to confirm - the first digit 

of the input area for the primary voltage 
flashes.

6.  Use button 2 to select the value for the 

1st digit.

7.  Use button 1 to move to the 2nd. digit.
8.  Use button 2 to select the value of the 

2nd digit.

9.  Use button 1 to move to the 3rd digit.
10. Use button 2 to select the value of the 

3rd digit.

11. Confirm with button 1.
12. The complete number flashes.
13. Use button 2 to select the decimal place and 

thus the unit of the primary voltage.

14. Confirm with button 1.
15. The input range of the secondary voltage 

flashes. 

16. Set the secondary voltage with button 2. 
17. Confirm with button 1.
18. Pressing buttons 1 and 2 simultaneously  

(1. sec.) exits the programming mode.  
Use button 2 to change to the programming 
mode for the parameter list.

Unit indicator

Voltage transformer, 
primary

Programming mode

Voltage transformer, 
secondary
Voltage transformer 
symbol

C

NOTE!

•  Changes are only applied after 

exiting programming mode.

•  Further information on voltage 

transformers and voltage transform-
er ratios can be found in the user 
manual.

Fig. "Voltage transformer" input area

Programming parameters

1.  Switch to programming mode.
2.  The symbols for programming mode 

PRG 

and for the current transformer 

CT appear.

3.  Use button 2 to switch to programming 

mode for the parameters.

4.  The device shows the symbol for the 

programming mode 

PRG, the address 000 and 

the value of the address (001, standard setting) 
are displayed (the device shows the most 
recently set address and the associated value).

5.  Press button 1 to confirm - the first digit of 

the input area for the parameter flashes.

6.  Use button 2 to select the value for the 1st digit.
7.  Use button 1 to move to the 2nd. digit.
8.  Use button 2 to select the value of the 2nd digit.
9.  Use button 1 to move to the 3rd digit.
10.  Use button 2 to select the value of the 3rd digit.
11. Confirm with button 1.
12. Pressing buttons 1 and 2 simultaneously  

(1. sec.) exits the programming mode.  
Use button 2 to change to the programming 
mode for the parameter list.

Parameter (primary 
device address 000)

Value of the 
parameter 
(address range)

Programming mode

C

NOTE!
You can find a parameter list (addresses) and information on the parameters (e.g. primary and 
secondary device addresses) in the user manual or on our website.

Parameter “primary device address” (addr. 000)
In a bus structure, a master differentiates 
between the connected devices on the basis of 
the device address.

•  The address range lies between a value  

of 0 and 255.

•  Reserved ranges (do not use!): 

- Value 0  
- Values 251 to 255 

Parameter “secondary device address” 
(addr. 081-084)
The parameter “secondary device address” 
offers the option of addressing more than 
250 devices in your bus structure.

M-Bus interface

M-Bus interface, 
2-pole plug contact 

M+
M-

The M-Bus interface of the device facilitates 
communication (meter data transfer) via the 
M-Bus protocol with a Master device.

The UMG 96 RM-M loads the M-Bus with 
an M-Bus device load of 1.5 mA.

Baud rate (addr. 001, see step 17)
Select a common Baud rate for the M-Bus 
interfaces in one Bus structure (see step 10)! 

C

NOTE!
Configure the Baud rate on the device 
(addr. 001). Configuration via M-Bus is 
excluded.

Setting

(Addr. 001)

Baud rate 

(in Baud)

0

300

1

600

2

1200

3

2400

4

4800

5

9600

6

19200

7

38400

Device 

standard setting

Establish the connection to the PC

Communication connections:

More information on device configuration and 
communication is provided as of step 12.

1.

PC 

(GridVis)

Level 

converter

UMG 96 

RM-M

UMG 96 

RM-M

RS232

M bus

Device connection with a PC via a level 
converter (RS232). 

M bus

2.

PC 

(GridVis)

UMG 96 

RM-M

UMG 96 

RM-M

USB

M bus

Device connection with a PC via a level 
converter (USB). 

M bus

Level 

converter

With the primary or secondary device address, you 
obtain data regarding the M-Bus interface from the 
parameter list and measured value list.

C

NOTE!
For the parameter list with addresses and 
setting ranges and a measured value list, 
see the device's user manual.

Changes to the values of the device addresses are 
not possible via the M-Bus.

The standard setting of the primary device address 
is “1” (see step 17).

M-Bus device features:

•  Addressing via primary and secondary device 

address in the range from 0 - 250.

•  Selectable number of 

data points (0 - 27)

•  Supports protocol types:

 

- SND_NKE/$E5 

 

- REQ_UD2/RSP_UD2

•  Slave search: Search on M-Bus

Number of data points (addr. 080)
Each data point is assigned to a certain measured 
value (see “List of the data points”). In order 
to determine the number of data points for the 
telegram RSP_UD2, configure address 080:

Address:  

080

Meaning:  

Number of data points

Setting range: 

0 to 27

Default setting: 

0 (= all data points)

Example: Read out data points 1 to 6

•  Choose setting 6 for the address 080. 
•  With each request the device transmits all data 

points up to and including data point 6.

Example: Read data point 10

•  Choose setting 10 for the address 080. 
•  With each request the device transmits all data 

points up to and including data point 10.

•  Do not neglect the required data points.

Data points

Description

Unit

Resolution

Device

Format Byte

1

Active energy, without backstop

Wh

10

0

2

Active energy, applied

Wh

10

0

6

3

Active energy, supplied

Wh

10

0

6

 4

Reactive energy, inductive

varh

10

1

6

5

Reactive energy, capacitive

varh

10

1

6

6

Reactive energy, without backstop

varh

10

1

6

7

Apparent energy

VAh

10

2

6

8

Running time, comparator 1a

sec

1

1

4

9

Running time, comparator 1b

sec

1

2

4

 10

Running time, comparator 1c

sec

1

3

4

11

Running time, comparator 2a

sec

1

4

4

12

Running time, comparator 2b

sec

1

5

4

13

Running time, comparator 2c

sec

1

6

4

14

Operating hours counter

sec

1

0

4

15

I_total

mA

1

4

4

16

P_total

W

1

5

4

17

Q_total, fundamental oscillation

var

1

6

4

18

S_total 

VA

1

7

4

19

Uln - Phase L1

mV

100

1

4

20

Uln - Phase L2

mV

100

2

4

21

Uln - Phase L3

mV

100

3

4

22

I - Phase L1

mA

1

1

4

23

I - Phase L2

mA

1

2

4

24

I - Phase L3

mA

1

3

4

25

P - Phase L1

W

1

1

4

26

P - Phase L2

W

1

2

4

27

P - Phase L3

W

1

3

4

List of the data points

Measuring the signal level
The data transfer in the M-Bus network takes place 
through a modulation of the supply voltage. 
The voltage is

•  36 V for a high signal 
•  24 V for a low signal 

The slave device responds to the master via 
the modulation of its current consumption. 
The modulation of the current consumption is 

•  1.5 mA for a high signal
•  11-20 mA for a low signal

Signal

Voltage

Reply current

High signal 

36 V

1.5 mA

Low signal

24 V

11-20 mA

C

NOTE!
For further information on the signal 
levels and the configuration of the RSP_
UD2 telegram, see the user manual.

Deutsche V

ersion:

siehe V

or

derseite

User manual:

www

.janitza.com

Janitza electronics GmbH
Vor dem Polstück 6
D-35633 Lahnau / Germany
Support tel. +49 6441 9642-22
Fax +49 6441 9642-30
e-mail: [email protected]
Website: http://www.janitza.com

Disclaimer

The observance of the information products for 
the devices is a prerequisite for safe operation 
and to achieve the stipulated performance 
characteristics and product characteristics. 
Janitza electronics GmbH accepts no liability 
for injuries to personnel, property damage 
or financial losses arising due to a failure to 
comply with the information products. Ensure 
that your information products are accessible 
and legible.

Further information can be found on our web-
site www.janitza.com at Support > Downloads.

Copyright notice

© 2016 - Janitza electronics GmbH - Lahnau.
All rights reserved. Duplication, editing, 
distribution and any form of exploitation, also 
as excerpts, is prohibited.

Subject to technical amendments

•  Make sure that your device agrees with the 

installation manual.

•  Read and understand first product-related 

documents.

•  Keep product supporting documentation 

throughout the life available and, where ap-
propriate, to pass on to subsequent users.

•  Please inform yourself about device revisi-

ons and the associated adjustments to the 
product-related documentation on 
www.janitza.com.

 

Disposal

Please observe national regulations!  
If disposing of individual parts, please dispose 
of them in accordance with their nature and 
existing country-specific regulations, for 
example as:

•  Electrical scrap
•  Plastics
•  Metals

Or, task a certified disposal business with the 
scrapping.

Relevant laws, applied standards and 
directives

The laws, standards and directives for the 
device applied by Janitza electronic GmbH 
can be found in the declaration of conformity 
on our website.

General

Procedure in the event of faults

Possible fault

Cause

Remedy

No display

External fusing for the power supply voltage has 

tripped.

Replace fuse.

No current display

Measurement voltage is not connected.

Connect the measuring-circuit voltage.

Measurement current is not connected.

Connect measuring-circuit current.

Current displayed is too large 

or too small.

Current measurement in the wrong phase.

Check connection and correct if necessary.

Current transformer factor is incorrectly programmed. Read out and program the current transformer trans-

formation ratio at the current transformer.

The current peak value at the measurement input 

was exceeded by harmonic components.

Install current transformer with a larger transforma-

tion ratio.

The current at the measurement input fell short of.

Install current transformer with a suitable transfor-

mation ratio.

Voltage displayed is too large 

or too small.

Measurement in the wrong phase.

Check connection and correct if necessary.

Voltage transformer incorrectly programmed.

Read out and program the voltage transformer trans-

formation ratio at the voltage transformer.

Voltage displayed is too 

small.

Overrange.

Install voltage transformers.

The peak voltage value at the measurement input has 

been exceeded by harmonic components.

Caution! Ensure the measurement inputs are not 

overloaded.

"EEE" in the display

See „error messages“ in the user manual.

 

Device still does not work  

despite the above measures.

Device defective.

Send the device to the manufacturer for inspection 

and testing along with an accurate fault description.

19

Technical data

Supply voltage

Nominal range

Option 230 V:  

AC 90 V - 277 V (50/60 Hz) or 
DC 90 V - 250 V, 300 V CATIII
Option 24 V:  

AC 24 V - 90 V (50/60 Hz) or 
DC 24 V - 90 V, 150 V CATIII

Operating range

+-10% of the nominal range

Power consumption

Option 230 V: max. 4,5 VA / 2 W

Option 24 V: max. 2,5 VA / 2 W

Internal fuse,
not replaceable

Type T1A / 250 VDC / 277 VAC
according to IEC 60127

Recommended over- 
current protection device 
for the line protection

Option 230 V: 6-16 A 

Option 24 V: 1-6 A

(Char. B) 
(IEC/UL approval)

3. Tree structure

Slave

(Measurement 

device)

Master

(Central unit)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

The tree structure combines the star and line structure:

•  Repeaters divide the bus segments.
•  Simple to locate a fault because only individual bus 

segments are usually affected in the event of a fault.

•  Connect M-Bus devices in star (1), 

line (2) or tree structures (3). 

•  Each M-Bus device has its own address 

within the bus structure.

•  Divide (expand) bus structures into individual 

bus segments with repeaters (line amplifiers).

•  Up to 250 subscribers can be connected 

together in a single bus segment (depending 
on the M-Bus master).

•  The bus structures ensure that the system 

remains stable when M-Bus devices are 
exchanged.

•  The bus structure is out of operation during 

a replacement of the M-Bus master.

Bus structure/topology

1. Star structure

Slave

(Measurement 

device)

Master

(Central unit)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Each M-Bus device is linked to the M-Bus 
Master. By switching individual devices on and 
off, it is easier to locate the fault.

2. Line structure

The M-Bus devices are connected (in series) 
with the M-Bus Master:

•  Economical bus structure.
•  Observe possible faults due to a voltage 

drop in the bus structure!

•  Faults are difficult to locate.

Master

(Central unit)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Repeater

Operation and button functions

The device is operated with buttons 1 and 2, 
whereby the following distinctions are made:

•  Short press (button 1 or 2): 

Next step (+1).

•  Long press (button 1 or 2): 

previous step (-1).

The device differentiates between display and 
programming mode.

Measured values are arranged in measured value 
display profiles and can be adjusted easily in the 
GridVis® software (included). Measured value 
display profile 1 is configured in the factory. 

Display mode

•  You can use buttons 1 and 2 to scroll between 

the measured value indications.

•  The measured value indication shows up to 

3 measured values.

•  A time for an automatic indication change 

between the measured value indications can be 
configured in the GridVis® software.

Fig. Display UMG 96 RM-M

Button 1

Button 2

Export

Mean value

CT:  Current 

transformer

VT:  

Voltage 

transformer

K1:  Output 1

K2:  Output 2

Password

Phase conductor - 

Phase conductor

Summation 

measurement

Programming 

mode

Min. value NT/export

Max. value, HT/reference

C

NOTE!
More detailed information on operation, display and button functions for your device can be 
found in the user manual.

13

C

NOTE!
Further technical data can be found in the 
user manual for the device.

Terminal connection capacity (power supply voltage)

Conductors to be connected. 

Only one conductor can be connected per terminal!
Single core, multi-core, 

fine-stranded

0.2 - 2.5 mm

2

, AWG 26 - 12

Terminal pins, core end sheath

0.2 - 2.5 mm

2

Tightening torque

0.4 - 0.5 Nm 

Stripping length

7 mm

Terminal connection capacity (current measurement)

Conductors to be connected. 

Only one conductor can be connected per terminal!
Single core, multi-core,  

fine-stranded

0.2 - 2.5 mm

2

, AWG 26-12

Terminal pins, core end sheath

0.2 - 2.5 mm

2

Tightening torque

0.4 - 0.5 Nm

Stripping length

7 mm

Terminal connection capacity (voltage measurement)

Conductors to be connected. 

Only one conductor can be connected per terminal!
Single core, multi-core, 

fine-stranded

0.08 - 4.0 mm

2

, AWG 28-12

Terminal pins, core end sheath

0.2 - 2.5 mm

2

Tightening torque

0.4 - 0.5 Nm

Stripping length

7 mm

Terminal connection capacity (digital outputs)

Single core, multi-core, 

fine-stranded

0.2 - 1.5 mm

2

, AWG 28-16

Terminal pins, core end sheath

0.2 - 1.5 mm

2

Tightening torque

0.2 - 0.25 Nm

Stripping length

7 mm

Terminal connection capacity (serial interface)

Single core, multi-core, 

fine-stranded

0.2 - 1.5 mm

2

, AWG 28 - 16

Terminal pins, core end sheath

0.2 - 1.5 mm

2

Tightening torque

0.2 - 0.25 Nm

Stripping length

7 mm

General information

Net weight 

(with attached connectors)

approx. 300 g

Packaging weight 

(including accessories)

approx. 625 g

Service life of 

background lighting

40000 h 

(after this period of time 

the background lighting 

efficiency will reduce by 

approx. 50%)

Transport and storage

The following information applies to devices which are trans-

ported or stored in the original packaging.
Free fall

1 m

Temperature

K55 (-25° C to +70° C)

Relative humidity 

0 to 90% RH

Ambient coditions during operation

The device is intended for weather-protected, stationary use. 

Protection class II i.a.w. IEC 60536 (VDE 0106, Part 1).
Operating temperature range

K55 (-10° C .. +55° C)

Relative humidity

0 to 75% RH

Operating altitude

0 .. 2000 m above sea level

Degree of pollution

2

Mounting position

vertical

Ventilation

Forced ventilation is 

not required.

Protection against ingress of 

solid foreign bodies and water

- Front side

- Rear side

- Front with seal

IP40 i.a.w. EN60529

IP20 i.a.w. EN60529

IP54 i.a.w. EN60529

Voltage measurement

3-phase 4-conductor systems 
with rated voltages of up to

277 V/480 V (+-10%)

3-phase 3-conductor 
systems, not earthed, with 
rated voltages of up to 

IT 480 V (+-10%)

Overvoltage category

300 V CAT III

Rated surge voltage

4 kV

Protection 
of voltage measurement

1 - 10 A 
(with IEC-/UL approval)

Metering range L-N

0

1)

 to 300 Vrms

(max. overvoltage 520 Vrms )

Metering range L-L

0

1)

 to 520 Vrms

(max. overvoltage 900 Vrms )

Resolution

0.01 V

Crest factor

2.45 (based on metering range)

Impedance

4 MOhm / phase

Power consumption

approx. 0.1 VA

Sampling rate

21.33 kHz (50 Hz), 
25.6 kHz (60 Hz)  
for each measurement channel

Frequency range of the 
fundamental oscillation - 
resolution

45 Hz to 65 Hz
0.01 Hz

1) ... The device determines measured values only if the Voltage   

        measurement input V1 voltage L1-N greater than 20 Vrms   

        (4-wire measurement) or a voltage L1-L2 of larger 34 Vrms  

        (3-wire measurement) is applied.

Current measurement

Nominal current

5 A

Metering range

0 to 6 Arms

Crest factor

1.98

Resolution

0.1 mA (display 0.01 A)

Overvoltage category

300 V CAT II

Rated surge voltage

2 kV

Power consumption

approx. 0.2 VA (Ri = 5 mOhm)

Overload for 1 sec.

120 A (sinusoidal)

Sampling rate

21.33 kHz (50 Hz), 
25.6 kHz (60 Hz)  
for each measurement channel

Digital outputs

2 digital outputs, semiconductor relays, not short-circuit proof.
Switching voltage

max. 33 V AC, 60 V DC

Switching current

max. 50 mAeff AC/DC

Response time

10/12 p 10 ms *

Pulse output (energy pulse)

max. 50 Hz

* Response time e.g. at 50 Hz: 200 ms + 10 ms = 210 ms

Cable length (digital outputs)

Up to 30 m

Unshielded

More than 30 m

Shielded

Serial interface

M-Bus

300, 600, 1200, 2400, 4800, 

9600, 19200, 38400 Baud

M-Bus device load

max. 20 mA

Stripping length

7 mm

2

Safety

Safety information
The installation manual is not a complete 
directory of all safety measures required to 
operate the device.
Special operating conditions may require further 
measures. The installation manual contains 
instructions that must be observed to ensure 
your personal safety and to prevent damage to 
property.

Symbols used:

c

This symbol is an addition to the 
safety instructions and indicates 
an electrical hazard.

m

This symbol is an addition to the 
safety instructions and indicates 
a potential hazard.

C

This symbol with the word 

NOTE! 

describes:

•  Procedures that do not pose 

any risks of injures.

•  Important information, 

procedures or handling steps.

Safety information is highlighted by a warning 
triangle and is indicated as follows depending 
on the degree of danger:

m

DANGER!

Indicates an imminent danger that 
causes severe or fatal injuries.

m

WARNING!

Indicates a potentially hazardous 
situation that can cause severe 
injuries or death.

m

CAUTION!

Indicates a potentially hazardous 
situation that can cause minor 
injuries or damage to property.

Safety measures
When operating electrical devices, certain parts 
of these devices are invariably subjected to 
hazardous voltage. Therefore, severe bodily 
injuries or damage to property can occur if they 
are not handled properly:

•  Before connecting connections, earth the 

device at the ground wire connection if 
present.

•  Hazardous voltages may be present in all 

switching parts that are connected to the 
power supply.

3

•  Hazardous voltages may also be present 

in the device even after disconnecting the 
supply voltage (capacitor storage).

•  Do not operate equipment with current 

transformer circuits while open.

•  Do not exceed the threshold values specified 

in the user manual and on the rating plate. 
Also adhere to this when inspecting and 
commissioning.

•  Observe the safety and warning instructions in 

the documents that belong to the device! 

Qualified staff

In order to prevent personal injuries and damage 
to property, only qualified staff with electrical 
training may work on the device, with knowledge 
of

•  the national accident prevention regulations
•  the safety engineering standards
•  installing, commissioning and operating the 

device.

Proper use

The device is

•  intended for installation in switch cabinets 

and small installation distributors (please 
observe step 3 "Assembly").

•  not intended for installation in vehicles! 

The use of the device in mobile equipment 
is considered to be non-standard 
environmental conditions and is therefore 
only permitted after separate agreement.

•  not intended for installation in environments 

with hazardous oils, acids, gases, vapours, 
dusts, radiation, etc.

The prerequisites of faultless, safe operation 
of this device are proper transport and proper 
storage, set-up, installation, operation and 
maintenance.

1

Doc. no. 2.040.123.1.a

 

Power Analyser

UMG 96 RM-M

Installation manual

 Installation

 Device settings

Power Analyser

16

17

5

6

8

7

Voltage measurement

The UMG 96 RM-M has 3 voltage measurement 
inputs and is suitable for various connection variants, 
with direct connection or via voltage transformer.

L2
L3
N

L1

Voltage measurement connection variant 

3p 4w

(Addr. 509 = 0, standard setting)

Circuit breaker

Fuse (UL/IEC listed)

m

CAUTION!

Risk of injuries or 
damage to the device

Disregard of the connection conditions for the 
voltage measurement inputs can result in injuries 
or to the device being damaged.
Therefore, note the following:

• 

The voltage measurement inputs

 

-

must not be occupied with DC voltage.

 

-

must be provided with a suitable, labelled 
fuse that is positioned close by and 
a circuit breaker (alternatively: 
a line safety switch).

 

-

are dangerous to touch.

• 

Voltages that exceed the allowed network 
rated voltages must be connected via 
a voltage transformer.

• 

Measured voltages and measured currents 
must derive from the same network!

C

NOTE!
As an alternative to the fuse and circuit 
breaker, you can use a line safety switch.

4

The UMG 96 RM-M is a multi-functional 
network analyser, which

•  measures and calculates electrical variables 

such as voltage, current, power, energy, 
harmonics, etc. in building installations, 
on distribution units, circuit breakers and 
busbar trunking systems.

•  displays and saves measurement results 

and transmits them via interfaces.

Device short description

Install the UMG 96 RM-M in the weatherproof front 
panel of switch cabinets.

Cut-out size:
92

+0.8

 x 92

+0.8

 mm

Ensure! 
Adequate ventilation
•   install the device 

vertically!

•   adhere to clearances from 

neighbouring components!

Fig. Installation situation, 
rear view

Assembly

m

CAUTION!

Damage to property due to 
disregard of the installation 
instructions

Failing to observe the installation instructions can 
damage or destroy your device.
Ensure that there is adequate air circulation in your 
installation environment; if the ambient temperatures 
are high, ensure there is adequate cooling if required.

Connecting the supply voltage

m

CAUTION!

Damage to property due to 
disregard of the connection 
conditions or impermissible 
voltage swells

Your device can be damaged or destroyed 
by a failure to comply with the connection 
conditions or by exceeding the permissible 
voltage range.
Before connecting the device to the supply 
voltage, please check:

• 

Voltage and frequency correspond to the 
details on the ratings plate! Threshold 
values stipulated in the user manual have 
been complied with!

• 

In building installations, the supply 
voltage must be protected with a UL/IEC 
approved circuit breaker / a fuse!

• 

The circuit breaker

 

-

must be easily accessible for the user 
and be installed close to the device.

 

-

must be labelled for the relevant device.

• 

Do not connect the supply voltage to the 
voltage transformers.

• 

Provide a fuse for the neutral conductor 
if the source's neutral conductor 
connection is not earthed.

The supply voltage level for your device is 
specified on the rating plate.
After connecting the supply voltage, an indication 
is shown on the display. If no indication appears, 
check whether the supply voltage is within the 
rated voltage range.

c

WARNING!

Risk of injury due 
to electric voltage!

Serious bodily injury or death can result from:

•  Contact with bare or stripped live wires.
•  Device inputs that are dangerous to touch.

De-energise your device before starting 
work! Check that it is de-energised.

Network systems

Three-phase four-conductor systems

with earthed neutral conductor

Three-phase four-conductor systems

with non-earthed neutral conductor 

(IT networks)

Three-phase, three-conductor systems

Not earthed

Three-phase, three-conductor systems

with earthed phase

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

U

L-N

 / U

L-L

277 VLN / 480 VLL

U

L-N

 / U

L-L

277 VLN / 480 VLL

U

L-L

480 VLL

U

L-L

240 VLL

Single-phase, two-conductor systems

with earthed neutral conductor

Separated single-phase, 

three-conductor systems

with earthed neutral conductor

The device can be used in 

•  2, 3 and 4 conductor 

networks (TN, TT and 
IT networks)

•  Residential and 

industrial applications

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

L1
L2

L3
E

E

N

E

L1
L2

L3
E

N

R

L1

L2
L3
E

E

L1

L2
E

E

L

N
E

E

L1

L2
L3
E

E

L1

L2

N

E

E

U

L-N

230 VLN

U

L-N

 / U

L-L

240 VLN / 480 VLL

Voltage measurement connection variants

Current measurement I1, I2, I3

The UMG 96 RM-M

•  enables current measurements via current 

transformer only.

•  enables the connection of current transformers 

with secondary currents of ../1 A and ../5 A.

•  has the current transformer ratio 5/5 A set as 

standard.

•  measures AC currents, does not measure DC 

currents!

c

WARNING!

Risk of injury due 
to electric voltage!

Serious bodily injury or death can result from:

•  Contact with bare or stripped live wires.
•  Current measurement inputs that are 

dangerous to touch on the device and on the 
current transformers.

De-energise your device before starting 
work! Check that it is de-energised.
Earth your system! Use the earth connection 
points with earthing symbols for this! 
Earth the secondary windings of current 
transformers and all of the metal parts of the 
transformer that could be touched!

c

WARNING!

Risk of injury due to 
large currents and high 
electric voltages!

Current transformers operating with an open 
secondary circuit (high voltage peaks) can result 
in serious or even fatal injuries.
Avoid open operation of the current transformers - 
short-circuit unloaded transformers! 

3p 4w

(Addr. 509 = 0, standard setting)

3p 4wu

(Addr. 509 = 1)

3p 4u

(Addr. 509 = 2)

3p 2u

(Addr. 509 = 5)

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

Measurement with 3 phase 

conductors and neutral conductor.

Measurement via voltage 

transformer with 3 phase 

conductors and a neutral 

conductor.

Measurement with 3 phase 

conductors without neutral 

conductor. Measured values which 

require an N, use a calculated N. 

Measurement via voltage 

transformer with 3 phase 

conductors without neutral 

conductor. Measured values which 

require an N, use a calculated N.

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

1p 2w1

(Addr. 509 = 4)

2p 4w

(Addr. 509 = 3)

1p 2w

(Addr. 509 = 6)

3p 1w

(Addr. 509 = 7)

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

Measured values derived from 

voltage measurement inputs V2 

and V3 are taken to be 0 and are 

not calculated.

System with equal loading of the 

phases. The measured values of 

the voltage measurement input V2 

are calculated.

TN-C system with 1-phase, three-

conductor connection. Measured 

values derived from voltage 

measurement input V3 are taken to 

be 0 and are not calculated.

3 systems with equal loading of 

the phases. The measured values 

for the phases that are not created 

(L2/L3, L1/L3, L1/L2) for the 

relevant systems are calculated.

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

L2
L3
N

L1

Load

Connection variant 

3p 4w current measurement

 

(I1, I2, I3) via current transformer

 (Addr. 510 = 0, 

standard setting).

Connection variants for current measurement I1, I2, I3

9

C

NOTE!
With measurement range exceeding, 
the measurement device display shows 

"EEE"

. Further information on this can 

be found in the user manual.

3p 2i

(Addr. 510 = 1)

3p 2i0

(Addr. 510 = 2)

3p 3w3

(Addr. 510 = 3)

3p 3w

(Addr. 510 = 4)

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

System with equal loading of the 

phases. The measured values for 

current measurement input I2 are 

measured.

The measured values for current 

measurement input I2 are 

calculated.

Measurement in the 3-phase 

network with unequal loading. 

Measurement in the 3-phase 

network with equal loading.  

The measured values for current 

measurement inputs I2 and I3 are 

calculated.

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

2p 4w

(Addr. 510 = 5)

1p 2i

(Addr. 510 = 6)

1p 2w

(Addr. 510 = 7)

3p 1w

(Addr. 510 = 8)

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

System with equal loading of the 

phases. The measured values for 

current measurement input I2 are 

calculated.

Measured values derived from 

current measurement input I3 

are taken to be 0 and are not 

calculated.

Measured values derived from 

current measurement inputs I2 and 

I3 are taken to be 0 and are not 

calculated.

3 systems with equal loading of 

the phases. The measured values 

for the phases that are not created 

(L2/L3, L1/L3, L1/L2) for the 

relevant systems are calculated.

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

L1
L2
L3

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3

I1

I2

I3

I1

I2

I3

L1

L2

L1

N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1
L2
L3
N

I1

I2

I3

L1

L2

L3

I1

I2

I3

L1

L2

L3

L1

L2

L3

18

10

11

12

C

NOTE!
For further information on device func-
tions, data and assembly, see the user 
manual.

C

NOTE!
Information on current data and current 
transformer data can be found in the user 
manual.

Suitable network systems and maximum rated voltages (DIN EN 61010-1/A1):

The voltage measurement inputs are designed for 
measurements in low voltage networks, in which 
rated voltages of up to 

•  277 V phase to earth and 480 V phase to phase 

in the 4-conductor system or

•  480 V phase to phase in the 3-conductor system

occur.
The measurement and surge voltages meet 
overvoltage category 300 V CATIII. 

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1
L2
L3

V1

V2

V3

V

N

L1

N

V1

V2

V3

V

N

L1

L2

V1

V2

V3

V

N

L1
L2
L3
N

V1

V2

V3

V

N

L1

L2

L3

L1

L2

L3
L1

L2

L3

V1

V2

V3

V

N

N

Part no. 

33.03.218

Fuse

N

L

Circuit breaker

Fig. Connecting supply voltage.

14

Programming mode

•  Press and hold buttons 1 and 2 simultaneously 

for 1 second to switch between 

display mode

 

and 

programming mode

. The text 

PRG 

appears in the display.

•  Configure the necessary settings for the 

operation of the device in programming mode.

•  The programming mode can be protected with 

a user password.

•  Button 2 switches between the programming 

menus:
1. 

Current transformer

2. 

Voltage transformer

3. 

Parameter list

The device switches from 

programming mode

 to 

display mode

 if

•  no buttons are pressed for 60 seconds.
•  buttons 1 and 2 are pressed simultaneously for 

1 second.

C

NOTE!
The following section contains an 
explanation of the programming menus 
current transformer, voltage transformer 
and parameters.
For further information on the 
programming menus and interfaces, see 
the device's user manual.

C

NOTE!
Changes are only applied after exiting 
programming mode.  

Programming the current transformer

1.  Switch to programming mode.
2.  The symbols for programming mode 

PRG 

and for the current transformer 

CT appear.

3.  Press button 1 - the first digit of the input 

field for the primary current flashes.

4.  Use button 2 to select the value for the 

1st digit.

5.  Use button 1 to move to the 2nd. digit.
6.  Use button 2 to select the value of the 

2nd digit.

7.  Use button 1 to move to the 3rd digit.
8.  Use button 2 to select the value of the 

3rd digit.

9.  Confirm with button 1.
10. The complete number flashes.
11. Use button 2 to select the decimal place and 

thus the unit of the primary current.

12. Confirm with button 1.
13. The input range of the secondary current 

flashes. 

14. Use button 2 to set the secondary current 

(value 1 A or 5 A). 

15. Confirm with button 1.
16. Pressing buttons 1 and 2 simultaneously 

(1. sec.) exits the programming mode. 
Use button 2 to change to the input field for 
the voltage transformer.

Current transformer 

symbol

Unit indicator

Current transformer, 

primary
Programming mode

Current transformer, 

secondary

C

NOTE!

•  Changes are only applied after exiting 

programming mode.

•  For further information on current 

transformers and current transformer 
ratios, see the user manual.

Fig. "Current transformer" input area

15

Programming voltage transformers

1.  Switch to programming mode.
2.  The symbols for programming mode 

PRG 

and for the current transformer 

CT appear.

3.  Use button 2 to change to programming 

mode for the voltage transformer.

4.  The symbols for Programming mode 

PRG

and for the voltage transformer 

VT appear.

5.  Press button 1 to confirm - the first digit 

of the input area for the primary voltage 
flashes.

6.  Use button 2 to select the value for the 

1st digit.

7.  Use button 1 to move to the 2nd. digit.
8.  Use button 2 to select the value of the 

2nd digit.

9.  Use button 1 to move to the 3rd digit.
10. Use button 2 to select the value of the 

3rd digit.

11. Confirm with button 1.
12. The complete number flashes.
13. Use button 2 to select the decimal place and 

thus the unit of the primary voltage.

14. Confirm with button 1.
15. The input range of the secondary voltage 

flashes. 

16. Set the secondary voltage with button 2. 
17. Confirm with button 1.
18. Pressing buttons 1 and 2 simultaneously  

(1. sec.) exits the programming mode.  
Use button 2 to change to the programming 
mode for the parameter list.

Unit indicator

Voltage transformer, 
primary

Programming mode

Voltage transformer, 
secondary
Voltage transformer 
symbol

C

NOTE!

•  Changes are only applied after 

exiting programming mode.

•  Further information on voltage 

transformers and voltage transform-
er ratios can be found in the user 
manual.

Fig. "Voltage transformer" input area

Programming parameters

1.  Switch to programming mode.
2.  The symbols for programming mode 

PRG 

and for the current transformer 

CT appear.

3.  Use button 2 to switch to programming 

mode for the parameters.

4.  The device shows the symbol for the 

programming mode 

PRG, the address 000 and 

the value of the address (001, standard setting) 
are displayed (the device shows the most 
recently set address and the associated value).

5.  Press button 1 to confirm - the first digit of 

the input area for the parameter flashes.

6.  Use button 2 to select the value for the 1st digit.
7.  Use button 1 to move to the 2nd. digit.
8.  Use button 2 to select the value of the 2nd digit.
9.  Use button 1 to move to the 3rd digit.
10.  Use button 2 to select the value of the 3rd digit.
11. Confirm with button 1.
12. Pressing buttons 1 and 2 simultaneously  

(1. sec.) exits the programming mode.  
Use button 2 to change to the programming 
mode for the parameter list.

Parameter (primary 
device address 000)

Value of the 
parameter 
(address range)

Programming mode

C

NOTE!
You can find a parameter list (addresses) and information on the parameters (e.g. primary and 
secondary device addresses) in the user manual or on our website.

Parameter “primary device address” (addr. 000)
In a bus structure, a master differentiates 
between the connected devices on the basis of 
the device address.

•  The address range lies between a value  

of 0 and 255.

•  Reserved ranges (do not use!): 

- Value 0  
- Values 251 to 255 

Parameter “secondary device address” 
(addr. 081-084)
The parameter “secondary device address” 
offers the option of addressing more than 
250 devices in your bus structure.

M-Bus interface

M-Bus interface, 
2-pole plug contact 

M+
M-

The M-Bus interface of the device facilitates 
communication (meter data transfer) via the 
M-Bus protocol with a Master device.

The UMG 96 RM-M loads the M-Bus with 
an M-Bus device load of 1.5 mA.

Baud rate (addr. 001, see step 17)
Select a common Baud rate for the M-Bus 
interfaces in one Bus structure (see step 10)! 

C

NOTE!
Configure the Baud rate on the device 
(addr. 001). Configuration via M-Bus is 
excluded.

Setting

(Addr. 001)

Baud rate 

(in Baud)

0

300

1

600

2

1200

3

2400

4

4800

5

9600

6

19200

7

38400

Device 

standard setting

Establish the connection to the PC

Communication connections:

More information on device configuration and 
communication is provided as of step 12.

1.

PC 

(GridVis)

Level 

converter

UMG 96 

RM-M

UMG 96 

RM-M

RS232

M bus

Device connection with a PC via a level 
converter (RS232). 

M bus

2.

PC 

(GridVis)

UMG 96 

RM-M

UMG 96 

RM-M

USB

M bus

Device connection with a PC via a level 
converter (USB). 

M bus

Level 

converter

With the primary or secondary device address, you 
obtain data regarding the M-Bus interface from the 
parameter list and measured value list.

C

NOTE!
For the parameter list with addresses and 
setting ranges and a measured value list, 
see the device's user manual.

Changes to the values of the device addresses are 
not possible via the M-Bus.

The standard setting of the primary device address 
is “1” (see step 17).

M-Bus device features:

•  Addressing via primary and secondary device 

address in the range from 0 - 250.

•  Selectable number of 

data points (0 - 27)

•  Supports protocol types:

 

- SND_NKE/$E5 

 

- REQ_UD2/RSP_UD2

•  Slave search: Search on M-Bus

Number of data points (addr. 080)
Each data point is assigned to a certain measured 
value (see “List of the data points”). In order 
to determine the number of data points for the 
telegram RSP_UD2, configure address 080:

Address:  

080

Meaning:  

Number of data points

Setting range: 

0 to 27

Default setting: 

0 (= all data points)

Example: Read out data points 1 to 6

•  Choose setting 6 for the address 080. 
•  With each request the device transmits all data 

points up to and including data point 6.

Example: Read data point 10

•  Choose setting 10 for the address 080. 
•  With each request the device transmits all data 

points up to and including data point 10.

•  Do not neglect the required data points.

Data points

Description

Unit

Resolution

Device

Format Byte

1

Active energy, without backstop

Wh

10

0

2

Active energy, applied

Wh

10

0

6

3

Active energy, supplied

Wh

10

0

6

 4

Reactive energy, inductive

varh

10

1

6

5

Reactive energy, capacitive

varh

10

1

6

6

Reactive energy, without backstop

varh

10

1

6

7

Apparent energy

VAh

10

2

6

8

Running time, comparator 1a

sec

1

1

4

9

Running time, comparator 1b

sec

1

2

4

 10

Running time, comparator 1c

sec

1

3

4

11

Running time, comparator 2a

sec

1

4

4

12

Running time, comparator 2b

sec

1

5

4

13

Running time, comparator 2c

sec

1

6

4

14

Operating hours counter

sec

1

0

4

15

I_total

mA

1

4

4

16

P_total

W

1

5

4

17

Q_total, fundamental oscillation

var

1

6

4

18

S_total 

VA

1

7

4

19

Uln - Phase L1

mV

100

1

4

20

Uln - Phase L2

mV

100

2

4

21

Uln - Phase L3

mV

100

3

4

22

I - Phase L1

mA

1

1

4

23

I - Phase L2

mA

1

2

4

24

I - Phase L3

mA

1

3

4

25

P - Phase L1

W

1

1

4

26

P - Phase L2

W

1

2

4

27

P - Phase L3

W

1

3

4

List of the data points

Measuring the signal level
The data transfer in the M-Bus network takes place 
through a modulation of the supply voltage. 
The voltage is

•  36 V for a high signal 
•  24 V for a low signal 

The slave device responds to the master via 
the modulation of its current consumption. 
The modulation of the current consumption is 

•  1.5 mA for a high signal
•  11-20 mA for a low signal

Signal

Voltage

Reply current

High signal 

36 V

1.5 mA

Low signal

24 V

11-20 mA

C

NOTE!
For further information on the signal 
levels and the configuration of the RSP_
UD2 telegram, see the user manual.

Deutsche V

ersion:

siehe V

or

derseite

User manual:

www

.janitza.com

Janitza electronics GmbH
Vor dem Polstück 6
D-35633 Lahnau / Germany
Support tel. +49 6441 9642-22
Fax +49 6441 9642-30
e-mail: [email protected]
Website: http://www.janitza.com

Disclaimer

The observance of the information products for 
the devices is a prerequisite for safe operation 
and to achieve the stipulated performance 
characteristics and product characteristics. 
Janitza electronics GmbH accepts no liability 
for injuries to personnel, property damage 
or financial losses arising due to a failure to 
comply with the information products. Ensure 
that your information products are accessible 
and legible.

Further information can be found on our web-
site www.janitza.com at Support > Downloads.

Copyright notice

© 2016 - Janitza electronics GmbH - Lahnau.
All rights reserved. Duplication, editing, 
distribution and any form of exploitation, also 
as excerpts, is prohibited.

Subject to technical amendments

•  Make sure that your device agrees with the 

installation manual.

•  Read and understand first product-related 

documents.

•  Keep product supporting documentation 

throughout the life available and, where ap-
propriate, to pass on to subsequent users.

•  Please inform yourself about device revisi-

ons and the associated adjustments to the 
product-related documentation on 
www.janitza.com.

 

Disposal

Please observe national regulations!  
If disposing of individual parts, please dispose 
of them in accordance with their nature and 
existing country-specific regulations, for 
example as:

•  Electrical scrap
•  Plastics
•  Metals

Or, task a certified disposal business with the 
scrapping.

Relevant laws, applied standards and 
directives

The laws, standards and directives for the 
device applied by Janitza electronic GmbH 
can be found in the declaration of conformity 
on our website.

General

Procedure in the event of faults

Possible fault

Cause

Remedy

No display

External fusing for the power supply voltage has 

tripped.

Replace fuse.

No current display

Measurement voltage is not connected.

Connect the measuring-circuit voltage.

Measurement current is not connected.

Connect measuring-circuit current.

Current displayed is too large 

or too small.

Current measurement in the wrong phase.

Check connection and correct if necessary.

Current transformer factor is incorrectly programmed. Read out and program the current transformer trans-

formation ratio at the current transformer.

The current peak value at the measurement input 

was exceeded by harmonic components.

Install current transformer with a larger transforma-

tion ratio.

The current at the measurement input fell short of.

Install current transformer with a suitable transfor-

mation ratio.

Voltage displayed is too large 

or too small.

Measurement in the wrong phase.

Check connection and correct if necessary.

Voltage transformer incorrectly programmed.

Read out and program the voltage transformer trans-

formation ratio at the voltage transformer.

Voltage displayed is too 

small.

Overrange.

Install voltage transformers.

The peak voltage value at the measurement input has 

been exceeded by harmonic components.

Caution! Ensure the measurement inputs are not 

overloaded.

"EEE" in the display

See „error messages“ in the user manual.

 

Device still does not work  

despite the above measures.

Device defective.

Send the device to the manufacturer for inspection 

and testing along with an accurate fault description.

19

Technical data

Supply voltage

Nominal range

Option 230 V:  

AC 90 V - 277 V (50/60 Hz) or 
DC 90 V - 250 V, 300 V CATIII
Option 24 V:  

AC 24 V - 90 V (50/60 Hz) or 
DC 24 V - 90 V, 150 V CATIII

Operating range

+-10% of the nominal range

Power consumption

Option 230 V: max. 4,5 VA / 2 W

Option 24 V: max. 2,5 VA / 2 W

Internal fuse,
not replaceable

Type T1A / 250 VDC / 277 VAC
according to IEC 60127

Recommended over- 
current protection device 
for the line protection

Option 230 V: 6-16 A 

Option 24 V: 1-6 A

(Char. B) 
(IEC/UL approval)

3. Tree structure

Slave

(Measurement 

device)

Master

(Central unit)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

The tree structure combines the star and line structure:

•  Repeaters divide the bus segments.
•  Simple to locate a fault because only individual bus 

segments are usually affected in the event of a fault.

•  Connect M-Bus devices in star (1), 

line (2) or tree structures (3). 

•  Each M-Bus device has its own address 

within the bus structure.

•  Divide (expand) bus structures into individual 

bus segments with repeaters (line amplifiers).

•  Up to 250 subscribers can be connected 

together in a single bus segment (depending 
on the M-Bus master).

•  The bus structures ensure that the system 

remains stable when M-Bus devices are 
exchanged.

•  The bus structure is out of operation during 

a replacement of the M-Bus master.

Bus structure/topology

1. Star structure

Slave

(Measurement 

device)

Master

(Central unit)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Each M-Bus device is linked to the M-Bus 
Master. By switching individual devices on and 
off, it is easier to locate the fault.

2. Line structure

The M-Bus devices are connected (in series) 
with the M-Bus Master:

•  Economical bus structure.
•  Observe possible faults due to a voltage 

drop in the bus structure!

•  Faults are difficult to locate.

Master

(Central unit)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Slave

(Measurement 

device)

Repeater

Operation and button functions

The device is operated with buttons 1 and 2, 
whereby the following distinctions are made:

•  Short press (button 1 or 2): 

Next step (+1).

•  Long press (button 1 or 2): 

previous step (-1).

The device differentiates between display and 
programming mode.

Measured values are arranged in measured value 
display profiles and can be adjusted easily in the 
GridVis® software (included). Measured value 
display profile 1 is configured in the factory. 

Display mode

•  You can use buttons 1 and 2 to scroll between 

the measured value indications.

•  The measured value indication shows up to 

3 measured values.

•  A time for an automatic indication change 

between the measured value indications can be 
configured in the GridVis® software.

Fig. Display UMG 96 RM-M

Button 1

Button 2

Export

Mean value

CT:  Current 

transformer

VT:  

Voltage 

transformer

K1:  Output 1

K2:  Output 2

Password

Phase conductor - 

Phase conductor

Summation 

measurement

Programming 

mode

Min. value NT/export

Max. value, HT/reference

C

NOTE!
More detailed information on operation, display and button functions for your device can be 
found in the user manual.

13

C

NOTE!
Further technical data can be found in the 
user manual for the device.

Terminal connection capacity (power supply voltage)

Conductors to be connected. 

Only one conductor can be connected per terminal!
Single core, multi-core, 

fine-stranded

0.2 - 2.5 mm

2

, AWG 26 - 12

Terminal pins, core end sheath

0.2 - 2.5 mm

2

Tightening torque

0.4 - 0.5 Nm 

Stripping length

7 mm

Terminal connection capacity (current measurement)

Conductors to be connected. 

Only one conductor can be connected per terminal!
Single core, multi-core,  

fine-stranded

0.2 - 2.5 mm

2

, AWG 26-12

Terminal pins, core end sheath

0.2 - 2.5 mm

2

Tightening torque

0.4 - 0.5 Nm

Stripping length

7 mm

Terminal connection capacity (voltage measurement)

Conductors to be connected. 

Only one conductor can be connected per terminal!
Single core, multi-core, 

fine-stranded

0.08 - 4.0 mm

2

, AWG 28-12

Terminal pins, core end sheath

0.2 - 2.5 mm

2

Tightening torque

0.4 - 0.5 Nm

Stripping length

7 mm

Terminal connection capacity (digital outputs)

Single core, multi-core, 

fine-stranded

0.2 - 1.5 mm

2

, AWG 28-16

Terminal pins, core end sheath

0.2 - 1.5 mm

2

Tightening torque

0.2 - 0.25 Nm

Stripping length

7 mm

Terminal connection capacity (serial interface)

Single core, multi-core, 

fine-stranded

0.2 - 1.5 mm

2

, AWG 28 - 16

Terminal pins, core end sheath

0.2 - 1.5 mm

2

Tightening torque

0.2 - 0.25 Nm

Stripping length

7 mm

General information

Net weight 

(with attached connectors)

approx. 300 g

Packaging weight 

(including accessories)

approx. 625 g

Service life of 

background lighting

40000 h 

(after this period of time 

the background lighting 

efficiency will reduce by 

approx. 50%)

Transport and storage

The following information applies to devices which are trans-

ported or stored in the original packaging.
Free fall

1 m

Temperature

K55 (-25° C to +70° C)

Relative humidity 

0 to 90% RH

Ambient coditions during operation

The device is intended for weather-protected, stationary use. 

Protection class II i.a.w. IEC 60536 (VDE 0106, Part 1).
Operating temperature range

K55 (-10° C .. +55° C)

Relative humidity

0 to 75% RH

Operating altitude

0 .. 2000 m above sea level

Degree of pollution

2

Mounting position

vertical

Ventilation

Forced ventilation is 

not required.

Protection against ingress of 

solid foreign bodies and water

- Front side

- Rear side

- Front with seal

IP40 i.a.w. EN60529

IP20 i.a.w. EN60529

IP54 i.a.w. EN60529

Voltage measurement

3-phase 4-conductor systems 
with rated voltages of up to

277 V/480 V (+-10%)

3-phase 3-conductor 
systems, not earthed, with 
rated voltages of up to 

IT 480 V (+-10%)

Overvoltage category

300 V CAT III

Rated surge voltage

4 kV

Protection 
of voltage measurement

1 - 10 A 
(with IEC-/UL approval)

Metering range L-N

0

1)

 to 300 Vrms

(max. overvoltage 520 Vrms )

Metering range L-L

0

1)

 to 520 Vrms

(max. overvoltage 900 Vrms )

Resolution

0.01 V

Crest factor

2.45 (based on metering range)

Impedance

4 MOhm / phase

Power consumption

approx. 0.1 VA

Sampling rate

21.33 kHz (50 Hz), 
25.6 kHz (60 Hz)  
for each measurement channel

Frequency range of the 
fundamental oscillation - 
resolution

45 Hz to 65 Hz
0.01 Hz

1) ... The device determines measured values only if the Voltage   

        measurement input V1 voltage L1-N greater than 20 Vrms   

        (4-wire measurement) or a voltage L1-L2 of larger 34 Vrms  

        (3-wire measurement) is applied.

Current measurement

Nominal current

5 A

Metering range

0 to 6 Arms

Crest factor

1.98

Resolution

0.1 mA (display 0.01 A)

Overvoltage category

300 V CAT II

Rated surge voltage

2 kV

Power consumption

approx. 0.2 VA (Ri = 5 mOhm)

Overload for 1 sec.

120 A (sinusoidal)

Sampling rate

21.33 kHz (50 Hz), 
25.6 kHz (60 Hz)  
for each measurement channel

Digital outputs

2 digital outputs, semiconductor relays, not short-circuit proof.
Switching voltage

max. 33 V AC, 60 V DC

Switching current

max. 50 mAeff AC/DC

Response time

10/12 p 10 ms *

Pulse output (energy pulse)

max. 50 Hz

* Response time e.g. at 50 Hz: 200 ms + 10 ms = 210 ms

Cable length (digital outputs)

Up to 30 m

Unshielded

More than 30 m

Shielded

Serial interface

M-Bus

300, 600, 1200, 2400, 4800, 

9600, 19200, 38400 Baud

M-Bus device load

max. 20 mA

Stripping length

7 mm

Содержание UMG 96 RM-M

Страница 1: ...en Ver fahren oder Handhabungen Sicherheitshinweise sind durch ein Warndreieck hervorgehoben und je nach Gef hrdungsgrad wie folgt dargestellt m GEFAHR Weist auf eine unmittelbar dro hende Gefahr hin...

Страница 2: ...ehmer zusammen abh ngig vom M Bus Master Die Bus Strukturen sorgen daf r dass bei Austausch von M Bus Ger ten das System stabil bleibt Die Bus Struktur ist bei einem Austausch des M Bus Masters au er...

Страница 3: ...Bedienung Anzeige und Tastenfunktionen Ihres Ger ts finden Sie im 3 e 4 Das UMG 96 RM M ist ein multifunktionaler Netzanalysator der Elektrische Gr en wie Spannung Strom Leistung Energie Oberschwingu...

Страница 4: ...26 P Phase L2 W 1 2 4 27 P Phase L3 W 1 3 4 Liste der Datenpunkte Sicherheitshinweise Die Installationsanleitung stellt kein vollst ndi ges Verzeichnis aller f r einen Betrieb des Ge r ts erforderlich...

Страница 5: ...Benutzerhandbuch Trotz obiger Ma nahmen funktioniert das Ger t nicht Ger t defekt Ger t und Fehlerbeschreibung zur berpr fung an den Hersteller senden Das UMG 96 RM M hat 3 Spannungsmesseing n ge und...

Страница 6: ...sl nge digitale Ausg nge bis 30 m nicht abgeschirmt gr er 30 m abgeschirmt 16 17 18 Spannungswandler programmieren 1 Wechseln Sie in den Programmier Modus 2 Die Symbole f r den Programmier Modus PRG u...

Страница 7: ...4 24 I Phase L3 mA 1 3 4 25 P Phase L1 W 1 1 4 26 P Phase L2 W 1 2 4 27 P Phase L3 W 1 3 4 16 19 14 Halten Sie die Taste 1 und 2 gleichzeitig f r 1 Sekunde gedr ckt um zwischen Anzeige Modus und Progr...

Страница 8: ...t max 20 mA Abisolierl nge 7 mm Leitungsl nge digitale Ausg nge bis 30 m nicht abgeschirmt gr er 30 m abgeschirmt 18 Versorgungsspannung Nennbereich Option 230 V AC 90 V 277 V 50 60 Hz oder DC 90 V 25...

Страница 9: ...ed by a warning triangle and is indicated as follows depending on the degree of danger m DANGER Indicates an imminent danger that causes severe or fatal injuries m WARNING Indicates a potentially haza...

Страница 10: ...uctures 3 Each M Bus device has its own address within the bus structure Divide expand bus structures into individual bus segments with repeaters line amplifiers Up to 250 subscribers can be connected...

Страница 11: ...tion on operation display and button functions for your device can be 13 3 4 The UMG 96 RM M is a multi functional network analyser which measures and calculates electrical variables such as voltage c...

Страница 12: ...1 4 26 P Phase L2 W 1 2 4 27 P Phase L3 W 1 3 4 List of the data points Safety information The installation manual is not a complete directory of all safety measures required to operate the device Sp...

Страница 13: ...Single core multi core fine stranded 0 2 1 5 mm2 AWG 28 16 Terminal pins core end sheath 0 2 1 5 mm2 Tightening torque 0 2 0 25 Nm Stripping length 7 mm The UMG 96 RM M has 3 voltage measurement inpu...

Страница 14: ...800 9600 19200 38400 Baud M Bus device load max 20 mA Stripping length 7 mm 16 17 18 Programming voltage transformers 1 Switch to programming mode 2 The symbols for programming mode PRG and for the cu...

Страница 15: ...mA 1 2 4 24 I Phase L3 mA 1 3 4 25 P Phase L1 W 1 1 4 26 P Phase L2 W 1 2 4 27 P Phase L3 W 1 3 4 16 14 Press and hold buttons 1 and 2 simultaneously for 1 second to switch between display mode and pr...

Страница 16: ...l interface M Bus 300 600 1200 2400 4800 9600 19200 38400 Baud M Bus device load max 20 mA Stripping length 7 mm 18 Supply voltage Nominal range Option 230 V AC 90 V 277 V 50 60 Hz or DC 90 V 250 V 30...

Отзывы: