Section 3: CONNECTION ALTERNATIVES MEASURING VOLTAGE
AND MEASURING CURRENT
According to the existing grid and the desired operating mode (CONTROL-MODE
Programming) the controller has to be connected accord. one of the following
alternatives. The separate auxiliary voltage (24 V DC) that is needed for the thyristor
switches has to be conducted to P1…P3 and to the connection “control 24V”.
The
connection of PE is mandatory!
Alternative 1: measuring performed in each phase - 3 current transformers needed
Use: CONTROL-MODE: 1 - 4; 7-12; 15 (control modes see page 11)
Alternative 2: single-phase measuring via current transformer in L1 Values extrapolated (balance assumed).
Measuring complies with conventional measuring for switching of three-phase capacitors.
Use: CONTROL-MODE 5; 13; 14; 16
Alternative 3: single-phase measuring as alternative 2 , but with capacitor current measuring in the compensation
system for collection of real capacitor currents.
Use: CONTROL-MODE 6
Reserve
- 6 -
PE
N
L2 (S)
L3 (T)
L1 (R)
( L1) ( N )
( L1) ( N )
( L1) ( N )
L1 L2 L3 monitoring
24VDC
aux. voltage
24VDC
aux. voltage
24VDC
aux. voltage
24VDC
L1 L2 L3 monitoring
24VDC
L1 L2 L3 monitoring
24VDC
Supply voltage
110-230V~
Supply voltage
110-230V~
Supply voltage
110-230V~
Measuring voltage
to P1...P3
to P1...P3
to P1...P3
Measuring voltage
Measuring voltage
L3
L3
L3
Measuring current
L2
Measuring current
L2
Measuring current
L2
L1
L1
L1
L1 (R)
L2 (S)
L3 (T)
PE
N
L1 (R)
L2 (S)
L3 (T)
PE
N
L1 L2 L3 N
PFC-system
Load-
site
Load-
site