23
www.janitza.de
Procont
®
-LMC-008-IO
RS-485 interface
3-conductor connection with A, B, GND
Protocol
Modbus RTU
Transmission rate
9.6 kbps, 19.2 kbps, 38.4 kbps
Ethernet interfaces LAN 100Base-T
Connection
1 x RJ45
Protocols and services
Modbus TCP
Terminal connection capacity (plug-in)
Connectible conductors.
Only connect one conductor per terminal point!
Single core, multi-core, fine-stranded
0.2 - 2.5 mm
2
, AWG 26-12
Wire ferrules (non-insulated)
- Recommended strip length
0.2 - 2.5 mm
2,
AWG 26-12
10 mm (0.3937 in)
Wire ferrules (insulated)
- Recommended strip length
0.2 - 2.5 mm
2
, AWG 26-12
13 mm (0.5118 in)
Wire ferrules: Length of the contact sleeve
10 mm (0.3937 in)