Measurement transformer settings

Set the following parameters at the integrated 
measurement transducer:

•  Compensate for the influence of the coil lengths 

through the potentiometer switching (1). To do 
so, set the parameters according to the table:

Measurement range

DIP switch

100 A

8

250 A

7

400 A

6

630 A

5

1000 A

4

1500 A

3

2000 A

2

4000 A

1

Setting

Rogowski coil

600 mm

Flex-CT-1A-600 mm

•  Set the current measurement range with the 

DIP switch (2) in accordance with the table:

Potentiometer

(1)

DIP switch

(2)

- 6 -

•  The transformer ratio should be adapted in the 

UMG 512-PRO measurement device too in 
accordance with the table. Change the settings 

•   by means of the GridVis software or
•  by entries on the device (measurement 

range: ratio 

x

 

/

 

1 A

 ). 

Please refer to the UMG 512-PRO operation 
manual for this.

Содержание MRG 512-PRO PQ Flex

Страница 1: ...H Vor dem Polst ck 6 D 35633 Lahnau Support tel 49 6441 9642 22 Fax 49 6441 9642 30 E mail info janitza com Internet http www janitza com www janitza com Mobile universal measurement device MRG 512 PR...

Страница 2: ...sic device 4 Connecting the measurement case 4 Reading out recordings 5 MRG 512 PRO PQ Flex views 5 Measurement transformer settings 6 Example connection voltage measurement 7 Example connection curre...

Страница 3: ...Do not work with the device if the front plate has been removed Otherwise you may come into contact with hazardous voltages It is not permitted to use the device with the front plate removed The UMG 5...

Страница 4: ...ectronics GmbH Tel no 49 6441 9642 22 This device must only be operated and repaired by specialised personnel Connecting the measurement case 1 Connect the mains cable to the measurement case 1 and co...

Страница 5: ...rement 2 Net Ok Batt Ok I O Differenzstrommess I 5 I 6 Eth AUX UMG 512 PRO Netz Ok Batt Ok I O Residual current transformer I 5 I 6 Ether AUX U L1 U L2 U L3 U L4 U N L4 L1 L2 L3 N Spannungseing nge Di...

Страница 6: ...A 6 630 A 5 1000 A 4 1500 A 3 2000 A 2 4000 A 1 Setting Rogowski coil 600 mm Flex CT 1A 600 mm Set the current measurement range with the DIP switch 2 in accordance with the table Potentiometer 1 DIP...

Страница 7: ...h fuse Max 20mm Locking sleeve with bayonet catch for accommodating a fuse Example connection current measurement N L1 L2 L3 PE I1 I2 I3 IN I5 I6 Voltage measurement terms connections Rogowski coil RC...

Страница 8: ...e signs when drawing energy Also check the power factor for plausibility Turn the current transformer if necessary Up to 2 residual current measurements can be selected c Attention Fatal hazard due to...

Отзывы: