Installationsanvisning Janfire Flex - a

 

 

IA Brännare Flex-a R2 SV 

 Janfire 2009 

16(19

 

 

 

After completed 10 min blow, starts feeding auger to feeding pellets (approx 60 sec), the fan starts 
blowing (first 10 sec with max rpm and then turn to pulsing blow with ignition fan level) and at the 
same time starts ignition coil warmed up for about 3 min and the Green diode on the selected 
power button will Flash at the same time as the yellow diode lights up. See the functional diagram. 
About 3 min after start the electrical coil power reduces to maintain a constant temperature of coil 
(about 750 °C). The ignition coil switches off after about 7 min. Through the start-up uses ignition 
fan level – which is factory set to 87 V. 

Ignition occurs normally after 3 -4 min. After 5 min starts pellets feeding (first with longer pauses, 
and then more often) and the fan starts blowing with more frequent pulses and then switch to 
continuous speed. The whole start-up phase takes about 13 minutes. 

 

 

 

 

Operation :  

After the start-up phase, shifts it to the selected power level with preset feeding and fan speed. 
Green diode on the selected power button will shine. 

Now we can start adjustment at the different levels. 

 

Feeding (quantity of distributed fuel) in each power level can be changed (see Chapter 5). The 
feeding pulse is normally 1 second and with various breaks in the respective power level available 
different quantities of pellets. 

Air flow can be adjusted by adjusting the voltage to the fan in each level individually, so that a good 
combustion is obtained.  

 

Содержание Flex-a

Страница 1: ...Installation and Maintenance Instructions Janfire Flex 2a Installation Service Pellet burner Janfire Flex a 11899043 R2 SV Janfire 2009...

Страница 2: ...Janfire 2009 2 19 Due to constant development Janfire AB reserves the right to change part or parts of this publication at any time without notice Janfire AB assumes no responsibility for errors or d...

Страница 3: ...and Service 5 1 4 Safety Systems 6 1 5 CE declaration 6 2 Technical Data 7 3 Operational Description 8 3 1 Pellet burner Flex a 9 3 2 Control panel 11 3 3 Adjustment of various parameters 12 3 4 Adju...

Страница 4: ...rsonnel and in accordance to local standards and regulations When unpacking the burner should be checked for any damage If any parts are damaged contact the installing contractor The local chimney swe...

Страница 5: ...e warning texts are in hierarchical order The text DANGER also includes the possibility of the events covered by WARNING or CAUTION 1 3 Safety Instructions for Installation and Service All electrical...

Страница 6: ...r has begun to leak then it has to be replaced Feeding hose of plastics of a special type The hose between the external screw and the burner is made of plastics so that it shall melt away not burn at...

Страница 7: ...gnition coil 1000 W Pellet storage volume Internal storage 3 liter 1 8 kg Internal dosage motor 15 W Combustion fan 60 W Variable speed operation Control panel Touch button Fuses 6 A circuit breaker 6...

Страница 8: ...re rises to the highest allowed level 140 C shuts the burner down If it still is too hot the water safety device blows The power is determined by the chosen power level and is adjusted by the thermost...

Страница 9: ...d during installation Burner output can thereby easy be changed for most effective operation 2 Good combustion with high efficiency and low wastes are achieved through that a small internal auger be a...

Страница 10: ...r ash removal and cleaning It can easily be moved out of the boiler and avoid heavy lifting Simple quick lock fasteners great for cleaning and ash removal 7 Janfire flex a can be obtained and adapted...

Страница 11: ...power 1 9 kW power M Manuell operation 15 kW Note Ext Dos buttons can only be activaded in Stop Mode Ex t Manuel operating of extern motor Dos Manuel operating of dosing motor DIODER Power indication...

Страница 12: ...er heating alarm requires that the burner has been cooled the Switch itself are automatically reset when the temperature in the burner falls down to normal levels Elspiral Ignition coil broken ignitio...

Страница 13: ...wer mode 1 60V 2 Fan setting for the power mode 2 75V 3 Fan setting for the power mode 3 90V 4 Fan setting for the power mode 4 120 M fan setting for ignition 87V Connect the voltmeter to the undersid...

Страница 14: ...ers settings mode Time is normally 2 min Only alarm diode at the bottom extern motor shine One press to Dos increase time for 1 min and turn on one diode more One press to Ext decrease time for 1 min...

Страница 15: ...e If burner starts when the water temperature is higher or even just below the thermostat switched off the burner goes on standby for at least 35 min safety time if the thermostat still switched off I...

Страница 16: ...nition fan level which is factory set to 87 V Ignition occurs normally after 3 4 min After 5 min starts pellets feeding first with longer pauses and then more often and the fan starts blowing with mor...

Страница 17: ...Installationsanvisning Janfire Flex a IA Br nnare Flex a R2 SV Janfire 2009 17 19 4 Inkopplingsschema El...

Страница 18: ...Installationsanvisning Janfire Flex a IA Br nnare Flex a R2 SV Janfire 2009 18 19...

Страница 19: ...Installationsanvisning Janfire Flex a IA Br nnare Flex a R2 SV Janfire 2009 19 19 Anteckningar...

Отзывы: