Jandy

®

 Pro Series, LXi Maintain Heat Relay   

|

   Installation Kit Instructions

INTERMATIC

®

 MODEL T104 MECHANICAL TIMER

(NOT PROVIDED IN THIS KIT)

INTERMATIC MODEL T104 (NOT PROVIDED WITH HEATER OR KIT) WIRE CONNECTIONS SHOWN AS AN EXAMPLE,

OTHER MODELS MAY HAVE DIFFERENT CONNECTIONS. CONSULT TIMER MANUFACTURER FOR PROPER CONNECTIONS.

FIELD INSTALLED COMPONENTS

OPTIONAL HEATER COMPONENTS

MAINTAIN HEAT (PUMP) RELAY

(SEE HEATER WIRING DIAGRAM)

240 VAC

PUMP

CLOCK

MOTOR

NOTE:

EQUIPMENT

GROUND

L2

L1

1

3

2

4

SPA

MENU

POOL

GAS HEATER IS OFF

PRESS POOL OR SPA

Figure 4. Main Control Panel

B. 

Configure the Universal Controller for 

the Maintain Heat Feature

1.  Maintain Temperature

a. 

Make sure the control is in the 

OFF

 mode. See 

Figure 4.

b. 

To enter the Service Setup mode, press and hold 

the 

MENU, POOL 

and

 SPA

 buttons for five (5) 

seconds. 

NOTE

  The display will revert back to

 OFF

 after one (1) 

minute since the last key press.

c. 

When connected, this option allows the heater 

to control the pump even if the time clock 

has turned the pump off. To select Maintain 

Temperature, use the 

Up

 or 

Down

 button to 

display 

MAINTAIN TEMP

Press the 

MENU 

button. The 

DISABLE 

(default 

mode) appears, use the

 

Up

 or 

Down

 

button to 

scroll to 

ENABLE

, press the 

MENU 

button to 

select.

 

Press 

POOL 

or

 SPA 

to exit the Service 

Setup mode.

2.  Maintain Temperature Delay

a. 

Make sure the control is in the 

OFF

 mode.

b. 

To enter the Service Setup mode, press and hold 

the 

MENU, POOL 

and

 SPA

 button for five (5) 

seconds. 

NOTE

  The display will revert back to 

OFF

 after one (1) 

minute since the last key press.

c. 

The maintain temperature delay is used when 

MAINTAIN TEMP

 

is connected

This feature 

allows for a time delay before the pump is 

turned on.  To select Maintain Temperature 

Delay, use the

 

Up

 or 

Down

 

button to scroll 

through to display 

MAINTAIN TEMP DELAY

Press the 

MENU 

button. The 

01:00 HRS 

(default time) appears, use the

 

Up

 or 

Down

 

button to scroll to display the desired time delay, 

press the

 

MENU 

button to select

Press 

POOL 

or

 SPA

 

to exit the Service Setup mode. 

Figure 3.  Maintain Heat (Pump) Relay