Pro Series, LXi Maintain Heat Relay
|
Installation Kit Instructions
INTERMATIC
®
MODEL T104 MECHANICAL TIMER
(NOT PROVIDED IN THIS KIT)
INTERMATIC MODEL T104 (NOT PROVIDED WITH HEATER OR KIT) WIRE CONNECTIONS SHOWN AS AN EXAMPLE,
OTHER MODELS MAY HAVE DIFFERENT CONNECTIONS. CONSULT TIMER MANUFACTURER FOR PROPER CONNECTIONS.
FIELD INSTALLED COMPONENTS
OPTIONAL HEATER COMPONENTS
MAINTAIN HEAT (PUMP) RELAY
(SEE HEATER WIRING DIAGRAM)
240 VAC
PUMP
CLOCK
MOTOR
NOTE:
EQUIPMENT
GROUND
L2
L1
1
3
2
4
SPA
MENU
POOL
GAS HEATER IS OFF
PRESS POOL OR SPA
Figure 4. Main Control Panel
B.
Configure the Universal Controller for
the Maintain Heat Feature
1. Maintain Temperature
a.
Make sure the control is in the
OFF
mode. See
Figure 4.
b.
To enter the Service Setup mode, press and hold
the
MENU, POOL
and
SPA
buttons for five (5)
seconds.
NOTE
The display will revert back to
OFF
after one (1)
minute since the last key press.
c.
When connected, this option allows the heater
to control the pump even if the time clock
has turned the pump off. To select Maintain
Temperature, use the
Up
or
Down
button to
display
MAINTAIN TEMP
.
Press the
MENU
button. The
DISABLE
(default
mode) appears, use the
Up
or
Down
button to
scroll to
ENABLE
, press the
MENU
button to
select.
Press
POOL
or
SPA
to exit the Service
Setup mode.
2. Maintain Temperature Delay
a.
Make sure the control is in the
OFF
mode.
b.
To enter the Service Setup mode, press and hold
the
MENU, POOL
and
SPA
button for five (5)
seconds.
NOTE
The display will revert back to
OFF
after one (1)
minute since the last key press.
c.
The maintain temperature delay is used when
MAINTAIN TEMP
is connected
.
This feature
allows for a time delay before the pump is
turned on. To select Maintain Temperature
Delay, use the
Up
or
Down
button to scroll
through to display
MAINTAIN TEMP DELAY
.
Press the
MENU
button. The
01:00 HRS
(default time) appears, use the
Up
or
Down
button to scroll to display the desired time delay,
press the
MENU
button to select
.
Press
POOL
or
SPA
to exit the Service Setup mode.
Figure 3. Maintain Heat (Pump) Relay